Specifications 6
UPS Technical Specifications
Input Voltage Range |
| 160 to 276 Vac | |
|
|
| |
Bypass Isolation Module |
| 187 to 276 Vac | |
Input Voltage Range |
| ||
|
| ||
|
|
| |
Input Power Factor |
| 0.95 Typical | |
|
|
| |
Frequency Range |
| 50/60 Hz 3 Hz | |
|
|
| |
Surge Protection |
| IEC 801@4 | |
|
|
| |
Output Wave Form |
| Sine wave | |
|
|
| |
Output Voltage (without | 200/208/220/230/240 Vac 3% | ||
Bypass Module) | |||
|
| ||
|
|
| |
Common Mode Noise |
| >60 dB @ 100 kHz | |
Rejection |
| ||
|
| ||
|
|
| |
Transverse Mode Noise |
| >80 dB @ 100 kHz | |
Rejection |
| ||
|
| ||
|
| ||
Input Cord | Detachable 2@meter cord with L6@30P | ||
|
|
| |
Outlets (UPS Module) |
| IEC 320 (1) | |
|
| ||
Output Voltages and Outlets | 120/208V: L6@30R or L14@30R, 4x5@15R | ||
(with BDM) | 120/240V: L6@30R or L14@30R, 4x5@15R | ||
|
| 120: L5@30R, 4x5@15R | |
| 208V Hardwired: 120/208V | ||
| 240V Hardwired: 120/240V | ||
|
| ||
Output Voltages and Outlets | (208V available with Model 2500 only) | ||
(with BIM) | 220/230/240V: 1 x IEC 320@C19 | ||
|
| 3 x IEC 320@C13 | |
| 220/230/240V Hardwired: 220/230/240V | ||
Batteries (10) per Module | 12 Vdc, 5 Ah, maintenance@free rechargeable lead acid | ||
|
|
| |
Battery Module |
| 120 Vdc | |
|
| ||
Operating Environment | Temperature: 10°C to 40°C | ||
|
| (50°F to 104°F) | |
| Humidity: | 5 to 95% | |
|
| (noncondensing) | |
|
|
| |
Agency Approvals | Safety: | EN50091@1 | |
|
| UL 1778 | |
|
| cUL | |
| EMC: | FCC Part 15 Class A | |
|
| EN50091@2 | |
|
|
|
Lucent Technologies Model 3000 UPS Operator's Manual (167@405@119 Issue 3) | 55 |