Powerware FE/QFE UPS manual Ups, VA Limit, parameter, Low, DC power is turned off

Page 39

o

r c

o

o m

d

 

m

 

 

3r e4

 

 

3

03 --Reserved--

 

Reserved

 

 

 

 

 

 

 

 

4

04 I Out 3.1

Service

acampsiout

The current your equipment is drawing from

 

 

 

 

(o)

the UPS.

 

 

 

 

 

 

 

5

05 VA Out 374

Change Not

vaout

Volt-Amps Out. The total “apparent power”

 

 

 

Allowed

(va)

your equipment is drawing from the UPS.

 

 

 

 

 

This value is based on parameter 2 multiplied

 

 

 

 

by parameter 4, and should be less than or

 

 

 

 

 

equal to the VA or kVA rating of the UPS. See

 

 

 

 

VA Limit, parameter 19.

 

 

 

 

 

 

6

06 I Batt 0.0

Service

ibatt

Battery Current. When the UPS is running on

 

 

 

(ib)

AC input, this is the charging current inA.

 

 

 

 

 

When the UPS runs on battery power

 

 

 

 

 

(inverter), this is the amount of current (inA)

 

 

 

 

 

the batteries are supplying to the UPS.

 

 

 

 

 

 

 

7

07 V Batt 48.51

Service

vbatt

Battery Volts. The present battery voltage.

 

 

 

 

(vb)

The UPS sounds an alarm if this value is too

 

 

 

 

 

low.

 

 

 

 

 

 

 

8

08 Freq 60.43 Hz

Change Not

frequency

In normal operation, this is the frequency of

 

 

 

Allowed

(f)

power the UPS is receiving from the AC input

 

 

 

 

source. If this value falls outside preset

 

 

 

 

 

limits, the UPS goes to battery power. When

 

 

 

 

the UPS is running on battery power, this is

 

 

 

 

 

the frequency the UPS is supplying to your

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

9

09 RunTime 12m

Change Not

runtime

Estimated Runtime Remaining. The amount

 

 

 

Allowed

(rt)

of time the UPS continues to support your

 

 

 

 

 

equipment when the UPS is running on

 

 

 

 

 

battery power. The UPS sounds an alarm

 

 

 

 

 

when this value falls below a preset limit.

 

 

 

 

 

 

 

10

10 Date 06/01/93

None

date

System Date. The UPS uses this date to

 

 

 

 

(d)

record alarms and inverter runs. The date

 

 

 

 

 

must be reset when you restart the UPS after

 

 

 

 

DC power is turned off.

 

 

 

 

 

 

 

11 or

11 Amb Temp 23c

Change Not

ambtemp

The temperature (in Celsius) inside the UPS.

 

[DISPLAY]

 

Allowed

(at)

The UPS sounds an alarm and shuts down if

 

[1] [1] [ENTER]

 

 

 

this value is too high.

 

 

 

 

 

 

 

12

12 SinkTemp 26c

Change Not

heatsinktemp

The temperature of the heatsink. The UPS

 

 

 

Allowed

(st)

sounds an alarm if this value is too high.

 

 

 

 

 

 

 

13

13 --Reserved--

 

Reserved

 

 

 

 

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

33

Image 39
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS Class a EMC Statements FCC Part ICES-003For Users in Germany Table of Contents Options Alarm Code Summary Service and SupportIntroduction Identifying Your UPSKVA Models 500 VA-3.1 kVA Models Page R N I N G Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S N G E RSikkerhedsanvisninger U T I O NR E A R S C H U W I N G Belangrijke VeiligheidsinstructiesV a R S E L V a a RR O I T U S Tarkeita TurvaohjeitaG E L E T A R aR O Consignes de sécuritéSicherheitswarnungen R N U N GH T U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi Avvisi di sicurezza R I C O L OV E R T E N Z a Viktig Sikkerhetsinformasion T E N Z I O N ER L I G V E R T Ê N C I a Regulamentos de SegurançaR S I K T I G I D a D OÐåäóïðåæäåíèå Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÎïàñíîV E R T E N C I a Advertencias de SeguridadÑòîðîæíî L I G R OSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T Startup for the FE and QFE 500 VA-3.1 kVA UPS UPS StartupLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS 7LPH ProgramDWH Where is the Battery Ah value from Table9ME External Battery Pack Ah ValuesRear Panels On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch SwitchKVA Models PanelOperation Front Panel IndicatorsIndicator Status Changing Operating Modes Using the Control PanelOperating Modes Entering PasswordsLocking and Unlocking the Control Panel Displaying and Changing ParametersRemote Control Panel Using the Configuration MenuInverter Test Battery TestAutomatic System Test Logic TestParameters ParametersLow DC power is turned offUPS VA Limit, parameterUsed by your equipment Configured for use with your networkSwitch is in the OFF position Shows -63cEach part of the system test see UPS ShutdownInverter Logs on ExplanationU T I O N Extended Power Outages Page Communication Powerware Software SuiteCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout DB-25 Port Settings Keystroke CommandsAction Key Sequence Commands Entering Commands from a Terminal or ComputerCommand then clears the minimum and maximum values CommandDelay Shows a list of terminal/computer commandsCancels a shutdown started with the shutdown command PasswordUPS restar hortly after power returns Shutdown cancelRemote Shutdown Remote MonitoringPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA 103A 149A Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA E9I I9GElectrical Input and Output Battery Environmental and SafetyPage Alarms TroubleshootingAlarms Temperature probe is missing or To start the user test alarm fromAlarm off Possible microprocessor problemUPS off and contact your service Alarm and Inverter LogsReading the Alarm Log from a Control Panel Requires service RepresentativeReading the Inverter Log from a Control Panel Inverter Codes Reading the Alarm Log from a Terminal or ComputerLow AC Output Alarm Code SummaryLow Battery Reading the Inverter Log from a Terminal or Computer852--3030 Service and Support