Powerware FE/QFE UPS manual Entering Commands from a Terminal or Computer

Page 50

m

Entering Commands from a Terminal or Computer

To monitor or control the FERRUPS UPS from a terminal or computer, simply type in one of the commands and press [ENTER] (see Table 8). Use the following command syntax:

:type the command in uppercase or lowercase

:use the entire command or the short form (you can also abbreviate the command as long as you include the letters in the short form

:use a semicolon to separate more than one command on a line

Table 8. Commands

Command

Short

Password

Function

 

 

Form

 

 

 

 

 

 

 

alarmshelp

ah

None

chargermode command, you can change the charger mode:

S ows

list of all possible alarm messages, the audio code and letter for

 

 

 

each alarm and whether the alarm is active.

alarmlog

al

None

Displays Alarm Log. See “Alarm and Inverter Logs” on page 62.

alarmtest

at

None

Allows you to test the alarm function. Alarmtestsounds the User Test

 

 

 

alarm (J). See page 61.

 

 

 

 

alarmtest cancel

at c

None

Turns the Us Test alarm off.

 

 

 

 

chargermode

chm

None*

use the extendedhistory or historycommands.

S ows the UPS battery charger mode. By entering a mode after the

 

 

 

: charg

rmode off (chm f) or cha germode disable (chm d) = charger off

 

 

 

: charg rmode on (chm o) or cha germode enable (chm e) = charger on

 

 

 

: charg rmode auto (chm a) = charger enabled if AC input voltage and

 

 

 

battery voltage are acceptable

 

 

 

 

 

 

clearalarms

ca

None

Clears all active alarms.

 

 

 

 

 

clearhistory

ch

None

Clears the minimum and maximum parameter values shown when you

 

 

 

 

 

clearpassword

cp

None

Clears the current password.

 

 

 

 

 

 

commands

cm

None

Displays a list of all valid commands.

 

 

 

 

 

contdisplay

cd

Depends

Continuously displays the parameter that you are currently displaying.

 

 

on

You can specify other parameters for the continuous

by entering

 

 

parameter

the name or number of each parameter after the contdisplay command.

 

 

password

 

 

 

 

 

 

contstatus

cs

None

Continuously displays the Status information (see the statuscommand.)

 

 

 

 

 

*If you change parameter 39 to “Yes,” this command requires a User password.

44

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

Image 50
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS For Users in Germany Class a EMC StatementsFCC Part ICES-003 Table of Contents Alarm Code Summary Service and Support OptionsKVA Models 500 VA-3.1 kVA Models IntroductionIdentifying Your UPS Page N G E R Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S R N I N GR E SikkerhedsanvisningerU T I O N V a a R Belangrijke VeiligheidsinstructiesV a R S E L A R S C H U W I N GA R a Tarkeita TurvaohjeitaG E L E T R O I T U SConsignes de sécurité R OH T U N G SicherheitswarnungenR N U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi V E R T E N Z a Avvisi di sicurezzaR I C O L O R L I G Viktig SikkerhetsinformasionT E N Z I O N E I D a D O Regulamentos de SegurançaR S I K T I G V E R T Ê N C I aÎïàñíî Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÐåäóïðåæäåíèåL I G R O Advertencias de SeguridadÑòîðîæíî V E R T E N C I aR a SäkerhetsföreskrifterE C a U C I Ó N K T I G T UPS Startup Startup for the FE and QFE 500 VA-3.1 kVA UPSLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS Program 7LPHWhere is the Battery Ah value from Table DWHExternal Battery Pack Ah Values 9MESwitch On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch Rear PanelsPanel KVA ModelsFront Panel Indicators OperationIndicator Status Using the Control Panel Changing Operating ModesEntering Passwords Operating ModesDisplaying and Changing Parameters Locking and Unlocking the Control PanelUsing the Configuration Menu Remote Control PanelLogic Test Battery TestAutomatic System Test Inverter TestParameters ParametersVA Limit, parameter DC power is turned offUPS LowShows -63c Configured for use with your networkSwitch is in the OFF position Used by your equipmentExplanation UPS ShutdownInverter Logs on Each part of the system test seeU T I O N Extended Power Outages Page Powerware Software Suite CommunicationCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout Action Key Sequence DB-25 Port SettingsKeystroke Commands Entering Commands from a Terminal or Computer CommandsShows a list of terminal/computer commands CommandDelay Command then clears the minimum and maximum valuesShutdown cancel PasswordUPS restar hortly after power returns Cancels a shutdown started with the shutdown commandRemote Monitoring Remote ShutdownPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA E9I I9G Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA 103A 149AElectrical Input and Output Environmental and Safety BatteryPage Troubleshooting AlarmsAlarms Possible microprocessor problem To start the user test alarm fromAlarm off Temperature probe is missing orRequires service Representative Alarm and Inverter LogsReading the Alarm Log from a Control Panel UPS off and contact your serviceReading the Inverter Log from a Control Panel Reading the Alarm Log from a Terminal or Computer Inverter CodesReading the Inverter Log from a Terminal or Computer Alarm Code SummaryLow Battery Low AC OutputService and Support 852--3030