Introduction 1
Battery Times for the UPS and BIM
During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown The duration of this time period is directly related to the UPS battery configuration By adding battery modules, you can customize the UPS to provide enough battery time for normal processing activities
Load (VA) |
| Average Battery Time (in Minutes) | |||
Load (W) |
|
|
| ||
at .7 PF* | 1 Module | 2 Modules | 3 Modules | ||
| |||||
|
| ||||
|
|
|
|
| |
600 | 420 | 36.8 | 88 | 146 | |
|
|
|
|
| |
800 | 560 | 27.6 | 66 | 110 | |
|
|
|
|
| |
1200 | 840 | 18.4 | 44 | 73 | |
|
|
|
|
| |
1600 | 1120 | 13.7 | 33 | 54 | |
|
|
|
|
| |
2000 | 1400 | 10.7 | 26 | 42 | |
|
|
|
|
| |
2500 | 1750 | 8.3 | 20 | 33 | |
|
|
|
|
| |
3000 | 2100 | 6.5 | 16 | 27 | |
|
|
|
|
|
*Typical Power Factor PF
Battery Times for the UPS with BDM
|
| Average Battery Time (in Minutes) | |||
Load (VA) | Load (W) |
|
|
| |
1 Module | 2 Modules | 3 Modules | |||
|
| ||||
|
|
|
|
| |
600 | 402 | 36.8 | 88 | 146 | |
|
|
|
|
| |
800 | 533 | 27.6 | 66 | 110 | |
|
|
|
|
| |
1200 | 800 | 18.4 | 44 | 73 | |
|
|
|
|
| |
1600 | 1067 | 13.7 | 33 | 54 | |
|
|
|
|
| |
2000 | 1333 | 10.7 | 26 | 42 | |
|
|
|
|
| |
2500 | 1667 | 8.3 | 20 | 33 | |
|
|
|
|
| |
3000 | 2000 | 6.5 | 16 | 27 | |
|
|
|
|
|
iNOTE If using an EBC, refer to the EBC manual for approximate battery times.
Lucent Technologies Model 3000 UPS Operators Manual 167+405+119 Issue 3 | 3 |