Lucent Technologies 3000 VA Battery Times for the UPS and BIM, Battery Times for the UPS with BDM

Page 13

Introduction 1

Battery Times for the UPS and BIM

During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown￿ The duration of this time period is directly related to the UPS battery configuration￿ By adding battery modules, you can customize the UPS to provide enough battery time for normal processing activities￿

Load (VA)

 

Average Battery Time (in Minutes)

Load (W)

 

 

 

at .7 PF*

1 Module

2 Modules

3 Modules

 

 

 

 

 

 

 

 

600

420

36.8

88

146

 

 

 

 

 

800

560

27.6

66

110

 

 

 

 

 

1200

840

18.4

44

73

 

 

 

 

 

1600

1120

13.7

33

54

 

 

 

 

 

2000

1400

10.7

26

42

 

 

 

 

 

2500

1750

8.3

20

33

 

 

 

 

 

3000

2100

6.5

16

27

 

 

 

 

 

*Typical Power Factor ￿PF￿

Battery Times for the UPS with BDM

 

 

Average Battery Time (in Minutes)

Load (VA)

Load (W)

 

 

 

1 Module

2 Modules

3 Modules

 

 

 

 

 

 

 

600

402

36.8

88

146

 

 

 

 

 

800

533

27.6

66

110

 

 

 

 

 

1200

800

18.4

44

73

 

 

 

 

 

1600

1067

13.7

33

54

 

 

 

 

 

2000

1333

10.7

26

42

 

 

 

 

 

2500

1667

8.3

20

33

 

 

 

 

 

3000

2000

6.5

16

27

 

 

 

 

 

iNOTE If using an EBC, refer to the EBC manual for approximate battery times.

Lucent Technologies Model 3000 UPS Operator￿s Manual ￿167+405+119 Issue 3￿

3

Image 13
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS UPS with BDM InstallationQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Model 3000 UPS NtroductionLoad Requirements UPS Model and Battery ConfigurationsBattery Times for the UPS with BDM Battery Times for the UPS and BIMIntroduction Afety Warnings This Manual Contains Important Safety InstructionsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Afety Warnings Requisitos de seguridadAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Important Installation Notes Read Before Installing the UPS UPS and Battery Module StorageNstallation Unpacking and InspectionSystems That Require Contact Closure UPS with Bypass Module InstallationSystems That Require a Serial Interface UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes UPS with Bypass Module Startup Phase 200/208/220/230/240VOutput Voltage Indicators Troubleshooting Tips Installation UPS Front Panel S!!! O!!P!!E!!R!!A!!T!!I!!O!!NOperating Modes Normal ModeBattery Mode Bypass ModeBattery Test on Demand DiagnosticsBattery Start Using Maintenance Bypass Using the Bypass ModuleUPS Shutdown Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Ommunication Initial Communications SettingsOptions Front Panel ommuncatons AccessUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate Serial Port Location UPS Communications Interface PortPWR.FAIL Communications Mode Reference ChartUPS Physical Specifications UPS Model 3000 SpecificationsPecifications Model 3000 Specifications with the 50Hz BIM Model 3000 Specifications with the 60Hz BDMEMC UPS Technical Specifications# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Silencing the Alarm Resetting the UPSService and Support PDM06 Parts ListNdex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 Class a FCC StatementEuropean EMC Statement EC Declaration of Conformity