Powerware FE/QFE UPS Command, Function, Date, Delay, Represents 2.5 mi lisec, Display, Format

Page 51

 

 

 

 

m

 

 

 

 

Command

Short

Password

delay. For a -second delay, enter delay 400.

Function

 

 

Form

 

 

 

date

da

None*

Displays[month]/[day]/[year]system time and date. To s t the date, enter ate

 

 

 

.

 

delay

dl

None

Delays next command when you nter number after delay. Each unit

 

 

 

represents 2.5 mi lisec

nds, so delay1would cause a 2.5 millisecond

 

 

 

 

 

display

d

Depends

Displays the values of

ne or more parameters (see Table 4 on page 32).

 

 

on

Format: display [parameter # or name] [parameter # or name]

 

 

parameter

Example: d1fullloadoldisplays the values of parameters 1, 16 and 21

 

 

password

 

 

 

 

 

 

extendedhistory

xh

None

Displays the minimum and maximum values of parameters 1 (Vac In),

 

 

 

2 (Vac Out), 7 (Vdc) and 5 (VA Out); the command then clears the

 

 

 

minimum and maximum values (see Table 4 on page 32).

 

 

 

 

format

f

None

Displays an 80-character line containing information on the FERRUPS’

 

 

 

status. CheckUPS II and other UPS monitoring software use this data.

 

 

 

 

help

? or he

None

Shows a list of terminal/computer commands.

 

 

 

 

history

h

None

Displays the minimum and maximum values of parameter 1 (Vac In); the

 

 

 

command then clears the minimum and maximum values.

 

 

 

 

identify

I

None

Shows Powerware’s address and telephone number and the software

 

 

 

version.

 

 

 

 

 

inverterlog

il

None

Displays the Inverter Log. See “Alarm and Inverter Logs” on page 62.

 

 

 

 

logs

l

None

Displays both the Alarm and Inverter Logs. See “Alarm and Inverter Logs”

 

 

 

on page 62.

 

 

 

 

 

off [time]

o [time]

None*

Shuts down the UPS a given number of seconds. The READY indicator

 

 

password

Example: Parameters 110displays parameters 1 through 10.

 

 

 

flashes until the UPS

huts down, and the UPS beeps five seconds before

 

 

 

shutdown. Example: OFF60shuts down the UPS in 60 seconds.

off [time] autostart

o [time]

None*

Shuts down the UPS in a given number of seconds (see above), and

 

a

 

restarts the UPS sho tly after power returns.

off cancel

o c

None*

Cancels timed shu down.

parameters

p

Depends

Shows a list of syst

parameters. See “Parameters” on page 32. You

 

 

on

can also displ y a range of parameters by entering the starting and

 

 

parameter

ending parameter number or name after the command.

*If you change parameter 39 to “Yes,” this command requires a User password.

Powerware® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide : Rev A www.powerware.com

45

Image 51
Contents Powerware Ferrups FE/QFE UPS Page Powerware Ferrups FE/QFE UPS Class a EMC Statements FCC Part ICES-003For Users in Germany Table of Contents Options Alarm Code Summary Service and SupportIntroduction Identifying Your UPSKVA Models 500 VA-3.1 kVA Models Page R N I N G Safety WarningsP O R T a N T S a F E T Y I N S T R U C T I O N S N G E RSikkerhedsanvisninger U T I O NR E A R S C H U W I N G Belangrijke VeiligheidsinstructiesV a R S E L V a a RR O I T U S Tarkeita TurvaohjeitaG E L E T A R aR O Consignes de sécuritéSicherheitswarnungen R N U N GH T U N G „Ò·Ûfl· C›„ÈÛÙ.ÃÁ˜ÒÁÙÈÏÔfi95%ÔÈÂflÙÂUPSÍÔÌÙ‹ÛÂÌÂÒ¸fi Avvisi di sicurezza R I C O L OV E R T E N Z a Viktig Sikkerhetsinformasion T E N Z I O N ER L I G V E R T Ê N C I a Regulamentos de SegurançaR S I K T I G I D a D OÐåäóïðåæäåíèå Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòèR I G O ÎïàñíîV E R T E N C I a Advertencias de SeguridadÑòîðîæíî L I G R OSäkerhetsföreskrifter E C a U C I Ó NR a K T I G T Startup for the FE and QFE 500 VA-3.1 kVA UPS UPS StartupLd The AC Line indicator illuminates see Figure Startup for the FE and QFE 4.3-18 kVA UPS 7LPH ProgramDWH Where is the Battery Ah value from Table9ME External Battery Pack Ah ValuesRear Panels On/Off Switch Power Cord RS-232 Communication PortRS-232 Communication Port On/Off Switch SwitchKVA Models PanelOperation Front Panel IndicatorsIndicator Status Changing Operating Modes Using the Control PanelOperating Modes Entering PasswordsLocking and Unlocking the Control Panel Displaying and Changing ParametersRemote Control Panel Using the Configuration MenuInverter Test Battery TestAutomatic System Test Logic TestParameters ParametersLow DC power is turned offUPS VA Limit, parameterUsed by your equipment Configured for use with your networkSwitch is in the OFF position Shows -63cEach part of the system test see UPS ShutdownInverter Logs on ExplanationU T I O N Extended Power Outages Page Communication Powerware Software SuiteCommunication Port Connecting a Terminal or Computer to the RS-232 Port DB-9 to UPS Pinout DB-25 Port Settings Keystroke CommandsAction Key Sequence Commands Entering Commands from a Terminal or ComputerCommand then clears the minimum and maximum values CommandDelay Shows a list of terminal/computer commandsCancels a shutdown started with the shutdown command PasswordUPS restar hortly after power returns Shutdown cancelRemote Shutdown Remote MonitoringPage Options Page Maintenance Page Specifications FE and QFE 4.3-18 kVA 103A 149A Audible Noise dB Runtime minutes Full Load Half Load WeightF9E uWA G9E uWA IuWA E9I I9GElectrical Input and Output Battery Environmental and SafetyPage Alarms TroubleshootingAlarms Temperature probe is missing or To start the user test alarm fromAlarm off Possible microprocessor problemUPS off and contact your service Alarm and Inverter LogsReading the Alarm Log from a Control Panel Requires service RepresentativeReading the Inverter Log from a Control Panel Inverter Codes Reading the Alarm Log from a Terminal or ComputerLow AC Output Alarm Code SummaryLow Battery Reading the Inverter Log from a Terminal or Computer852--3030 Service and Support