TECHNICAL DATA & SERVICE MANUAL
Indoor Unit
Outdoor Unit
Model No
SPECIAL PRECAUTIONS
Please Read Before Starting
When Transporting
When Installing…
Others
When Servicing
Check of Density Limit
Manifold gauge Vacuum pump
1. Care regarding tubing
3. Different tools required
Fig.
Configuration and characteristics of cylinders
Fig.
Section 1: SPECIFICATIONS
Section 4: SERVICE PROCEDURES
Section 2: PROCESSES AND FUNCTIONS
Section 3: ELECTRICAL DATA
1. SPECIFICATIONS
TENTATIVE
1. Specifications 1-1Unit Specifications
4-WayCassette Type
POWER SOURCE
FEATURES
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
Wall Mounted Type
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
Ceiling Type
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
Low Silhouette Duct Type
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications 1-1Unit Specifications
POWER SOURCE
FEATURES
DIMENSIONS & WEIGHT
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
Remote controller Optional / Supplied
A Indoor Unit
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
A Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1. Specifications
1-2Major Component Specifications
Remote controller Supplied / Optional
A Indoor Unit
1. Specifications
1-2Major Component Specifications
Remote controller Supplied / Optional
A Indoor Unit
1-2Major Component Specifications B Outdoor Unit
1. Specifications
U-36PE1U6
1. Specifications
1-2Major Component Specifications B Outdoor Unit
P-42PE1U6
1. Specifications
1-2Major Component Specifications B Outdoor Unit
1. Specifications
1-2Major Component Specifications B Outdoor Unit
U-36PS1U6
1. Specifications
1-2Major Component Specifications B Outdoor Unit
1. Specifications
1-2Major Component Specifications B Outdoor Unit
1-3Other Component Specifications Outdoor Unit
1. Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1-35
1. Specifications
1-3Other Component Specifications Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1-36
1. Specifications
1-3Other Component Specifications Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1-37
1. Specifications 1-4Dimensional data
Indoor unit : 4-WayCassette Type 26 Type
1. Specifications
1-4Dimensional data
Indoor unit : 4-WayCassette Type 36, 42Type
Indoor unit : Wall Mounted Type
1-4Dimensional data
1. Specifications
Drain and wiring port 3-5/32
Indoor unit : Ceiling Type 26 Type
1. Specifications 1-4Dimensional data
Indoor unit : Ceiling Type 36, 42 Type
1. Specifications 1-4Dimensional data
Indoor unit : Low Silhouette Duct Type 26 Type
1. Specifications 1-4Dimensional data
Indoor unit : Low Silhouette Duct Type 36 Type
1. Specifications 1-4Dimensional data
Indoor unit : Low Silhouette Duct Type
1. Specifications 1-4Dimensional data
1. Specifications 1-4Dimensional Data
B Outdoor Unit: U-42PE1U6, U-42PS1U6
1. Specifications 1-4Dimensional Data
1-5Refrigerant Flow Diagram
Outdoor Unit : U-26PE1U6, U-26PS1U6
Indoor Unit : 26, 30, 36 Types
U-36PE1U6, U-36PS1U6
Outdoor Unit: U-42PE1U6, U-42PS1U6
1-6Operating Range
1. Specifications
1-5Refrigerant Flow Diagram
1. Specifications
U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6
U-42PE1U6, U-42PS1U6
1. Specifications 1-8Noise Criterion Curves
4-WayCassette Type
1. Specifications 1-8Noise Criterion Curves
208 - 230 V, 1 Phase, 60 Hz
Wall Mounted Type
S-26PK1U6
MODEL
1. Specifications 1-8Noise Criterion Curves
Ceiling Type
Low Silhouette Duct Type
1-8Noise Criterion Curves
1. Specifications
Outdoor Units
1. Specifications 1-8Noise Criterion Curves
1. Specifications 1-9Increasing the Fan Speed
How to read the diagram
Indoor Fan Performance
26 Type
1-10Air throw distance chart 4-WayCassette Type
1. Specifications
Model: 26 Type
Model: 36, 42 Type
1. Specifications 1-10Air throw distance chart
Wall Mounted Type
1-10Air throw distance chart Ceiling Type
1. Specifications
Model: 26 Type
Model: 36 Type
1. Specifications
General Precautions on Wiring
Time delay fuse or
Time delay fuse or
1. Specifications
Wiring System Diagrams
Outdoor Unit
Indoor Unit U1, T1, F1 Types
1. Specifications
How to Connect Wiring to the Terminal
For stranded wiring
Fig.
1. Specifications
Outdoor Unit 1. Tubing Size
Table
Indoor unit type
1. Specifications
2. Check of density limit
1. Specifications
3. SELECTING THE INSTALLATION SITE
Installation space
Installation requirements
1. Specifications
3-3.Installing the Unit in Heavy Snow Areas
3-2. Air-DischargeChamber for Top Discharge
Countermeasures against snow and wind
1. Specifications
3-5.Dimensions of Wind Ducting
For U-26PES1U6 / U-36PES1U6unit
For U-42PES1U6unit
1. Specifications
U-42PES1U6unit
Wind
direction
Required space around outdoor unit
1. Specifications
U-26PES1U6 / U-36PES1U6 / U-42PES1U6
For U-42PES1U6unit
1. Specifications
3-6.Dimensions of Snow Ducting
1. Specifications
U-42PES1U6unit
1. Specifications
Reference diagram for snow-proofvents –
Space requirements for setting –
U-26PES1U6 / U-36PES1U6 / U-42PES1U6
1. Specifications
Reference diagram for snow-proofvents –
Space requirements for setting –
Installation in front-rearrows
4. HOW TO INSTALL THE OUTDOOR UNIT
1. Specifications
4-1.Installing the Outdoor Unit
4-3.Routing the Tubing and Wiring
1. Specifications
Indoor Unit 5. SELECTING THE INSTALLATION SITE
5-1.Indoor Unit AVOID
Ceiling Type
6. HOW TO INSTALL THE INDOOR UNIT
1. Specifications
4-WayCassette Type U1 Type
6-1.Suspending the Indoor Unit
1. Specifications
6-3.Placing the Unit Inside the Ceiling
Fig.
Fig.
1. Specifications
6-4.Installing the Drain Piping
Fig.
Fig.
1. Specifications
6-5.Checking the Drainage
ing to the outdoor unit are completed
the drainage
1. Specifications
6-6.Before Installing the Ceiling Panel
Ceiling Panel
Fig.
6-8.When Removing the Ceiling Panel for Servicing
1. Specifications
6-7.Installing the Ceiling Panel
1. Specifications
1 Accessories
2 Installation
a Installing the air-intakeplenum
1. Specifications
d Installing the ceiling panel
ceiling
Fig.
1. Specifications
trical wiring or conduits are
Wall Mounted Type K1 Type
6-10.Removing the Wall Fixture from the Unit
1. Specifications
6-12.Installing the Rear Panel on the Wall
a If Wooden Wall
b If Block, Brick, Concrete or Similar Type Wall
1. Specifications
How to remove the grille
How to replace the grille
6-14.Preparing the Indoor Side Tubing
1. Specifications
6-15.Wiring Instructions
General Precautions on Wiring
How to remove the cover plate
1. Specifications
6-18.Installing the Drain Hose
wiring to the outdoor unit are completed
6-17.Shaping the Tubing
1. Specifications
Ceiling Type T1 Type
6-19.Suspending the Indoor Unit
Fig.
1. Specifications
Fig.
Fig.
Fig.
1. Specifications
Fig.
Fig. Fig.
Fig.
1. Specifications
6-21.Installing the Drain Piping
6-20.Duct for Fresh Air
Fig.
1. Specifications
Low Silhouette Ducted Type F1 Type
Table
Fig.
1. Specifications
enough to support the weight
6-23.Suspending the Indoor Unit
It is important that you use
1. Specifications
Fig. 6-24.Installing the Drain Piping
Tighten the hose clamps so
their locking nuts face upward
1. Specifications
when you short the pin on the
6-25.Checking the Drainage
Be careful since the fan will start
1. Specifications
How to read the diagram
HT : Using the booster cable
6-26.Increasing the Fan Speed
1. Specifications
6-27.When Installing the Indoor Unit
Fig.
Fig.
1. Specifications
Checkpoint after installation
Symptom
SUPPLEMENT ON DRAIN PIPING
7. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER
1. Specifications
7-1.Wireless Remote Controller Installation
How to Install Batteries
1. Specifications
7-2.Room Temperature Sensor Setting
Fig. 7-3.Address Switches
7-4.Setting the Model Code
1. Specifications
7-5.Indicator Section Installation
1 7-6.Operating Controller Installation
controller wires together
1. Specifications
7-7.Indicator Section Installation
7-8.Operating Controller Installation
Ceiling Type T1 Type
1. Specifications
7-9.Electrical Wiring
7-10.Test Run Switch
Fig.
1. Specifications
7-11.Misoperation Alarm Indicators
Alarm
Table
1. Specifications
controller wires together
with the power supply
wires. Doing so can result
1. Specifications
Fig.
Fig.
Fig.
1. Specifications
7-13.Electrical Wiring
7-14.Test Run Switch
To avoid placing an
1. Specifications
7-15.Misoperation Alarm Indicators
8. Transmitter 9. Remote control sensor
10. Temperature setting buttons
1. Specifications
7-16.Basic Wiring Diagram
Be sure to do the wiring
correctly incorrect wiring
1. Specifications
7-17.Wiring System Diagram for Group Control
Group control using 2 signal receiving units
Wiring procedure
1. Specifications
When installing multiple remote controllers
Setting method
1Basic wiring diagram
1. Specifications
<CZ-RWSK1U> 7-19.Test Run Procedure
Wireless remote controller transmitter
Wall mounted Type K1 Type
1. Specifications
7-21-1.Changing the room temperature sensor
7-21-2.Using the remote controller
Using the controller
1. Specifications
7-22.Precautions
Indoor unit control PCB
Outdoor unit control PCB
1. Specifications
S-26PK1U6
Nos. 1, 2 OFF, No. 3 ON
Nos. 1, 2, 3 all OFF
1. Specifications
7-24.Diagnosis Table
Cause
Indoor unit
1. Specifications
Flaring Procedure with a Flare Tool
Fig.
Fig.
1. Specifications
Caution Before Connecting Tubes Tightly
Cautions During Brazing
Fig.
1. Specifications
Precautions for Packed Valve Operation
Never grasp the drain or refrigerant connecting
outlets when moving the unit
1. Specifications
5. Finishing the Installation
4. Taping the Tubes
Fig.
1. Specifications
Manifold gauge Fig. Vacuum pump
Fig.
1. Leak Test
1. Specifications
2. Evacuation
Use a cylinder specifically
designed for use with R410A
1. Specifications
3. Charging Additional Refrigerant
4.Finishing the Job
R410A
Room Temperature Control
2. PROCESSES AND FUNCTIONS
2-2Cold Draft Prevention Heating Cycle
2-3Automatic Fan Speed Indoor Unit
2-1Room Temperature Control
2. Processes and functions
A Cooling
Fig. Chart Summary and Explanations
2. Processes and functions B Heating
Fig. Chart Summary and Explanations
2-2Cold Draft Prevention Heating Cycle
2. Processes and functions
2-3Automatic Fan Speed Indoor Unit
B Heating
2. Processes and functions
A Cooling
2-4Control Functions
2.Processes and functions
Discharge temperature release control
Current release control
Freeze prevention low-temperaturerelease control
2. Processes and functions
Overcurrent protection control
Current release value shift control
2. Processes and functions
Defrost control
2. Processes and functions
2-5Outdoor Unit Control PCB
1 Layout Diagram CR-CH4872R
1 Explanation of Functions
2-6Outdoor Unit Control PCB CR-CH4272R
2. Processes and functions
Fig.
Table 1. Method of System Address Setting
2. Processes and functions
Page
Outdoor Units
3. ELECTRICAL DATA
Indoor Units
3-1Indoor Units
3. Electrical data
3. Electrical data
3. Electrical data
Wall Mounted Type : S-26PK1U6
3. Electrical data
Wall Mounted Type : S-26PK1U6
3. Electrical data
Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6
3. Electrical data
Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6
3. Electrical data
Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6
3. Electrical data
Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6
U-26PE1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
U-26PS1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
U-36PE1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
U-36PS1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
U-42PE1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
U-42PS1U6
3-2Outdoor Units
3. Electrical data
3-2Outdoor Units
3. Electrical data
Page
4. SERVICE PROCEDURES
4-1.Meaning of Alarm Messages
4-2.Symptoms and Parts to Inspect
4-3.Details of Alarm Messages
4. Service procedures
4-1.Meaning of Alarm Messages
Wired
Blinking
4. Service procedures
Wired
Wireless
remote
4. Service procedures
Remarks
4. Service procedures
4-2.Symptoms and Parts to Inspect
Alarm
contents
4. Service procedures
Alarm
contents
Judgment condition
4. Service procedures
Alarm
contents
Judgment condition
4. Service procedures
4-3.Details of Alarm Messages
1 Alarm “P29”
Input power detection circuit trouble
HIC PCB trouble
4. Service procedures
2 Alarm “P26”
4. Service procedures
3 Alarm “E31”
HIC-CH4872R
HIC-CH2672R
4. Service procedures
4 Alarm P22
4. Service procedures
5 Alarms “F04,” “F06,” “F07,” “F08,” “F12”
4. Service procedures
<Check procedure>
Sensor Temperature Correlation Table
Sensor installation
4-4.Table of Thermistor Characteristics
4. Service procedures
Check Pin
1 Outdoor Air Temp. TO, Intake Temp. TS, Heat
5. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL
Temperatures
Alarm History
5-1.Overview
5. Outdoor unit maintenance remote control
System diagram
Temperature monitor
Outdoor unit alarm history monitor
5. Outdoor unit maintenance remote control
5-3.Normal Display Operations and Functions
Normal display functions
All units start/stop Fig. 1 <Operation>
Display contents
3XX-YYR.C
XX= Main bus line outdoor system address 1 –
Item code
5. Outdoor unit maintenance remote control
button
5. Outdoor unit maintenance remote control
5. Outdoor unit maintenance remote control
5. Outdoor unit maintenance remote control
List of Item Codes
Item code
Parameter
5. Outdoor unit maintenance remote control
Setting mode 2 <Operating procedure>
Refrigerant type
5. Outdoor unit maintenance remote control
List of Item Codes
6-3.TestRun Procedure
6-5.TestRun Using the Remote Controller
6-6.Precautions
6-8.Examples of Wiring Diagrams
6. TEST RUN 6-1.Preparing for Test Run
6. Test run
Fig.
Fig.
Fig.
6. Test run U1, K1, T1, F1 Type 6-2.Caution
6-3.TestRun Procedure
6-5.Test Run Using the Remote Controller
6-6.Precautions
6-4.Items to Check Before the Test Run
6. Test run
Wired remote
6. Test run
Cause
Indoor unit
Fig.
6. Test run 6-8.Examples of Wiring Diagrams
Basic wiring diagram
Basic wiring diagram
Fig. 6-6a Wiring procedure
6. Test run
Fig. 6-6b
Fig.
Setting the outdoor unit system addresses
6. Test run
6. Test run
Main-subremote controller control
Remote controller setting mode