Briggs & Stratton 202826GS Controls, Automatic Operation Sequence, Setting Exercise Timer

Page 20

Controls

See the Operator’s Manual for complete description of the home generator controls.

Operation

Automatic Operation Sequence

The generator’s control panel houses a logic control circuit board. This control board constantly monitors utility power source voltage. Should that voltage drop below a preset level, control board action will signal the engine to crank and start.

When utility source voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 10 second timer. The timer is used to ‘sense’ brown- outs.

Once the timer has expired, the engine will crank and start.

Utility Voltage Pickup Sensor

This sensor monitors utility power supply voltage. When that voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool-down.

Engine Cool-down Timer

When the load is transferred back to the utility power source, the engine cool-down timer starts timing.

The timer will run for about one minute, then the generator will stop.

Minimum engine run time is 5 minutes.

Setting Exercise Timer

The home generator is equipped with an exercise timer that will start and exercise the system once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).

A button on the control panel is labeled “Set Exercise” (see System Control Panel). The specific day and the specific time of day this button is pressed is programmed into the control board memory. This date and time is then used to automatically initiate the system exercise cycle. The “SET EXERCISE” legend on the control panel will flash until the set exercise cycle is set.

To perform the Set Exercise procedure:

1.Choose the day and time you want your home generator to exercise.

2.On that day and time, press and hold down the “Set Exercise” button for three seconds.

NOTE: “SET EXERCISE” will flash until the button is pressed for three seconds, then “SET EXERCISE” will illuminate for 5 seconds, and finally turn off.

For example, if you press the “Set Exercise” button on Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM (+/- 1/2 hour).

NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed. The exerciser will need to be re-set if the 15 Amp fuse is removed or changed, or if the 12 Volt DC battery is disconnected.

If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.

Installation Inspection

Complete the ”Installation Checklist” as you make the inspection. Ensure all items have been filled-in and all signatures have been obtained. Instruct the owner to mail the white copy to:

Briggs & Stratton Power Products Warranty Registration

P. O. Box 239

Jefferson, WI 53549-0239

More detailed Operating, Maintenance and Troubleshooting information is given in the Operator’s Manual.

20

BRIGGSandSTRATTON.COM

Image 20
Contents Home Generator System Where to Find Us Date of Purchase GeneratorEngine Model Number Model Revision Serial NumberTable of Contents Safety Rules Hazard Symbols and MeaningsPage Installation Never operate generator without protective housing or coversInstaller Responsibilities Unpacking PrecautionsShipment Contents Equipment DescriptionGeneral Location Guidelines Home Generator LocationGenerator Location Fuel and Electrical Inlet Locations Lifting the GeneratorAccess Doors To Open an Access DoorTo Close an Access Door Gaseous Fuel SystemNo leakage is permitted Fuel Consumption Natural Gas LP VaporFuel Pipe Sizing LP Vapor Natural+12 Volt DC, .5 Amp Output Internal power supply System ConnectorsPole Connector Plug Transfer Switch Communication Fault Detection SystemGenerator AC Connection System Grounding the GeneratorFuel Supply System Final Installation ConsiderationsSystem Control Panel Engine Adjustment Initial Start-up No LoadPage Schematic Wiring Diagram Setting Exercise Timer Installation InspectionControls OperationGenerador doméstico Dónde encontrarnos Fecha de compra GeneradorMotor Número de Modelo Revisión Número de SerieInstrucciones importantes de seguridad Instalación Mandos UtilizaciónSímbolos de Peligro y Significados BRIGGSandSTRATTON.COMTensión peligrosa Ate para arriba el pelo largo y quite la joyeríaInstala el fusible se puede producir el arranque del motor No modifique al generador en ninguna formaInstalación Pautas Generales para la Ubicación del Generador Ubicación del Sistema de Generador de DomésticoUbicación del Generador Dimensiones de la Entrada para Electricidad y Combustible Elevación del GeneradorPuertas de Acceso Sistema de combustible gaseosoPara abrir una puerta de acceso Para cerrar una puerta de accesoSe debe contar también con una abertura para manómetro Dimensiones de la Cañería de Combustible Consumo de CombustibleGas Natural Vapor de PL Vapor de GasConexiones de Sistema Cableado para toma de 10 polosSalida de +12 V CC y 0,5 a Fuente de alimentación interna Cableado para toma bipolarSistema de Conexión de c.a. del Generador Interconexiones del Circuito de ControlComunicación del conectador Conexión a Tierra del GeneradorPanel de Control del Sistema Sistema de Suministro de CombustibleInstale el fusible de 15 Amperios en el panel de control Arranque inicial sin cargaAjuste del Motor Mandos UtilizaciónSecuencia de operación automática Cargue el generador a plena cargaTemporizador de enfriamiento del motor Configuración del temporizador de prácticaInspección posterior a la instalación Manuel d’Installation et Démarrage Où nous trouver Date d’achat GénératriceMoteur Numéro de modèle Révision Numéro de sérieDirectives de sécurité importantes Installation Commandes FonctionnementSymboles de Danger et Moyens Directives de sécurité importantesSécurité Certains composants de ce produit ainsi que lesTension dangereuse Avis Responsabilités de l’Installateur Description de l’équipementResponsabilités de l’Acheteur Précautions Lors du DéballageDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteInstallez l’unité à l’extérieur Seulement Soulèvement de la Génératrice Portes d’Accès Le système de combustible gazeuxRetrait des commandes La sortie pour manomètre permet l’installation temporaireAucune fuite ne peut être tolérée CapacitéDimension du Réservoir de Propane Nécessaire Consommation de CombustibleGas Naturel Vapeur PL Grosseur du Tuyau de CombustibleConnexions de système Interconnexions du Circuit de Commande Mise à la Masse de la GénératriceCommunication du commutateur de transfert Système de Détection des PannesSystème d’Alimentation en Combustible Tableau de Commande du SystèmeConsidérations pour l’installation finale Démarrage initial sans charge Réglage du MoteurRéglez l’interrupteur de système de la génératrice sur Auto Recommencez le processus jusqu’à ce que le moteur démarreFrançais Commandes Vérification installationFonctionnement Séquence de fonctionnement automatique