Powerware FE/QFE UPS manual Startup for the FE and QFE 4.3-18 kVA UPS

Page 25

Startup for the FE and QFE 4.3–18 kVA UPS

To start the FE and QFE 4.3–18 kVA UPS, use the following steps:

hd Confirm the equipment to be protected by the UPS is powered off.

id For Plug-Receptacle UPSs: Verify that the AC input power is off at the service panel. Plug the UPS power cord into a power outlet.

NOTE If the plug does not match your receptacle outlet, ask your electrician to install the proper outlet.

For Hardwired UPSs: Confirm that an electrician has completed and tested the connection to the proper power source and connected your protected equipment according to the

po poOpo AUPP–18 kVA) Installation Guide. Confirm that your AC line disconnect switch and the UPS ON/OFF switch are both in the OFF position.

ld If your UPS has a DC switch, turn on the switch according to the UPS model:

4.3–7 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position.

If you do not have an external battery cabinet(s): unlock the UPS front cover panel using the FERRUPS key and remove the front cover panel. Locate the DC switch behind the UPS front cover panel. If there is a precharge button next to the switch, press it for a few seconds. Turn the DC switch to the ON position and reinstall the UPS front cover panel.

10–18 kVA: If you have an external battery cabinet(s) with a DC switch, turn the switch to the ON position.

nd Starting the UPS on battery power: Use the key to turn the ON/OFF switch to the ON position. After a brief self-check, the BATTERY POWER and READY indicators illuminate. The UPS beeps every 20 seconds, indicating the UPS is running on battery power. The control panel scrolls this display:

)(55836

0RGH￿ $XWR

&KDUJHU￿ 2II %HHSHU￿ (QDEOHG

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

19

Image 25
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS FCC Part ICES-003 Class a EMC StatementsFor Users in Germany Table of Contents Options Alarm Code Summary Service and SupportIdentifying Your UPS IntroductionKVA Models 500 VA-3.1 kVA Models Page P O R T a N T S a F E T Y I N S T R U C T I O N S Safety WarningsN G E R R N I N GU T I O N SikkerhedsanvisningerR E V a R S E L Belangrijke VeiligheidsinstructiesV a a R A R S C H U W I N GG E L E T Tarkeita TurvaohjeitaA R a R O I T U SR O Consignes de sécuritéR N U N G SicherheitswarnungenH T U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi R I C O L O Avvisi di sicurezzaV E R T E N Z a T E N Z I O N E Viktig SikkerhetsinformasionR L I G R S I K T I G Regulamentos de SegurançaI D a D O V E R T Ê N C I aR I G O Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèÎïàñíî ÐåäóïðåæäåíèåÑòîðîæíî Advertencias de SeguridadL I G R O V E R T E N C I aE C a U C I Ó N SäkerhetsföreskrifterR a K T I G T Startup for the FE and QFE 500 VA-3.1 kVA UPS UPS StartupLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS 7LPH ProgramDWH Where is the Battery Ah value from Table9ME External Battery Pack Ah ValuesRS-232 Communication Port On/Off Switch On/Off Switch Power Cord RS-232 Communication PortSwitch Rear PanelsKVA Models PanelOperation Front Panel IndicatorsIndicator Status Changing Operating Modes Using the Control PanelOperating Modes Entering PasswordsLocking and Unlocking the Control Panel Displaying and Changing ParametersRemote Control Panel Using the Configuration MenuAutomatic System Test Battery TestLogic Test Inverter TestParameters ParametersUPS DC power is turned offVA Limit, parameter LowSwitch is in the OFF position Configured for use with your networkShows -63c Used by your equipmentInverter Logs on UPS ShutdownExplanation Each part of the system test seeU T I O N Extended Power Outages Page Communication Powerware Software SuiteCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout Keystroke Commands DB-25 Port SettingsAction Key Sequence Commands Entering Commands from a Terminal or ComputerDelay CommandShows a list of terminal/computer commands Command then clears the minimum and maximum valuesUPS restar hortly after power returns PasswordShutdown cancel Cancels a shutdown started with the shutdown commandRemote Shutdown Remote MonitoringPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA F9E uWA G9E uWA IuWA Audible Noise dB Runtime minutes Full Load Half Load WeightE9I I9G 103A 149AElectrical Input and Output Battery Environmental and SafetyPage Alarms TroubleshootingAlarms Alarm off To start the user test alarm fromPossible microprocessor problem Temperature probe is missing orReading the Alarm Log from a Control Panel Alarm and Inverter LogsRequires service Representative UPS off and contact your serviceReading the Inverter Log from a Control Panel Inverter Codes Reading the Alarm Log from a Terminal or ComputerLow Battery Alarm Code SummaryReading the Inverter Log from a Terminal or Computer Low AC Output852--3030 Service and Support