General Precautions on Wiring

1. Specifications

1-11. ELECTRICAL WIRING

General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.

(3)To prevent possible hazards from insulation failure, the unit must be grounded.

(4)Each wiring connection must be done in accordance with the wiring system diagram.

Wrong wiring may cause the unit to misoperate or become damaged.

(5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

1(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no

responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

(7)Regulations on wire diameters differ from locality to locality. For field wiring rules, must follow your LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all relevant rules and regulations.

(8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

Outdoor Unit The remote control wiring and the inter-unit control wiring should be wired apart from the inter- unit power wiring.

Type Use shielded wires for inter-unit control wiring between units and ground the shield on one side only.

(9)If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacturer, because special-purpose tools are required.

(10)All wiring used must be Class 1.

Recommended Wire Length and Wire Diameter for Power Supply System

You must follow LOCAL ELECTRICAL CODES for wiring.

Outdoor Unit

Type

Time delay fuse or

circuit capacity

 

U-26PE1U6

30 A

U-36PE1U6

35 A

U-42PE1U6

40 A

Type

Time delay fuse or

circuit capacity

 

U-26PS1U6

25 A

U-36PS1U6

30 A

U-42PS1U6

35 A

Indoor Unit

 

 

 

 

 

 

 

 

 

 

Type

 

Time delay fuse or

 

 

 

 

 

 

 

 

circuit capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1, K1, T1, F1

 

15 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Wiring

 

 

 

 

 

 

 

 

 

 

(A) Inter-Unit Control Wiring

 

(B) Remote Control Wiring

(C) Control Wiring For Group Control

 

 

 

 

 

 

 

 

 

 

 

 

AWG #18

 

 

* 2

2

)

AWG #18

* 2

2

)

Use high voltage wire (300 V)*1

 

AWG #18

(0.75 mm

 

- (0.75 mm

Max. 3,300 ft.

 

 

Max. 1,650 ft.

 

Max. 650 - ft. (Total)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWG=American Wire Gauge

*1 With ring-type wire terminal *2 Wire joint connection

1-60