Lucent Technologies 3000 VA UPS Shutdown, Changing the Output Voltage, Using the Bypass Module

Page 51

UPS Operation 4

UPS Shutdown

Performing a UPS shutdown turns off the power to your protected equipment. Make sure the equipment is prepared for a power5off before shutting down the UPS.

iNOTE Do not perform a UPS shutdown if you want to use the Maintenance Bypass feature on the Bypass Module ￿see •Using the Bypass Module" on page￿41￿.

To perform a UPS shutdown:

￿Press and hold the Output Off button until the long beep ceases (approximately three seconds).

The ￿Indicator remains lit indicating Normal Mode, load offline.

￿Unplug the UPS.

The UPS enters Battery Mode for several seconds. The ￿Indicator turns off and the UPS shuts down.

￿When all LEDs are no longer illuminated on the UPS, switch the circuit breaker to the OFF (O) position on each battery module or cabinet.

Changing the Output Voltage

To change the operating voltage of the UPS:

￿Perform a UPS shutdown as described in the previous section.

￿Follow the instructions in •UPS with Bypass Module Startup" on page 33.

Using the Bypass Module

The Bypass Module provides continuous online power for your equipment. With the Bypass Module, you can replace the UPS without losing power to the load.

Using Maintenance Bypass

Use the following procedure to transfer the critical load to Maintenance Bypass (AC￿Line operation) and remove the UPS:

￿Turn the Bypass switch on the Bypass Module to the BYPASS position (see Figure￿18). The Bypass Module is now powering your equipment from utility power.

￿Press and hold the Output Off button until the long beep ceases (approximately three seconds). The ￿Indicator remains lit.

￿#￿￿￿" ￿￿￿￿￿￿￿￿￿￿￿! ￿￿￿￿￿ ￿￿￿￿ ￿￿￿ ￿￿￿ ￿"￿ ￿! ￿￿￿#￿￿ ￿￿6￿$￿￿5$￿￿￿ I!!#￿ ￿￿

41

Image 51
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS UPS with BDM InstallationQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Model 3000 UPS NtroductionLoad Requirements UPS Model and Battery ConfigurationsBattery Times for the UPS with BDM Battery Times for the UPS and BIMIntroduction Afety Warnings This Manual Contains Important Safety InstructionsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Afety Warnings Requisitos de seguridadAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Unpacking and Inspection UPS and Battery Module StorageImportant Installation Notes Read Before Installing the UPS NstallationUPS with Bypass Module Installation Systems That Require Contact ClosureSystems That Require a Serial Interface UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes UPS with Bypass Module Startup Phase 200/208/220/230/240VOutput Voltage Indicators Troubleshooting Tips Installation UPS Front Panel S!!! O!!P!!E!!R!!A!!T!!I!!O!!NOperating Modes Normal ModeBattery Mode Bypass ModeDiagnostics Battery Test on DemandBattery Start Changing the Output Voltage Using the Bypass ModuleUsing Maintenance Bypass UPS ShutdownUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Ommunication Initial Communications SettingsOptions Front Panel ommuncatons AccessUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate Serial Port Location UPS Communications Interface PortPWR.FAIL Communications Mode Reference ChartUPS Model 3000 Specifications UPS Physical SpecificationsPecifications Model 3000 Specifications with the 50Hz BIM Model 3000 Specifications with the 60Hz BDMEMC UPS Technical Specifications# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Resetting the UPS Silencing the AlarmService and Support PDM06 Parts ListNdex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 EC Declaration of Conformity FCC StatementClass a European EMC Statement