DCS 500 11003, = decrease so that motor voltage is 70%, = decrease so that motor voltage is 40%

Page 30

Chapter 2 - Start-Up Instructions

12522 = decrease so that motor voltage is 90 %. Flux and thus the field current as well are reduced.

How to proceed:

1.decrease 12522 (in steps of 100 at a time)

2.press ACT, read off motor voltage

3.press PAR and correct 12522 if necessary (then continue with 2.) Read out and note down value of:

11003

=

(will later be entered in 1015)

 

 

12522

= decrease so that motor voltage is 70%.

Flux and thus the field current as well are reduced.

 

Proceed as described in (1. / 2. / 3.) above!

Read out and note down value of:

11003

=

(will later be entered in 1014)

 

 

 

 

12522

= decrease so that motor voltage is 40%.

Flux and thus the field current as well are reduced.

 

Proceed as described in (1. / 2. / 3.) above!

Read out and note down value of:

11003

=

(will later be entered in 1013)

 

 

 

 

 

 

12522

= 4095

 

12516

= 0

 

Internal reference value equal to zero.

Switch OFF power, thus stopping the drive!

1002 = 12512

1004 = 0

1009 = 10%

1010 = - 99%

As-delivered values (default values) for all 4 parameters restored. 1015 = equal to the 1st value of 11003

1014 = equal to the 2nd value of 11003

1013 = equal to the 3rd value of 11003 Linearization function matched to field circuit.

501 = 90 % of the rated motor voltage.

1012 = 90 % of the value on the motor rating plate.

This measure serves to provide a greater safety margin for the motor voltage during start-up.

IV A 2 - 18

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 30
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsIncoming inspection Storage and transportRating plate Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageConv.fan curr.fault Earth faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000