Table 11. Electrical Input and Output

m e

Online: 60 Hz (FE) or 50 Hz (QFE) with nominal power line grid stability of ±0.005 Hz.

 

On inverter: 60 Hz (FE) or 50 Hz (QFE) ±0.03 Hz. Output frequency tracks input line frequency

 

up to limit, which is adjustable from ±0.01 Hz to ±3.00 Hz. Inverter turns on if line frequency

 

exceeds the selected limit.

q

±3% load regulation (under any line, load, or battery condition to within -8.3% and +5% of

 

nominal)

u v

Sine wave; <5% THD at rated linear loads, computer-grade power

n b

On line (nominal Vac in): 150% surge and 125% for 10 minutes.

 

On inverter (nominal Vdc in): 150% surge and 110% for 10 minutes.

 

Overload operation is not thermally limited. The FERRUPS UPS microprocessor continuously

 

monitors output VA and sounds an alarm before loss of output voltage regulation occurs.

cb h o

DC fuse and battery charger fuse

n o

Output Protection: The ferroresonant transformer inherently limits current and provides

 

overload protection. The FERRUPS UPS has high AC and low AC output voltage alarms, as

 

well as an overload alarm. If the AC output voltage falls below the low AC output voltage

 

alarm setpoint, the UPS sounds an alarm after five seconds. If the AC output voltage falls

 

below the low AC output shutdown setpoint, the UPS sounds an alarm and shuts down.

 

Some models have output receptacles protected by fuses or circuit breakers.

k r

The FERRUPS UPS provides 2000-to-1 spike attenuation. Tested using lightning standard

o

per ANSI/IEEE C62.41 Category A (6000V spike and 200A) and Category B (6000V spike

 

and 3000A) test, and ANSI/IEEE C62.45 test procedures.

h h

The FERRUPS UPS provides a true separately derived power source, as defined by National

n m f

Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct

a

connection between input and output, and less than 2 pF of effective input to output

 

capacitance.

 

 

56

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

Image 62
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS For Users in Germany Class a EMC StatementsFCC Part ICES-003 Table of Contents Alarm Code Summary Service and Support OptionsKVA Models 500 VA-3.1 kVA Models IntroductionIdentifying Your UPS Page N G E R Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S R N I N GR E SikkerhedsanvisningerU T I O N V a a R Belangrijke VeiligheidsinstructiesV a R S E L A R S C H U W I N GA R a Tarkeita TurvaohjeitaG E L E T R O I T U SConsignes de sécurité R OH T U N G SicherheitswarnungenR N U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi V E R T E N Z a Avvisi di sicurezzaR I C O L O R L I G Viktig SikkerhetsinformasionT E N Z I O N E I D a D O Regulamentos de SegurançaR S I K T I G V E R T Ê N C I aÎïàñíî Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÐåäóïðåæäåíèåL I G R O Advertencias de SeguridadÑòîðîæíî V E R T E N C I aR a SäkerhetsföreskrifterE C a U C I Ó N K T I G T UPS Startup Startup for the FE and QFE 500 VA-3.1 kVA UPSLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS Program 7LPHWhere is the Battery Ah value from Table DWHExternal Battery Pack Ah Values 9MESwitch On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch Rear PanelsPanel KVA ModelsFront Panel Indicators OperationIndicator Status Using the Control Panel Changing Operating ModesEntering Passwords Operating ModesDisplaying and Changing Parameters Locking and Unlocking the Control PanelUsing the Configuration Menu Remote Control PanelLogic Test Battery TestAutomatic System Test Inverter TestParameters ParametersVA Limit, parameter DC power is turned offUPS LowShows -63c Configured for use with your networkSwitch is in the OFF position Used by your equipmentExplanation UPS ShutdownInverter Logs on Each part of the system test seeU T I O N Extended Power Outages Page Powerware Software Suite CommunicationCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout Action Key Sequence DB-25 Port SettingsKeystroke Commands Entering Commands from a Terminal or Computer CommandsShows a list of terminal/computer commands CommandDelay Command then clears the minimum and maximum valuesShutdown cancel PasswordUPS restar hortly after power returns Cancels a shutdown started with the shutdown commandRemote Monitoring Remote ShutdownPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA E9I I9G Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA 103A 149AElectrical Input and Output Environmental and Safety BatteryPage Troubleshooting AlarmsAlarms Possible microprocessor problem To start the user test alarm fromAlarm off Temperature probe is missing orRequires service Representative Alarm and Inverter LogsReading the Alarm Log from a Control Panel UPS off and contact your serviceReading the Inverter Log from a Control Panel Reading the Alarm Log from a Terminal or Computer Inverter CodesReading the Inverter Log from a Terminal or Computer Alarm Code SummaryLow Battery Low AC OutputService and Support 852--3030