Installation 3

22See the following table for specifications and tightening torque.

 

 

Power Cable Terminations

 

Tightening Torque

 

 

 

 

 

 

 

 

Wire Function

Terminal

Terminal Wire

Entrelec

Phoenix

 

 

 

Position

Size Rating*

 

Contact

 

 

 

 

 

 

 

Input

 

Ground

1

22-12 AWG

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

 

 

 

 

(0.34-4 mm2)

 

 

L1

2

 

 

 

 

 

 

 

 

 

 

 

 

L2/Neutral

3

18-10 AWG

3.5 - 5.3 lb/in

4.5 - 7.0 lb/in

 

 

 

 

 

 

 

 

(0.75-6 mm2)

Output

 

L1

5

 

 

 

 

 

 

 

 

 

 

 

 

 

L2/Neutral

6

 

 

 

 

 

 

 

 

 

 

 

 

Ground

8

22-12 AWG

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

 

 

 

 

 

 

No Connection

4, 7

(0.34-4 mm2)

 

 

 

 

 

*Use #164AWG (1.5 mm2) 75_C copper wire minimum.

23Replace the terminal box cover.

24If you are using a Remote Emergency Power5Off (REPO) switch, follow the instructions in •REPO Installation" on page 31.

25Start the UPS according to the •UPS with Bypass ￿odule Startup" procedure on page 33.

REPO Installation

WARNING Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation.

The REPO switch is a customer5supplied switch that can disconnect UPS output voltage from your protected equipment. To use a REPO switch, you need external wiring and a switch with the following specifications:

￿The switch should be a wall5mounted, momentary5contact, normally open, pushbutton switch.

￿￿inimum ratings of 240 Vac and 35 mA.

￿Wire should be 18 AWG minimum.

CAUTION The black and white REPO wires are at high'voltage potential (240V). Refer to your local electrical code for proper installation of the high'voltage REPO wires.

Lucent Technologies Model 3000 UPS Operator's Manual (16744054119 Issue 3)

31

Image 41
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS UPS with BDM InstallationQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Model 3000 UPS NtroductionLoad Requirements UPS Model and Battery ConfigurationsBattery Times for the UPS with BDM Battery Times for the UPS and BIMIntroduction Afety Warnings This Manual Contains Important Safety InstructionsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Afety Warnings Requisitos de seguridadAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Important Installation Notes Read Before Installing the UPS UPS and Battery Module StorageNstallation Unpacking and InspectionSystems That Require a Serial Interface UPS with Bypass Module InstallationSystems That Require Contact Closure UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes UPS with Bypass Module Startup Phase 200/208/220/230/240VOutput Voltage Indicators Troubleshooting Tips Installation UPS Front Panel S!!! O!!P!!E!!R!!A!!T!!I!!O!!NOperating Modes Normal ModeBattery Mode Bypass ModeBattery Start DiagnosticsBattery Test on Demand Using Maintenance Bypass Using the Bypass ModuleUPS Shutdown Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Ommunication Initial Communications SettingsOptions Front Panel ommuncatons AccessUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate Serial Port Location UPS Communications Interface PortPWR.FAIL Communications Mode Reference ChartPecifications UPS Model 3000 SpecificationsUPS Physical Specifications Model 3000 Specifications with the 50Hz BIM Model 3000 Specifications with the 60Hz BDMEMC UPS Technical Specifications# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Service and Support Resetting the UPSSilencing the Alarm PDM06 Parts ListNdex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 Class a FCC StatementEuropean EMC Statement EC Declaration of Conformity