Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

 

 

Definition /

 

Status

 

Remark

 

seven

 

 

LCD of control panel

 

 

 

Action

 

signal

 

 

 

segm.

 

 

 

 

 

 

 

CDP 31x

 

 

 

 

 

 

(FAULT_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 44

I/O-Board not found

 

 

Missing input/output (I/O-) boards

11101

bit 7

(1)

 

 

 

 

 

 

 

IOB1/2x/3/IOE1

 

 

 

 

 

 

Can

 

 

 

 

 

 

 

The existance of the boards had been recog-

 

 

 

 

not be

 

 

 

 

 

 

 

nized by the software and something hap-

 

 

 

 

reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pened to the board or the cable.

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Is +/- 10 V supply available?

 

 

 

 

 

 

 

 

 

 

 

 

- Flat cable connections between

 

 

 

 

 

 

 

 

 

 

 

 

SDCS-CON-x and SDCS-IOB-1/2x/3/IOE1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 48

Motor 2 overtemp.

 

 

Overtemperature of MOTOR 2

11101

bit 8

(2)

 

 

 

 

 

 

 

Check: - Parameter setting MOT2 TEMP_

 

 

 

 

 

 

 

 

 

 

 

 

FAULT_L [P 1603] correct?

 

 

 

 

 

 

 

 

 

 

 

 

{See Fault Code F 6}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 50

No C FAN ack

 

 

No CONVERTER FAN supply acknowledge

11102

bit 10

(2)

 

 

 

 

 

 

 

Depending on type of unit (size):

 

 

 

 

 

 

 

 

 

 

 

 

Size C4

Fault signal F 50

 

 

 

 

 

 

 

 

 

 

 

 

Sizes C1/C2/A5

Alarm signal A 126

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Was input for acknowledge

 

 

 

 

 

 

 

 

 

 

 

 

signal (parameter [P 910]) used?

 

 

 

 

 

 

 

 

 

 

 

 

{See Fault Code F 40}.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 52

No BRAKE ack

 

 

No BRAKE acknowledge

11101

bit 10

(2)

 

 

 

 

 

 

 

Check: - Was parameter [P 304] used?

 

 

 

 

 

 

 

 

 

 

 

 

- Cabling and limit switches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 60

 

 

Fieldbus Timeout

 

 

Serial interface (communication bus) is not

11103

bit 13

/(3)

 

 

 

 

 

 

 

O.K.

 

 

 

 

 

 

De-

 

 

 

 

 

 

 

Check: - Does a field bus module selected

 

 

 

 

pends

 

 

 

 

 

 

 

via parameter [P 4001] exist?

 

 

 

 

on

 

 

 

 

 

 

 

- Communication between control

 

 

 

 

[P 920]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system and module Nxxx-0xO.K.?

 

 

 

 

 

 

 

 

 

 

 

 

No or incomplete telegrams?

 

 

 

 

 

 

 

 

 

 

 

 

- Communication between module

 

 

 

 

 

 

 

 

 

 

 

 

Nxxx-0xand thyristor power con-

 

 

 

 

 

 

 

 

 

 

 

 

verter O.K.?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Correct setting of the time inter-

 

 

 

 

 

 

 

 

 

 

 

 

val between two telegrams via

 

 

 

 

 

 

 

 

 

 

 

 

parameter [P 921]?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 10

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 62
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsRating plate Incoming inspectionStorage and transport Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 11209 = If the field time constant is not known1204 = 1205 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Display Mode release key Setting of the Display ContrastFull Name of output pins Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageMotor 1 overtemp Conv.fan curr.faultEarth fault P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitCheck Parameters of Field Exciter Field ex.1 comerrorMains overvoltage Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000