3Installation

￿Place the conduit through the access hole on the junction box (see Figure￿10). Connect the exposed conduit wires to the corresponding compression terminals (see the following table). Tighten the compression terminals with a screwdriver.

￿Pivot the REPO receptacle guard out of the way, plug the REPO plug/receptacle UPS connector into the REPO receptacle on the UPS rear panel (see Figure￿5 on page 26 or Figure￿6 on page 27). Twist the connector in place.

 

 

Mounting Holes

Plug/Receptacle

 

 

 

 

 

 

 

 

 

 

UPS Connector

 

 

Access Hole

 

 

 

 

 

for Conduit

 

 

 

 

 

 

 

Three Foot Cord

 

 

 

Terminal Block

 

 

 

 

 

Figure 10. REPO Cord Junction Box

 

 

 

Power Cable Terminations

 

Tightening Torque

 

Wire Function

Terminal

Terminal Wire

Entrelec

Phoenix

 

 

Position

Size Rating*

 

Contact

REPO

L1

TB184

 

 

 

 

L2

TB185

12822 AWG

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

 

(480 mm2)

 

Ground

TB186

 

 

 

*Suggested wire size is #188AWG (0.75 mm2) 75_C copper wire minimum.

NOTE: The REPO function activates when L1 and L2 are shorted together.

32

Lucent Technologies Model 3000 UPS Operator's Manual (16784058119 Issue 3)

Image 42
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS with BDM Installation UPSQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Ntroduction Model 3000 UPSUPS Model and Battery Configurations Load RequirementsBattery Times for the UPS and BIM Battery Times for the UPS with BDMIntroduction This Manual Contains Important Safety Instructions Afety WarningsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Requisitos de seguridad Afety WarningsAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Nstallation UPS and Battery Module StorageImportant Installation Notes Read Before Installing the UPS Unpacking and InspectionUPS with Bypass Module Installation Systems That Require Contact ClosureSystems That Require a Serial Interface UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes Phase 200/208/220/230/240V UPS with Bypass Module StartupOutput Voltage Indicators Troubleshooting Tips Installation S!!! O!!P!!E!!R!!A!!T!!I!!O!!N UPS Front PanelNormal Mode Operating ModesBypass Mode Battery ModeDiagnostics Battery Test on DemandBattery Start UPS Shutdown Using the Bypass ModuleUsing Maintenance Bypass Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Initial Communications Settings OmmunicationFront Panel ommuncatons Access OptionsUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate UPS Communications Interface Port Serial Port LocationCommunications Mode Reference Chart PWR.FAILUPS Model 3000 Specifications UPS Physical SpecificationsPecifications Model 3000 Specifications with the 60Hz BDM Model 3000 Specifications with the 50Hz BIMUPS Technical Specifications EMC# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Resetting the UPS Silencing the AlarmService and Support Parts List PDM06Ndex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 European EMC Statement FCC StatementClass a EC Declaration of Conformity