Powerware FE/QFE UPS Alarm Code Summary, Reading the Inverter Log from a Terminal or Computer

Page 71

Reading the Inverter Log from a Terminal or Computer

To display the Inverter Log on a terminal or computer, you can use the inverterlog or logs command (see “Entering Commands from a Terminal or Computer” page 44). These commands display up to 20 log entries in a table. For example, the log might look like this:

Active

EventDate

EventTime

Duration

Code/Event

No

08/25/1993

11:25:32

00:00:45

M-Manual turnon

No

08/24/1993

12:13:18

00:01:08

L-Line fault

The table shows whether the UPS is running on inverter (battery power) now (Active), the date and time that the UPS ran on battery power, the length of time the UPS ran on battery power (Duration), and the reason (Code/Event).

You can also display parameter 24 to view the Inverter Log; this display is the same as the control panel display.

Alarm Code Summary

A

:

Low Battery

L

: : :

Check Charger

B

: : :

Near Low Battery

M

– –

Check Battery

C

::

High Battery

N

:

Check Inverter

D

: :

Low Runtime

O

– – –

Memory Check

E

:

Low AC Output

P

: :

Emergency PwrOff

F

: : :

High AC Output

Q

:

Hi PFM Res Temp

G

:

Output Overload

R

: :

Probe Missing

H

: : : :

Hi Ambient Temp

S

: : :

High AC Input

I

: :

Hi Heatsink Temp

T

Call Service

J

: – – –

User Test Alarm

W

: – –

Fan Alarm

K:– Hi Transfmr Temp

Figure 12. Alarm Code Summary

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

65

Image 71
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS For Users in Germany Class a EMC StatementsFCC Part ICES-003 Table of Contents Options Alarm Code Summary Service and SupportKVA Models 500 VA-3.1 kVA Models IntroductionIdentifying Your UPS Page R N I N G Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S N G E RR E SikkerhedsanvisningerU T I O N A R S C H U W I N G Belangrijke VeiligheidsinstructiesV a R S E L V a a RR O I T U S Tarkeita TurvaohjeitaG E L E T A R aR O Consignes de sécuritéH T U N G SicherheitswarnungenR N U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi V E R T E N Z a Avvisi di sicurezzaR I C O L O R L I G Viktig SikkerhetsinformasionT E N Z I O N E V E R T Ê N C I a Regulamentos de SegurançaR S I K T I G I D a D OÐåäóïðåæäåíèå Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÎïàñíîV E R T E N C I a Advertencias de SeguridadÑòîðîæíî L I G R OR a SäkerhetsföreskrifterE C a U C I Ó N K T I G T Startup for the FE and QFE 500 VA-3.1 kVA UPS UPS StartupLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS 7LPH ProgramDWH Where is the Battery Ah value from Table9ME External Battery Pack Ah ValuesRear Panels On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch SwitchKVA Models PanelOperation Front Panel IndicatorsIndicator Status Changing Operating Modes Using the Control PanelOperating Modes Entering PasswordsLocking and Unlocking the Control Panel Displaying and Changing ParametersRemote Control Panel Using the Configuration MenuInverter Test Battery TestAutomatic System Test Logic TestParameters ParametersLow DC power is turned offUPS VA Limit, parameterUsed by your equipment Configured for use with your networkSwitch is in the OFF position Shows -63cEach part of the system test see UPS ShutdownInverter Logs on ExplanationU T I O N Extended Power Outages Page Communication Powerware Software SuiteCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout Action Key Sequence DB-25 Port SettingsKeystroke Commands Commands Entering Commands from a Terminal or ComputerCommand then clears the minimum and maximum values CommandDelay Shows a list of terminal/computer commandsCancels a shutdown started with the shutdown command PasswordUPS restar hortly after power returns Shutdown cancelRemote Shutdown Remote MonitoringPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA 103A 149A Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA E9I I9GElectrical Input and Output Battery Environmental and SafetyPage Alarms TroubleshootingAlarms Temperature probe is missing or To start the user test alarm fromAlarm off Possible microprocessor problemUPS off and contact your service Alarm and Inverter LogsReading the Alarm Log from a Control Panel Requires service RepresentativeReading the Inverter Log from a Control Panel Inverter Codes Reading the Alarm Log from a Terminal or ComputerLow AC Output Alarm Code SummaryLow Battery Reading the Inverter Log from a Terminal or Computer852--3030 Service and Support