Lucent Technologies 3000 VA manual Output Voltage Indicators

Page 54

4UPS Operation

5Press and hold the Output￿ On button until the alarm beeps again.

Two indicators, corresponding with the current setting, remain flashing. The output voltage is factory.configured for 230V.

OVERLOAD

I1

I2

I3

OUTPUT ON

240V

230V

220V

208V

Figure 19. Output Voltage Indicators

6Press the Output Off button to scroll through the output voltage options, top to bottom. Each time you press the button, the UPS beeps and the next two indicators flash.

i NOTE If you do not save a selection within two minutes, the setup automatically aborts and switches back to the original configuration.

7Press and hold the Output￿ On button until the alarm beeps to select and save the output voltage. Failure to release the button immediately after the beep will cause the UPS to abort the setup.

8Press and hold the Output￿ On button until you hear the UPS beep (approximately one second).

The ￿Indicator remains lit and the Output On Indicator turns on, indicating the UPS is online.

9Turn the Bypass switch on the Bypass Module to the NORMAL position.

The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal Mode with the load online.

44

￿#￿￿￿" ￿￿￿￿￿￿￿￿￿￿￿! ￿￿￿￿￿ ￿￿￿￿ ￿￿￿ ￿￿￿ ￿"￿ ￿! ￿￿￿#￿￿ ￿￿6￿$￿￿5$￿￿￿ I!!#￿ ￿￿

Image 54
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS with BDM Installation UPSQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Ntroduction Model 3000 UPSUPS Model and Battery Configurations Load RequirementsBattery Times for the UPS and BIM Battery Times for the UPS with BDMIntroduction This Manual Contains Important Safety Instructions Afety WarningsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Requisitos de seguridad Afety WarningsAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Nstallation UPS and Battery Module StorageImportant Installation Notes Read Before Installing the UPS Unpacking and InspectionUPS with Bypass Module Installation Systems That Require Contact ClosureSystems That Require a Serial Interface UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes Phase 200/208/220/230/240V UPS with Bypass Module StartupOutput Voltage Indicators Troubleshooting Tips Installation S!!! O!!P!!E!!R!!A!!T!!I!!O!!N UPS Front PanelNormal Mode Operating ModesBypass Mode Battery ModeDiagnostics Battery Test on DemandBattery Start UPS Shutdown Using the Bypass ModuleUsing Maintenance Bypass Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Initial Communications Settings OmmunicationFront Panel ommuncatons Access OptionsUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate UPS Communications Interface Port Serial Port LocationCommunications Mode Reference Chart PWR.FAILUPS Model 3000 Specifications UPS Physical SpecificationsPecifications Model 3000 Specifications with the 60Hz BDM Model 3000 Specifications with the 50Hz BIMUPS Technical Specifications EMC# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Resetting the UPS Silencing the AlarmService and Support Parts List PDM06Ndex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 European EMC Statement FCC StatementClass a EC Declaration of Conformity