Tripp Lite Single-Phase 10kVA, Single-Phase 7.5kVA Optional Connection, Power OFF optional

Page 9

Connection continued

Cold Start (optional): To use your UPS as a stand-alone power source when AC input power is unavailable (i.e. during a blackout), you can “cold start” your UPS and power connected equipment from the UPS's battery. Your UPS's battery must be at least partially charged for this operation to succeed. Press and hold the “ON” Button I until you hear a beep to cold start your UPS. The LCD Display H will show ON BATTERY MODE. Battery power will begin discharging. Some electronic equipment may draw more amps during startup; when cold starting, consider reducing the initial load on the UPS.

Configure UPS output: Put the UPS into bypass mode by holding the OFF button K down until the UPS beeps, then put the UPS into setup mode by holding down both of its scroll buttons J at once. Scroll through the setup options and select the appropriate setting for each of the following options.

Output Voltage: Select 200, 208, 220, 230 or 240V AC.

Output Frequency: The UPS will automatically select 50 or 60 Hz to match the input.

Economy Mode: The UPS can provide true on-line operation with zero trans- fer time. It can also operate in a more energy-efficient line-interactive mode. Select “Economy On” to put the UPS in line-interactive mode. Select “Economy Off” to put the UPS in on-line mode. After setting these options, exit the setup mode with the scroll buttons J , then exit bypass mode by hold- ing the ON button I down until the UPS beeps.

Turn UPS output power ON: Press the ON button I until the UPS beeps. Turn the UPS Output Circuit Breakers M ON. (The UPS Output Circuit Breakers are located on the detachable PDU O .) Turn the Manual Bypass Switch L from BYPASS to NORMAL. The UPS will now provide output power through its AC outlets N to connected equipment.

Power OFF (optional)

Turn UPS inverter OFF: Press the UPS's “OFF” Button K until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display H will show BYPASS MODE

Turn UPS output power OFF: Turn off the Output Circuit Breakers M locat- ed on the detachable PDU O . Your load will no longer be energized, and the LCD Display will be dark.

5Plug Your Equipment into the PDU's Outlets.

Your UPS is designed to support electronic equipment only. You will overload your UPS if the total VA rating for all the equipment you connect exceeds the UPS's output capacity. Do not connect household appliances or laser printers to the UPS's outlets. To find your equipment's VA ratings, look on their name- plates. If the equipment is listed in amps, multiply the number of amps by the input voltage (240V, 208V or 120V) to determine VA. (Example: 1 amp × 120 = 120 VA).

L

M

O

N

4b

5

Optional Connection

The following connections are optional. Your UPS system will function properly without these connections.

1RS-232 Serial Communication Connection

Use the included cable A to connect the power module's RS-232 port to the communication port on your computer. This will allow full network monitoring and control of your UPS system. Install on your computer the Tripp Lite PowerAlert Software appropriate to your computer's operating system.

Note: RS-232 serial communications are unavailable for PowerAlert Software monitoring while the SNMP/WEB Card is installed in the UPS system's accessory slot. Removing the SNMP/WEB Card from the accessory slot will restore the availability of RS-232 serial communications for PowerAlert Software monitoring.

A

B

1a/1b

9

Image 9
Contents SmartOnline Single-Phase 7.5kVA & 10kVA Important Safety Warnings Mounting Rack Post MountingPost Telecom Mounting Mounting Tower Power Module Front Panel Controls FeaturesBattery Module Power Module Detachable Power Distribution UnitPower Module Feature Description Features Rear PanelDetachable Power Distribution Unit Feature Description Battery Module Feature DescriptionHardwire the PDU to a Utility Power Source Hardwiring CautionsConnect the battery module to the power module Power onPower OFF optional Optional ConnectionPlug Your Equipment into the PDUs Outlets Contact-Closure Communication Connection UPS Power/Battery Module RemovalRisk of electrical shock High Voltage WarningsOperation Startup Self-TestFailed Self-Test On Battery Alarm Normal OperationOverload Messages Shutdown Messages Bypass MessagesWarranty and Warranty Registration Storage and ServiceService Year Limited WarrantyManual del propietario Advertencias de seguridad importantes Montaje Bastidor Montaje de 4 postesMontaje de 2 postes Telecomunicaciones Montaje en torre Controles del panel frontal del módulo de potencia CaracterísticasMódulo de batería Características Panel posterior continuación Descripción de características del módulo de potenciaDescripción de características del módulo de batería Precauciones del cableado ConexiónConecte el módulo de batería al módulo de potencia EncendidoConecte sus equipos en el UPS Apagado opcionalConexión opcional continuación Operación de derivación manual módulo de potenciaRemoción del módulo de potencia/batería de la UPS ¡ADVERTENCIA! ¡Alto voltaje! ¡Riesgo de choque eléctrico Advertencias de alto voltajeOperación Auto-prueba de arranqueFallo durante la auto-prueba Alarma On Battery Operación normalMensajes de sobrecarga Mensajes de apagado Mensajes BypassAlmacenamiento y servicio AlmacenamientoServicio Póliza DE Garantía Garantía limitada de 2 añosManuel de lutilisateur Avertissements pour Connexion de lEquipement Consignes de Sécurité ImportantesMontage Baie Montage à 4 supportsMontage à 2 supports Telecom Montage Tour Caractéristiques Commandes de Panneau Avant de Module dAlimentationModule Batterie Caractéristiques Panneau Arrière suite Description des Caractéristiques de Module dAlimentationDescription des Caractéristiques de Module de Batterie Connexion Précautions pour CâblageConnecter le module de batterie Au module dalimentation Alimentation en Marche Connexion suiteAlimentation sur Arrêt facultatif Connecter votre équipement à lUPSConnexion Communication Fermeture de Contact Connexion en Option suiteMise en Garde! Haute tension! Risque de choc électrique Mise en Garde! Haute tension Risque de choc électriqueFonctionnement Autotest de DémarrageEchec de lAutotest Fonctionnement suite Alarme Sur BatterieFonctionnement Normal Messages de SurchargeMessages de Fermeture Messages de BypassEntreposage et Service Garantie Limitée à 2 AnsEntreposage Page 200607001 Manual del propietario Manuel du propriétaire Contactos en módulo de potencia/batería Español Français Introduction Post Mounting Mounting RackConnection Troubleshooting Warranty Registration Year Limited WarrantyManual del propietario Introducción Montaje de 4 postes Montaje BastidorMontaje en bastidor continúa Solución de problemas Condiciones Garantía limitada de 2 añosManuel de lutilisateur Consignes de Sécurité Importantes Conserver ces Instructions Montage à 4 supports Montage BaieMontage Baie suite Dépannage Numéros didentification de conformité aux règlements Garantie limitée à 2 ansÐóêîâîäñòâî ïîëüçîâàòåëÿ Page Ìîíòàæ Ñòåëëàæ Ìîíòàæ Ñòåëëàæ ïðîäîëæåíèå Òåõíè÷åñêîå îáñëóæèâàíèå Ãàðàíòèéíûå îáÿçàòåëüñòâà