Powerware FE/QFE UPS manual Parameters

Page 38

Parameters

Table 4 shows the first 26 parameters. You can view or reset the parameters using the control panel or a terminal or computer.

If you plan to view or change parameters from the control panel, see “Using the Control Panel” on page 27 for instructions.

If you plan to view or change parameters from a terminal or computer that you have connected to the RS-232 port, see “Entering Commands from a Terminal or Computer” on page 44. When you use commands to display or change parameters, identify the parameter with either its number or name (see Table 4). If you use the name, you can enter the entire parameter name or just the short form; you can also abbreviate the parameter name as long as your abbreviation includes the letters in the short form.

Although you do not need a password to view any of the first

26 parameters, all of them require a password to change (see the password column in Table 4.) See “Entering Passwords” on page 28 or “Entering Commands from a Terminal or Computer” on page 44 for password information.

NOTE All changeable parameters except 0 (Time), 10 (Date), and 15 (Unit ID) are set at the factory. Only qualified technicians using the proper metering equipment should change other parameters. Improper calibration may cause the FERRUPS UPS to malfunction. Call your service representative before you attempt to change any parameters except 0, 10, and 15.

Table 4. Parameters

o

r c

o

o m

d

m

 

 

3r e4

 

0

00 Time 07:04:00

None

time

System Time. The UPS uses this time to

 

 

 

(t)

record alarms and inverter runs. When the

 

 

 

 

DC power has been off and you restart the

 

 

 

 

UPS, the time shown is the last recorded

 

 

 

 

time before shutdown. Reset time when DC

 

 

 

 

power has been off.

 

 

 

 

 

1

01 V In 120.7

Service

acvoltsin

The input voltage the UPS is receiving. When

 

 

 

(vi)

this value drops below the brownout voltage,

 

 

 

 

the UPS switches to inverter.

 

 

 

 

 

2

02 V Out 120.7

Service

acvoltsout

The voltage the UPS is providing to your

 

 

 

(vo)

equipment.

 

 

32

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

Image 38
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS For Users in Germany Class a EMC StatementsFCC Part ICES-003 Table of Contents Alarm Code Summary Service and Support OptionsKVA Models 500 VA-3.1 kVA Models IntroductionIdentifying Your UPS Page N G E R Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S R N I N GR E SikkerhedsanvisningerU T I O N V a a R Belangrijke VeiligheidsinstructiesV a R S E L A R S C H U W I N GA R a Tarkeita TurvaohjeitaG E L E T R O I T U SConsignes de sécurité R OH T U N G SicherheitswarnungenR N U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi V E R T E N Z a Avvisi di sicurezzaR I C O L O R L I G Viktig SikkerhetsinformasionT E N Z I O N E I D a D O Regulamentos de SegurançaR S I K T I G V E R T Ê N C I aÎïàñíî Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÐåäóïðåæäåíèåL I G R O Advertencias de SeguridadÑòîðîæíî V E R T E N C I aR a SäkerhetsföreskrifterE C a U C I Ó N K T I G T UPS Startup Startup for the FE and QFE 500 VA-3.1 kVA UPSLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS Program 7LPHWhere is the Battery Ah value from Table DWHExternal Battery Pack Ah Values 9MESwitch On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch Rear PanelsPanel KVA ModelsFront Panel Indicators OperationIndicator Status Using the Control Panel Changing Operating ModesEntering Passwords Operating ModesDisplaying and Changing Parameters Locking and Unlocking the Control PanelUsing the Configuration Menu Remote Control PanelLogic Test Battery TestAutomatic System Test Inverter TestParameters ParametersVA Limit, parameter DC power is turned offUPS LowShows -63c Configured for use with your networkSwitch is in the OFF position Used by your equipmentExplanation UPS ShutdownInverter Logs on Each part of the system test seeU T I O N Extended Power Outages Page Powerware Software Suite CommunicationCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout Action Key Sequence DB-25 Port SettingsKeystroke Commands Entering Commands from a Terminal or Computer CommandsShows a list of terminal/computer commands CommandDelay Command then clears the minimum and maximum valuesShutdown cancel PasswordUPS restar hortly after power returns Cancels a shutdown started with the shutdown commandRemote Monitoring Remote ShutdownPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA E9I I9G Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA 103A 149AElectrical Input and Output Environmental and Safety BatteryPage Troubleshooting AlarmsAlarms Possible microprocessor problem To start the user test alarm fromAlarm off Temperature probe is missing orRequires service Representative Alarm and Inverter LogsReading the Alarm Log from a Control Panel UPS off and contact your serviceReading the Inverter Log from a Control Panel Reading the Alarm Log from a Terminal or Computer Inverter CodesReading the Inverter Log from a Terminal or Computer Alarm Code SummaryLow Battery Low AC OutputService and Support 852--3030