Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

Definition /

 

Signal

 

Remark

 

seven

 

 

LCD of control panel

 

Possible source

 

number

 

 

 

segm.

 

 

 

 

 

CDP 31x

 

 

 

(ALARM_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 108

RAM-backup failed

 

Alarm No Battery Backup Function for RAM

11104

bit 7

 

 

 

 

 

 

 

Capacitor for RAM backup has discharged

 

 

 

 

 

 

 

 

 

 

 

(perhaps unit has been stored for too long

 

 

 

 

 

 

 

 

 

 

 

without the electronics voltage switched

 

 

 

 

 

 

 

 

 

 

 

on?); load capacitor by leaving unit electron-

 

 

 

 

 

 

 

 

 

 

 

ics switched on for a lengthy period.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A 110

System restart

 

Alarm System Restart

 

 

 

 

 

 

 

 

 

 

 

Signal is filed in fault memory (fault logger),

 

 

 

 

 

 

 

 

 

 

 

but not displayed at the unit or the LC-

 

 

 

 

 

 

 

 

 

 

 

Display of the CDP 31x.

 

 

 

 

 

 

 

 

 

 

 

 

A 118

Mains underv.alarm

 

Alarm Mains Undervoltage (AC)

11104

bit 10

 

 

 

 

 

 

 

Setting of undervoltage monitoring with Pa-

 

 

 

 

 

 

 

 

 

 

 

rameter [P 508]

 

 

 

 

 

 

 

 

 

 

 

Check: - See also Fault Code F 29.

 

 

 

 

 

 

 

 

 

 

 

 

A 120

Arm.curr.dev.alarm

 

Alarm Armature Current Deviation

11104

bit 13

 

 

 

 

 

 

 

If the current reference [P 10405] deviates

 

 

 

 

 

 

 

 

 

 

 

from the current feedback for more than

 

 

 

 

 

 

 

 

 

 

 

5 sec by more than 20 %, referenced to the

 

 

 

 

 

 

 

 

 

 

 

rated current, this signal will be outputted.

 

 

 

 

 

 

 

 

 

 

 

 

A 121

Ext.Overvolt.Alarm

 

Overvoltage protection DCF 506 has acted

11105

bit 6

 

 

 

 

 

 

 

There was an overvoltage condition in the

 

 

 

 

 

 

 

 

 

 

 

DC circuit of the field supply, which had been

 

 

 

 

S21.232

 

 

 

 

 

 

limited by the activation of a free wheeling

 

 

 

 

and

 

 

 

 

 

 

circuit.

 

 

 

 

higher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Power wiring of the field supply

 

 

 

 

 

 

 

 

 

 

 

- Control logic according to wiring

 

 

 

 

 

 

 

 

 

 

 

example?

 

 

 

 

 

 

 

 

 

 

 

- Does PP_DI_OVP [1216] has been

 

 

 

 

 

 

 

 

 

 

 

connected to a binary input?

 

 

 

 

 

 

 

 

 

 

 

- Setting of OVP_SELECT [1217]

 

 

 

 

 

 

 

 

 

 

 

correct? (see Fault 121)

 

 

 

 

 

 

 

 

 

 

 

 

A 123

Motor 2 temp. alarm

 

Alarm Overtemperature MOTOR 2

11104

bit 8

 

 

 

 

 

 

 

Check: - Parameter setting MOT2.TEMP_

 

 

 

 

 

 

 

 

 

 

 

ALARM_L [P 1602] correct?

 

 

 

 

 

 

 

 

 

 

 

See also Fault Code F 6.

 

 

 

 

 

 

 

 

 

 

 

 

A 124

Motor 2 overl alarm

 

Alarm Overload MOTOR 2 (Thermal Model 2)

11104

bit 9

 

 

 

 

 

 

 

Check: - See Fault Code F 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

A 126

 

Conv.FAN ack.alarm

 

Alarm No (Thyristor Power) Converter FAN

11104

bit 12

 

 

 

 

 

 

 

Acknowledge

 

 

 

 

 

 

 

 

 

 

 

Check: - See Fault Code F 50.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

 

 

IV A 4 - 13

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 65
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Contents of this manual How to use this manualTarget group Associated publicationsRating plate Incoming inspectionStorage and transport How this chapter is structured General notesRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals Set this only for units of the DCP 500 series 518 = 500 V fixed! rated power converter voltage519 11202 = Save MOT1 SET1305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 11209 = If the field time constant is not known1204 = 1205 = 1002 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1004 = 1009 = 1010 == decrease so that motor voltage is 70% 11003Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1204 POT1 = 10%...20% max. speed 1708 = 0,1 s 1709 = 0,1 s408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3601 = 1201 = 5Panel display FEX2/3 Autotuning3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Display Mode release key Setting of the Display ContrastFull Name of output pins Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveTo enter the Reference Setting Speed Reference Setting for the DriveTo exit the Reference Setting ModeDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FMotor 1 overtemp Conv.fan curr.faultEarth fault SDCS-IOB-3, SDCS-POW P418Local & discon Ext.Overvolt.FaultNected Limited by the activation of a free wheeling CircuitCheck Parameters of Field Exciter Field ex.1 comerrorMains overvoltage Arm. curent ripple No ext. FAN ack See Fault Code FNo main cont. ack Field ex.1 not OKIV a 4 Current Difference Reversal Fault103 Motor 1 temp. alarm Alarm Signals aCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition110 108118 120128 127129 130136 134137 138At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000