Lucent Technologies 3000 VA manual 604Hz BDM 240

Page 53

UPS Operation 4

Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass (AC Line operation) to the UPS:

￿Reconnect the battery modules to the battery connector on the UPS rear panel.

￿Turn the circuit breaker on all battery modules to the ON ( ) position.

￿Plug the Y+cord of the Bypass Module into the power connectors on the UPS as shown in Figure￿18.

i NOTE Steps 4 through 7 are for changing the output voltage. The output voltage is factory(configured for 230V. If you do not need to change the UPS output voltage, skip to Step￿8. Use the following table to select the correct output voltage according to your Bypass Module.

Bypass Module

UPS Voltage Selection*

Model Number

 

 

 

604Hz BDM 208: 120/208

208

 

 

604Hz BDM 208: 120/240

208

 

 

604Hz BDM 208: 120

208

 

 

604Hz BDM 240: 120/240

Set to 220V for 110/220V BDM output

 

Set to 230V for 115/230V BDM output

 

Set to 240V for 120/240V BDM output

 

 

604Hz BDM 240: 120

Set to 220V for 110V BDM output

 

Set to 230V for 115V BDM output

 

Set to 240V for 120V BDM output

 

 

504Hz BIM 208 ￿Model 2500 only￿

208

 

 

504Hz BIM 220

220

 

 

504Hz BIM 230

230

 

 

504Hz BIM 240

240

*The UPS output voltage should be set according to local mains voltage.

4Press the Output Off button until the alarm beeps. All indicators flash simultaneously.

Lucent Technologies Model 3000 UPS Operator￿s Manual ￿16744054119 Issue 3￿

43

Image 53
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS UPS with BDM InstallationQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Model 3000 UPS NtroductionLoad Requirements UPS Model and Battery ConfigurationsBattery Times for the UPS with BDM Battery Times for the UPS and BIMIntroduction Afety Warnings This Manual Contains Important Safety InstructionsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Afety Warnings Requisitos de seguridadAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings Important Installation Notes Read Before Installing the UPS UPS and Battery Module StorageNstallation Unpacking and InspectionSystems That Require a Serial Interface UPS with Bypass Module InstallationSystems That Require Contact Closure UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes UPS with Bypass Module Startup Phase 200/208/220/230/240VOutput Voltage Indicators Troubleshooting Tips Installation UPS Front Panel S!!! O!!P!!E!!R!!A!!T!!I!!O!!NOperating Modes Normal ModeBattery Mode Bypass Mode Battery Start Diagnostics Battery Test on Demand Using Maintenance Bypass Using the Bypass ModuleUPS Shutdown Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Ommunication Initial Communications SettingsOptions Front Panel ommuncatons AccessUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate Serial Port Location UPS Communications Interface PortPWR.FAIL Communications Mode Reference ChartPecifications UPS Model 3000 SpecificationsUPS Physical Specifications Model 3000 Specifications with the 50Hz BIM Model 3000 Specifications with the 60Hz BDMEMC UPS Technical Specifications# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Service and Support Resetting the UPSSilencing the Alarm PDM06 Parts ListNdex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 Class a FCC StatementEuropean EMC Statement EC Declaration of Conformity