Page 66

Table 14. Alarms

k

W

W

v h l

v s c

 

b

l

 

 

 

 

 

 

 

A

:

Low

The UPS has shut down after running on

Wait for AC input power to be restored.

 

 

Battery

battery and discharging the batteries.

When AC input power returns, turn on the

 

 

 

 

UPS. The CHARGING indicator illuminates

 

 

 

 

as the UPS begins recharging batteries.

B

: : :Near Low

The battery voltage has reached the Near

 

Battery

Low Battery setpoint.

The alarm should clear itself when the battery charger has charged the batteries enough.

C

::

High

The battery voltage is too high because of

Contact your service representative.

 

 

Battery

a problem with the charging circuit or

 

 

 

 

parameter settings.

 

D

: :

Low

The UPS is running on battery power, and

 

 

Runtime

the battery runtime remaining is low.

Shut down your equipment and turn off the UPS to conserve battery power. When AC input power returns, turn the UPS on again.

E

:

Low AC

The output voltage is below a

 

 

Output

preprogrammed setpoint.

The UPS shuts down. Shut down your equipment or bypass the UPS, and turn the UPS switch off. Contact your service representative.

F

: : :

High AC

The output voltage is higher than the alarm

Contact your service representative.

 

 

Output

setting.

 

 

 

 

 

 

G

:

Output

Power requirements exceed UPS capacity

Turn off and unplug the UPS. Remove some

 

 

Overload

(check the UPS VA rating) or the load is

of the equipment from the UPS. Restart the

 

 

 

defective.

UPS.

 

 

 

 

If the overload condition persists (125% for

 

 

 

 

10 minutes), the UPS automatically shuts

 

 

 

 

down.

H

: : : : Hi Ambient

The temperature inside the UPS is too high.

 

Temp

If the temperature reaches a preset point,

 

 

the UPS shuts down.

If the UPS has shut down, contact your service representative. If not, shut down the protected equipment and the UPS, correct the cause of the high temperature if possible, and turn the UPS on again. If the problem persists, contact your service representative.

I

: :

Hi

The inverter temperature is too high. If the

 

 

Heatsink

temperature reaches a preset point, the

 

 

Temp

UPS shuts down.

If the UPS has shut down, contact your service representative. If not, shut down your equipment or bypass the UPS; turn the UPS off. Contact your service representative.

60

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

Image 66
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS Class a EMC Statements FCC Part ICES-003For Users in Germany Table of Contents Alarm Code Summary Service and Support OptionsIntroduction Identifying Your UPSKVA Models 500 VA-3.1 kVA Models Page N G E R Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S R N I N GSikkerhedsanvisninger U T I O NR E V a a R Belangrijke VeiligheidsinstructiesV a R S E L A R S C H U W I N GA R a Tarkeita TurvaohjeitaG E L E T R O I T U SConsignes de sécurité R OSicherheitswarnungen R N U N GH T U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi Avvisi di sicurezza R I C O L OV E R T E N Z a Viktig Sikkerhetsinformasion T E N Z I O N ER L I G I D a D O Regulamentos de SegurançaR S I K T I G V E R T Ê N C I aÎïàñíî Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÐåäóïðåæäåíèåL I G R O Advertencias de SeguridadÑòîðîæíî V E R T E N C I aSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T UPS Startup Startup for the FE and QFE 500 VA-3.1 kVA UPSLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS Program 7LPHWhere is the Battery Ah value from Table DWHExternal Battery Pack Ah Values 9MESwitch On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch Rear PanelsPanel KVA ModelsFront Panel Indicators OperationIndicator Status Using the Control Panel Changing Operating ModesEntering Passwords Operating ModesDisplaying and Changing Parameters Locking and Unlocking the Control PanelUsing the Configuration Menu Remote Control PanelLogic Test Battery TestAutomatic System Test Inverter TestParameters ParametersVA Limit, parameter DC power is turned offUPS LowShows -63c Configured for use with your networkSwitch is in the OFF position Used by your equipmentExplanation UPS ShutdownInverter Logs on Each part of the system test seeU T I O N Extended Power Outages Page Powerware Software Suite CommunicationCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout DB-25 Port Settings Keystroke CommandsAction Key Sequence Entering Commands from a Terminal or Computer CommandsShows a list of terminal/computer commands CommandDelay Command then clears the minimum and maximum valuesShutdown cancel PasswordUPS restar hortly after power returns Cancels a shutdown started with the shutdown commandRemote Monitoring Remote ShutdownPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA E9I I9G Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA 103A 149AElectrical Input and Output Environmental and Safety BatteryPage Troubleshooting AlarmsAlarms Possible microprocessor problem To start the user test alarm fromAlarm off Temperature probe is missing orRequires service Representative Alarm and Inverter LogsReading the Alarm Log from a Control Panel UPS off and contact your serviceReading the Inverter Log from a Control Panel Reading the Alarm Log from a Terminal or Computer Inverter CodesReading the Inverter Log from a Terminal or Computer Alarm Code SummaryLow Battery Low AC OutputService and Support 852--3030