Panasonic R410A service manual Specifications, U-26PES1U6 / U-36PES1U6 / U-42PES1U6

Models: R410A

1 198
Download 198 pages 33.93 Kb
Page 75
Image 75
U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6

1. Specifications

Reference diagram for air-discharge chamber (field supply)

U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6

Required space around outdoor unit

If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.

If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

39-3/8

Min. 7-7/8

Min.

 

Unit: inch

CAUTION

The top and both sides must remain open. If there are obstacles to the front and rear of

 

the outdoor unit, the obstacle at either the front or rear must be no taller than the height of

1

the outdoor unit.

 

(2)Multiple-unit installation Required space around outdoor unit Installation in lateral rows

CAUTION

More than 11-13/16

More than 11-13/16

than 15-3/4

More

More than 7-7/8

 

 

 

Unit: inch

The front and top must remain open.

The obstacles must be no taller than the height of the outdoor unit.

Installation in front-rear rows

 

Installation with intakes facing outlets

Installation with intakes facing

 

intakes or outlets facing outlets

More than 15-3/4

 

More than 59-1/16

More than 78-3/4

CAUTION

Unit: inch

The front and both sides must remain open.

1-69

Page 75
Image 75
Panasonic R410A service manual Specifications, U-26PES1U6 / U-36PES1U6 / U-42PES1U6, Required space around outdoor unit