Chapter 4 - Signals and Troubleshooting

4.5 Alarm Signals (A)

The alarm signals will be shown on the seven segment display of the control board SDCS-CON-x as codes A . . as well as on the LCD of the control panel CDP 31x as plain text. Alarm signals will only be displayed, if there is no fault signal active.

The alarm signals - with the exception of A 101 and A 102 - will not result in switching off the signal 10910 resp. in stopping the drive.

 

Code

 

 

Text on

 

Definition /

 

Signal

 

Remark

 

seven

 

 

LCD of control panel

 

Possible source

 

number

 

 

 

segm.

 

 

CDP 31x

 

 

 

(ALARM_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 101

 

Start inhibition

 

Alarm Start Inhibition

11104

bit 0

 

 

 

 

 

 

 

Pin 908 (START_INHIBIT) is set to logical

 

 

 

 

 

 

 

 

 

 

 

"1“; drive cannot be switched ON.

 

 

 

 

 

 

 

 

 

 

 

When pin is set to logical "0“, the alarm sig-

 

 

 

 

 

 

 

 

 

 

 

nal will be reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 102

 

Emergency stop

 

Alarm EMERGENCY STOP

11104

bit 1

 

 

 

 

 

 

 

Pin 906 has a logical "0" level; for signal re-

 

 

 

 

 

 

 

 

 

 

 

set, see introductory remarks in Chapter 4.4

 

 

 

 

 

 

 

 

 

 

 

"Fault Signals“ and Chapter 3.7 "EMER-

 

 

 

 

 

 

 

 

 

 

 

GENCY STOP RESETTING“.

 

 

 

 

 

 

 

 

 

 

 

 

A 103

Motor 1 temp. alarm

 

Alarm Overtemperature MOTOR 1

11104

bit 2

 

 

 

 

 

 

 

Check: - Parameter setting MOT1.TEMP_

 

 

 

 

 

 

 

 

 

 

 

ALARM_L [P 1402] correct?

 

 

 

 

 

 

 

 

 

 

 

See also Fault Code F 6.

 

 

 

 

 

 

 

 

 

 

 

 

A 104

Motor 1 overl.alarm

 

Alarm Overload MOTOR 1 (Thermal Model 1)

11104

bit 3

 

 

 

 

 

 

 

Check: - See Fault Code F 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 105

 

Conv. overtemp.

 

Alarm Overtemperature Power Section

11104

bit 4

 

 

 

 

 

alarm

 

This signal will already appear at approx.

 

 

 

 

 

 

 

 

 

 

 

10 °C below the shutdown temperature ap-

 

 

 

 

 

 

 

 

 

 

 

plying for Fault Signal F 4 (see P 10512).

 

 

 

 

 

 

 

 

 

 

 

Check: - See Fault Code F 4.

 

 

 

 

 

 

 

 

 

 

 

 

A 106

Current reg blocked

 

Alarm Current Regulator/Controller blocked

11104

bit 5

 

 

 

 

 

 

 

Pin 404 (BLOCK) is set to logical "1“.

 

 

 

 

 

 

 

 

 

 

 

When pin is set to logical "0“, the alarm sig-

 

 

 

 

 

 

 

 

 

 

 

nal will be reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 12

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 64
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions How to use this manual Contents of this manualTarget group Associated publicationsStorage and transport Incoming inspectionRating plate General notes How this chapter is structuredRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 518 = 500 V fixed! rated power converter voltage Set this only for units of the DCP 500 series519 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET 1002 =1004 = 1009 = 1010 =11003 = decrease so that motor voltage is 70%Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed1708 = 0,1 s 1709 = 0,1 s 1204 POT1 = 10%...20% max. speed408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 1201 = 5Panel display FEX2/3 Autotuning 3601 =3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysSpeed Reference Setting for the Drive To enter the Reference SettingTo exit the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageEarth fault Conv.fan curr.faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWExt.Overvolt.Fault Local & disconNected Limited by the activation of a free wheeling CircuitMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple See Fault Code F No ext. FAN ackNo main cont. ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceAlarm Signals a 103 Motor 1 temp. alarmCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition108 110118 120127 128129 130134 136137 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000