7-24. Diagnosis Table

1-117

7-24. Diagnosis Table

 

 

 

 

 

 

 

Cause

 

Wired remote

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simultaneous-operation multi system

Control by main-sub

spcontroller dilay

receiver lamp

 

1:1 connection (single type)

 

Group connection

 

 

 

(flexible combination)

remote controllers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nothing is

Nothing is

Remote controller is not connected correctly.

Remote controller is not connected with

Same as at left

Same as at left

Indoor unit power is not ON.

indoor unit correctly

 

 

 

 

displayed

displayed

 

 

 

Indoor unit power is not ON.

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting has not been

Automatic address setting has not been

Same as at left

Same as at left

 

 

completed.

completed.

 

 

 

 

E 0 1 displayed

 

Inter-unit control wiring is cut or is not

Inter-unit control wiring is cut or is not

 

 

 

 

 

connected correctly.

connected correctly.

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller is not connected correctly

Remote controller is not connected with

 

 

 

 

 

 

(remote controller receiving failure).

indoor unit correctly

 

 

 

 

E 0 2 displayed

Operating lamp

Remote controller is not connected correctly

Remote controller is not connected with

Same as at left

Same as at left

is blinking.

(failure in transmission from remote controller

indoor unit correctly

 

 

 

 

 

 

to indoor unit).

 

 

 

 

 

 

 

E 0 9 displayed

 

 

 

 

 

 

 

 

 

 

2 remote controllers are

 

 

 

 

 

 

 

 

 

 

set as the main remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller.

E 1 4 displayed

 

 

 

 

 

 

 

Control wiring for group control is cut or

Same as at left

 

 

 

 

 

 

 

is not connected correctly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 0 4 displayed

 

Indoor-outdoor inter-unit wiring is not

Same as at left

Same as at left

Same as at left

 

connected correctly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor-outdoor inter-unit wiring is cut or

Same as at left

Same as at left

 

 

 

 

 

E 0 6 displayed

Standby lamp

 

 

 

is not connected correctly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is blinking.

 

 

 

 

 

 

 

 

 

 

E 1 5 displayed

Indoor unit capacity is too low.

Same as at left

Same as at left

Same as at left

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 1 6 displayed

 

Indoor unit capacity is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E 2 0 displayed

 

No serial signal is being received at all from

 

 

 

 

 

 

 

 

the indoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P 0 5 displayed

Operation lamp and

Inter-unit circuit or open phase in the outdoor

Reversed phase or open phase in the

Reversed phase or open phase in the

Same as at left

Standby lamp are

unit power

3-phase power at one of the outdoor

outdoor unit 3-phase power

 

 

blinking alternately.

Insufficient gas

units in the group

 

 

 

 

L 0 2 displayed

Both the Operation

Indoor-outdoor unit type mismatch

Same as at left

Same as at left

 

L 1 3 displayed

lamp and Standby

 

 

 

 

 

 

 

 

 

 

 

lamp are blinking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control wiring for group control is connected

Same as at left

L 0 7 displayed

together.

 

 

 

 

 

 

 

 

 

 

 

 

 

to the indoor unit, however it is set for individual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.

 

P 0 9 displayed

Timer lamp and

The indoor unit ceiling panel connector is not

Ceiling panel connector at one of the

Indoor unit ceiling panel connector is not

Same as at left

Standby lamp are

connected correctly.

indoor units in the group is not

connected correctly.

 

 

blinking alternately.

 

 

 

connected correctly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 