Lucent Technologies 3000 VA manual UPS Technical Specifications, Emc

Page 65

Specifications 6

UPS Technical Specifications

Input Voltage Range

 

160 to 276 Vac

 

 

 

Bypass Isolation Module

 

187 to 276 Vac

Input Voltage Range

 

 

 

 

 

 

Input Power Factor

 

0.95 Typical

 

 

 

Frequency Range

 

50/60 Hz ￿3 Hz

 

 

 

Surge Protection

 

IEC 801@4

 

 

 

Output Wave Form

 

Sine wave

 

 

 

Output Voltage (without

200/208/220/230/240 Vac ￿3%

Bypass Module)

 

 

 

 

 

Common Mode Noise

 

>60 dB @ 100 kHz

Rejection

 

 

 

 

 

 

Transverse Mode Noise

 

>80 dB @ 100 kHz

Rejection

 

 

 

 

 

Input Cord

Detachable 2@meter cord with L6@30P

 

 

 

Outlets (UPS Module)

 

IEC 320 (1)

 

 

Output Voltages and Outlets

120/208V: L6@30R or L14@30R, 4x5@15R

(with BDM)

120/240V: L6@30R or L14@30R, 4x5@15R

 

 

120: L5@30R, 4x5@15R

 

208V Hardwired: 120/208V

 

240V Hardwired: 120/240V

 

 

Output Voltages and Outlets

(208V available with Model 2500 only)

(with BIM)

220/230/240V: 1 x IEC 320@C19

 

 

3 x IEC 320@C13

 

220/230/240V Hardwired: 220/230/240V

Batteries (10) per Module

12 Vdc, 5 Ah, maintenance@free rechargeable lead acid

 

 

 

Battery Module

 

120 Vdc

 

 

Operating Environment

Temperature: 10°C to 40°C

 

 

(50°F to 104°F)

 

Humidity:

5 to 95%

 

 

(noncondensing)

 

 

 

Agency Approvals

Safety:

EN50091@1

 

 

UL 1778

 

 

cUL

 

EMC:

FCC Part 15 Class A

 

 

EN50091@2

 

 

 

Lucent Technologies Model 3000 UPS Operator's Manual (167@405@119 Issue 3)

55

Image 65
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS UPS with BDM InstallationQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Model 3000 UPS NtroductionLoad Requirements UPS Model and Battery ConfigurationsBattery Times for the UPS with BDM Battery Times for the UPS and BIMIntroduction Afety Warnings This Manual Contains Important Safety InstructionsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Afety Warnings Requisitos de seguridadAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Important Installation Notes Read Before Installing the UPS UPS and Battery Module StorageNstallation Unpacking and InspectionSystems That Require a Serial Interface UPS with Bypass Module InstallationSystems That Require Contact Closure UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes UPS with Bypass Module Startup Phase 200/208/220/230/240VOutput Voltage Indicators Troubleshooting Tips Installation UPS Front Panel S!!! O!!P!!E!!R!!A!!T!!I!!O!!NOperating Modes Normal ModeBattery Mode Bypass ModeBattery Start DiagnosticsBattery Test on Demand Using Maintenance Bypass Using the Bypass ModuleUPS Shutdown Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Ommunication Initial Communications SettingsOptions Front Panel ommuncatons AccessUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate Serial Port Location UPS Communications Interface Port PWR.FAIL Communications Mode Reference ChartPecifications UPS Model 3000 SpecificationsUPS Physical Specifications Model 3000 Specifications with the 50Hz BIM Model 3000 Specifications with the 60Hz BDMEMC UPS Technical Specifications# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Service and Support Resetting the UPSSilencing the Alarm PDM06 Parts ListNdex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 Class a FCC StatementEuropean EMC Statement EC Declaration of Conformity