Lucent Technologies 3000 VA manual UPS Model and Battery Configurations, Load Requirements

Page 12

1Introduction

UPS Model and Battery Configurations

This UPS is designed to work with single?phase, three?wire, AC power sources. There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment:

￿Load requirements

￿Battery times

Load Requirements

The load is the equipment to be protected by the UPS. Select the UPS model that meets the power consumption requirements of the load in volt?amperes (VA). The total load VA should not exceed the UPS VA rating. To determine the total load requirements:

￿Obtain the load ratings from either the nameplate or operator's manual of the equipment to be protected by the UPS. The ratings are listed in either watts (W), amperes or amperes max (A), or volt?amperes.

￿If the rating is in watts, multiply by 1.4 to obtain the VA requirement (this is the typical relationship between watts and volt?ampere ratings in most computing equipment).

If the rating is in amperes or amperes max, multiply by the input voltage to obtain the VA requirement.

￿Add all of the resultant VA ratings together to obtain the total load requirements of the equipment to be protected (see Figure￿2).

 

3￿COMPUTERS

 

 

3￿MONITORS

 

 

200￿WATTS

 

 

1￿AMP

 

 

EACH

 

 

EACH￿AT￿240V

 

 

 

 

 

 

 

3￿x￿200￿WATTS￿x￿1.4￿=￿840￿VA

3￿x￿1￿AMP￿x￿240￿=￿720￿VA

EXTERNAL

MODEM

50￿VA

50￿VA

840￿VA￿+￿720￿VA￿+￿50￿VA￿=￿1610￿VA￿(Total￿Load￿Requirements)

Figure 2. Volt#Amperes Calculation Example

If the total load requirements of the equipment exceeds the capacity of the UPS, you must either reduce the equipment, or use a UPS with a larger load capacity.

When deciding on which pieces of equipment to remove from the UPS, select equipment that has a lower priority for power protection. Computers, monitors, and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs.

2

￿#￿￿￿" ￿￿￿￿￿￿￿￿￿￿￿! ￿￿￿￿￿ ￿￿￿￿ ￿￿￿ ￿￿￿ ￿"￿ ￿! ￿￿￿#￿￿ ￿￿6￿$￿￿5$￿￿￿ I!!#￿ ￿￿

Image 12
Contents ##*&% % *& %+# +%* !%&# +*# &, -*$ Page Page Special Symbols UPS with BDM Installation UPSQuick Start UPS with BIM Installation Quick Start Able of Contents Troubleshooting Ntroduction Model 3000 UPSUPS Model and Battery Configurations Load RequirementsBattery Times for the UPS and BIM Battery Times for the UPS with BDMIntroduction This Manual Contains Important Safety Instructions Afety WarningsSikkerhedsanvisninger Belangrijke Veiligheidsinstructies Tärkeitä turvaohjeita Consignes de Sécurité Safety Warnings Wichtige Sicherheitsanweisungen Importanti istruzioni di sicurezza Safety Warnings Viktig Sikkerhetsinformasion Regulamentos de Segurança Requisitos de seguridad Afety WarningsAfet3 Warnings Viktig säkerhetsinformation Safety Warnings Safety Warnings UPS and Battery Module Storage Important Installation Notes Read Before Installing the UPSNstallation Unpacking and InspectionUPS with Bypass Module Installation Systems That Require Contact ClosureSystems That Require a Serial Interface UPS with Distribution Module Setup UPS with Isolation Module Setup For Stability Repo UPS with BIM Rear Panel Installation UPS with Hardwired Bypass Module Rear Panel Hz Hardwired BIM Terminal Block Repo Installation Mounting Holes Phase 200/208/220/230/240V UPS with Bypass Module StartupOutput Voltage Indicators Troubleshooting Tips Installation S!!! O!!P!!E!!R!!A!!T!!I!!O!!N UPS Front PanelNormal Mode Operating ModesBypass Mode Battery ModeDiagnostics Battery Test on DemandBattery Start Using the Bypass Module Using Maintenance BypassUPS Shutdown Changing the Output VoltageUPS with Bypass Module Rear Panel 6%Hz BDM Shown 604Hz BDM 240 Output Voltage Indicators Initial Communications Settings OmmunicationFront Panel ommuncatons Access OptionsUPS Serial Communications Menu Ascii Select LAN Configuration Select Baud Rate UPS Communications Interface Port Serial Port LocationCommunications Mode Reference Chart PWR.FAILUPS Model 3000 Specifications UPS Physical SpecificationsPecifications Model 3000 Specifications with the 60Hz BDM Model 3000 Specifications with the 50Hz BIMUPS Technical Specifications EMC# ! ! # 6$5$ I!!# Roubleshooting Troubleshooting Resetting the UPS Silencing the AlarmService and Support Parts List PDM06Ndex Numeric LOWBATT,49 Over temperature,alarm,58 UTILFAIL,49 FCC Statement Class aEuropean EMC Statement EC Declaration of Conformity