System Connectors
Except for the power output and grounding connectors, all signal wire connections are made to removable two- or
A
B
C
D
E
F
G
A - 10 Pole Connector Plug
B - Fault Contacts — Use NO, COM and NC to hook up a siren, light, optional GenAlert, etc. to alert you in case of a fault. Contacts reverse state (NO goes to NC and vice versa) upon a fault condition.
C - Transfer Switch Communication — Use TxRx and TxRx GND to transfer switch to monitor generator functions.
D - Remote LED Output — Use this to hook up the remote LED supplied with the generator. The remote LED will turn on and off in a series of blinks if certain faults are detected in the generator.
E - +12 Volt DC, .5 Amp Output — Internal power supply.
F - 240 Volt Utility — Use to hook up the 240V utility leads from the transfer switch to the generator.
G - 2 Pole Connector Plug
13