Chapter 2 - Start-Up Instructions
General notes
CAUTION: it is absolutely essential that the applicable accident prevention regulations be observed by the user (in this context, please also read the chapter entitled "Safety Instructions")!
How this chapter is structured
For better understanding the individual steps of
These steps of
Example:
522 = GERMAN [Only with the
Activates German texts on the display ...........
b) frames with marking on the left side („columns“ shaded in grey):
These steps of
Example:
Only when connection diagram 1 (Appendix A) is being used!
906 = 12502
Function „EMERGENCY STOP“
Recommended motor voltages and field voltages
•Motor voltage UA when the following units are used
DCS 501B / DCP 501B: | UAmax | = Line voltage * 1.16 | (2- quadrant unit) |
DCS 502B / DCP 502B: | UAmax | = Line voltage * 1.05 | (4- quadrant unit) |
•Field voltage UF (= max. output voltage) when the following is being used
SDCS-FEX-1:
If there is a divergence of more than 10 % between the field supply unit's output
voltage and the rated field voltage UFrated stated on the motor's rating plate, then the connecting voltage UN should be reduced, using a matching transformer or a series
resistor Rv:Rv = (0.9 * UN - UF) / IFIF = Rated field current
(Note: also suitable for
•Field voltage UF when the following is being used
DCF 503 / DCF 504:
•Field voltage UF when the following is being used
DCF 501B / DCF 502B:
Maximally possible output voltage UAmax using
DCF 501B / DCF 502B:
DCS 500B / DCP 500B Operating Instructions | IV A 2 - 1 |
3ADW000055R0401_DCS500B_Operating Instruction_e_d