Page 42

C A U T I O N

When AC input voltage is present, the UPS system can provide output voltage even though its batteries are disconnected. To confirm that there is no UPS output voltage, always disconnect the AC input source; if the UPS has one or more separate battery cabinets, open the DC disconnect switch on each battery cabinet or disconnect the battery cabinet from the UPS.

hd UPSs with no bypass switch: Turn off the protected equipment. Continue to Step 2.

If you need to use the equipment while the UPS is off, plug the equipment into standard wall outlets and restart the equipment.

UPSs with a Break-Before-Make (BBM) bypass switch (see the label on the side of the switch): Shut down the protected equipment. Turn the bypass switch to the LINE position. Continue to Step 2.

If you need to use the equipment while the UPS is off, restart the equipment. The equipment receives direct AC line instead of conditioned power from the UPS.

UPSs with a Make-Before-Break (MBB) bypass switch (see the label on the side of the switch): Verify that the AC LINE indicator is on, the BATTERY POWER indicator is off, and the UPS is providing output. If all three of these conditions are present, turn the bypass switch to the LINE position. Your equipment receives direct AC line instead of conditioned power from the UPS. Continue to Step 2.

If all three of these conditions are not present, follow Steps 2–4 before you turn the bypass switch to the LINE position. This causes a break in power to your equipment between shutting down the UPS and turning the bypass switch to the LINE position.

C A U T I O N

Equipment can be damaged if you change the switch position when line is applied and the UPS is off or on battery! Refer to TIP 410.

id Turn the UPS ON/OFF switch to the OFF position.

ld If the UPS is plugged in, unplug it. For hardwired models, turn the AC line disconnect switch to the OFF position.

36

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

Image 42
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS Class a EMC Statements FCC Part ICES-003For Users in Germany Table of Contents Alarm Code Summary Service and Support OptionsIntroduction Identifying Your UPSKVA Models 500 VA-3.1 kVA Models Page N G E R Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S R N I N GSikkerhedsanvisninger U T I O NR E V a a R Belangrijke VeiligheidsinstructiesV a R S E L A R S C H U W I N GA R a Tarkeita TurvaohjeitaG E L E T R O I T U SConsignes de sécurité R OSicherheitswarnungen R N U N GH T U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi Avvisi di sicurezza R I C O L OV E R T E N Z a Viktig Sikkerhetsinformasion T E N Z I O N ER L I G I D a D O Regulamentos de SegurançaR S I K T I G V E R T Ê N C I aÎïàñíî Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÐåäóïðåæäåíèåL I G R O Advertencias de SeguridadÑòîðîæíî V E R T E N C I aSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T UPS Startup Startup for the FE and QFE 500 VA-3.1 kVA UPSLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS Program 7LPHWhere is the Battery Ah value from Table DWHExternal Battery Pack Ah Values 9MESwitch On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch Rear PanelsPanel KVA ModelsFront Panel Indicators OperationIndicator Status Using the Control Panel Changing Operating ModesEntering Passwords Operating ModesDisplaying and Changing Parameters Locking and Unlocking the Control PanelUsing the Configuration Menu Remote Control PanelLogic Test Battery TestAutomatic System Test Inverter TestParameters Parameters VA Limit, parameter DC power is turned off UPS LowShows -63c Configured for use with your networkSwitch is in the OFF position Used by your equipmentExplanation UPS ShutdownInverter Logs on Each part of the system test seeU T I O N Extended Power Outages Page Powerware Software Suite CommunicationCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout DB-25 Port Settings Keystroke CommandsAction Key Sequence Entering Commands from a Terminal or Computer CommandsShows a list of terminal/computer commands CommandDelay Command then clears the minimum and maximum valuesShutdown cancel PasswordUPS restar hortly after power returns Cancels a shutdown started with the shutdown commandRemote Monitoring Remote ShutdownPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA E9I I9G Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA 103A 149AElectrical Input and Output Environmental and Safety BatteryPage Troubleshooting AlarmsAlarms Possible microprocessor problem To start the user test alarm fromAlarm off Temperature probe is missing orRequires service Representative Alarm and Inverter LogsReading the Alarm Log from a Control Panel UPS off and contact your serviceReading the Inverter Log from a Control Panel Reading the Alarm Log from a Terminal or Computer Inverter CodesReading the Inverter Log from a Terminal or Computer Alarm Code SummaryLow Battery Low AC OutputService and Support 852--3030