Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

 

Definition /

 

 

Signal

 

Remark

 

seven

 

 

LCD of control panel

 

 

Possible source

 

 

number

 

 

 

segm.

 

 

 

 

 

CDP 31x

 

 

 

 

 

(ALARM_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 134

Backup not allowed

 

 

Alarm Change of Parameter Set not allowed

 

11105

bit 4

 

 

 

 

 

 

 

 

Signal will appear when an attempt has

 

 

 

 

 

 

 

 

 

 

 

 

 

been made to change from Motor Set 1 to

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Set 2 or vice versa, e.g. while the mo-

 

 

 

 

 

 

 

 

 

 

 

 

 

tor shaft is turning or the line contactor is

 

 

 

 

 

 

 

 

 

 

 

 

 

switched on.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 136

Write backup alarm

 

 

Alarm Write Backup of Values in Non-Volatile

 

11105

bit 5

 

 

 

 

 

 

 

 

Memory failed

 

 

 

 

 

 

 

 

 

 

 

 

 

The attempt to save values in non-volatile

 

 

 

 

 

 

 

 

 

 

 

 

 

memory has failed;

 

 

 

 

 

 

 

 

 

 

 

 

 

parameter memory could not be erased.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Is Jumper S3 enabling the save

 

 

 

 

 

 

 

 

 

 

 

 

 

routine?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 137

Arm. current ripple

 

Armature current ripple

 

11105

bit 9

Can

 

 

 

 

 

 

One or several thyristors carry no current.

 

 

 

 

 

not be re-

 

 

 

 

 

 

 

 

 

 

 

set

 

 

 

 

 

 

Check: - Current feedback with oscilloscope

 

 

 

 

 

 

 

 

 

 

 

 

 

(6 pulses within one cycle visible?)

 

 

 

 

 

 

 

 

 

 

 

 

 

- Branch fuses, thyristor gate con-

 

 

 

 

 

 

 

 

 

 

 

 

 

nection; gate-cathode resistance.

 

 

 

 

 

 

 

 

 

 

 

 

 

- Sensitivity of monitoring function:

 

 

 

 

 

 

 

 

 

 

 

 

 

set CUR_RIPPLE_LIM [421] (de

 

 

 

 

 

 

 

 

 

 

 

 

 

pending on the methode; see F34)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 138

Init values read

 

 

Alarm Initializiation Values read

 

 

 

 

 

 

 

 

 

 

Default values have been loaded, using

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter [P 11202], Value 3 (FACTORY_

 

 

 

 

 

 

 

 

 

 

 

 

 

SET_VALUE); signal may only be entered in

 

 

 

 

 

 

 

 

 

 

 

 

 

the Fault Logger.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 140

 

Auto-reclosing

 

 

Auto-Reclosing (Self-Restart)

 

11105

bit 8

 

 

 

 

 

 

 

 

This alarm indicates when self-restart is per-

 

 

 

 

 

modified

 

 

 

 

 

 

 

formed. During that time the alarms F29,

 

 

 

 

 

in

 

 

 

 

 

 

 

 

 

 

 

 

S21.232

 

 

 

 

 

 

 

F31, F39 and F41 are suppressed. This

 

 

 

 

 

 

 

 

 

 

 

 

function is started when the line voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

drops below the alarm or error threshold,

 

 

 

 

 

 

 

 

 

 

 

 

 

when not in synchronism, no field or no line

 

 

 

 

 

 

 

 

 

 

 

 

 

contactor acknowledgement and with

 

 

 

 

 

 

 

 

 

 

 

 

 

PWR_LOSS_MODE [9.19] = enable and

 

 

 

 

 

 

 

 

 

 

 

 

 

PWR_DOWN_TIME [5.10] greater than

 

 

 

 

 

 

 

 

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 15

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 67
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Associated publications How to use this manualContents of this manual Target groupStorage and transport Incoming inspectionRating plate = Line voltage General notesHow this chapter is structured Recommended motor voltages and field voltagesMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals 11202 = Save MOT1 SET 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 5191305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1009 = 1010 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1004 == decrease so that motor voltage is 40% 11003= decrease so that motor voltage is 70% Proceed as described in 1. / 2. / 3. above12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1008 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 408 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3603 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3602 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveMode Speed Reference Setting for the DriveTo enter the Reference Setting To exit the Reference SettingDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FEarth fault Conv.fan curr.faultMotor 1 overtemp SDCS-IOB-3, SDCS-POW P418Limited by the activation of a free wheeling Circuit Ext.Overvolt.FaultLocal & discon NectedMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple Field ex.1 not OK See Fault Code FNo ext. FAN ack No main cont. ackIV a 4 Current Difference Reversal Fault101 Start inhibition Alarm Signals a103 Motor 1 temp. alarm Check See Fault Code F 105 Conv. overtemp120 108110 118130 127128 129138 134136 137At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000