Briggs & Stratton 202826GS system manual Home Generator Location, General Location Guidelines

Page 8

Home Generator Location

Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.

warning

Exhaust heat/gases can ignite combustibles or structures causing a fire.

DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.

Keep at least minimum distances shown in General Location Guidelines in Installation Manual to insure for proper generator cooling and maintenance clearances.

Generator Location

Install generator outdoors in an area which will not accumulate deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator.

WARNING

Running engine gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting, or death.

Operate generator ONLY outdoors.

Install a battery operated carbon monoxide alarm near the bedrooms.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.

General Location Guidelines

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet our outlet openings.

Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch and fuel supply to reduce the length of wiring, conduit, and piping.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Minimum (MIN) clearances from aerial view of generator (B) to combustible (D), and non-combustible (A) materials is shown below.

These distances are provided to give generator location guidance relative ONLY to combustibles, generator cooling, and maintenance.

The minimum distances in the figure are as shown. All four sides of the generator cannot be enclosed or restricted, even if the minimum distances are maintained. DO NOT connect (A) and/or (D) to (E)

A roof cannot be used.

Exhaust (C) must not be allowed to accumulate.

 

 

5’ (1.5m)

 

 

2’

 

 

(62cm)

 

 

3’

 

 

(1m)

 

 

B

 

5’ (1.5m)

5’ (1.5m)

D

A

C

 

 

 

5’ (1.5m)

 

E

E

ANon-Combustible material with Fire Resistant Rating of 1 hour or greater

BHome Standby Generator

CEngine Exhaust

DCombustible Material or Structure with a Fire Resistance Rating of less than 1 hour.

EAny structure or material. DO NOT connect (A) and/or (D) to (E).



BRIGGSandSTRATTON.COM

Image 8
Contents Home Generator System Where to Find Us Date of Purchase GeneratorEngine Model Number Model Revision Serial NumberTable of Contents Safety Rules Hazard Symbols and MeaningsPage Installation Never operate generator without protective housing or coversInstaller Responsibilities Unpacking PrecautionsShipment Contents Equipment DescriptionGeneral Location Guidelines Home Generator LocationGenerator Location Fuel and Electrical Inlet Locations Lifting the GeneratorAccess Doors To Open an Access DoorTo Close an Access Door Gaseous Fuel SystemNo leakage is permitted Fuel Consumption Natural Gas LP VaporFuel Pipe Sizing LP Vapor Natural+12 Volt DC, .5 Amp Output Internal power supply System ConnectorsPole Connector Plug Transfer Switch Communication Fault Detection SystemGenerator AC Connection System Grounding the GeneratorFuel Supply System Final Installation ConsiderationsSystem Control Panel Engine Adjustment Initial Start-up No LoadPage Schematic Wiring Diagram Setting Exercise Timer Installation InspectionControls OperationGenerador doméstico Dónde encontrarnos Fecha de compra GeneradorMotor Número de Modelo Revisión Número de SerieInstrucciones importantes de seguridad Instalación Mandos UtilizaciónSímbolos de Peligro y Significados BRIGGSandSTRATTON.COMTensión peligrosa Ate para arriba el pelo largo y quite la joyeríaInstala el fusible se puede producir el arranque del motor No modifique al generador en ninguna formaInstalación Pautas Generales para la Ubicación del Generador Ubicación del Sistema de Generador de DomésticoUbicación del Generador Dimensiones de la Entrada para Electricidad y Combustible Elevación del GeneradorPuertas de Acceso Sistema de combustible gaseosoPara abrir una puerta de acceso Para cerrar una puerta de accesoSe debe contar también con una abertura para manómetro Dimensiones de la Cañería de Combustible Consumo de CombustibleGas Natural Vapor de PL Vapor de GasConexiones de Sistema Cableado para toma de 10 polosSalida de +12 V CC y 0,5 a Fuente de alimentación interna Cableado para toma bipolarSistema de Conexión de c.a. del Generador Interconexiones del Circuito de ControlComunicación del conectador Conexión a Tierra del GeneradorPanel de Control del Sistema Sistema de Suministro de CombustibleInstale el fusible de 15 Amperios en el panel de control Arranque inicial sin cargaAjuste del Motor Mandos UtilizaciónSecuencia de operación automática Cargue el generador a plena cargaTemporizador de enfriamiento del motor Configuración del temporizador de prácticaInspección posterior a la instalación Manuel d’Installation et Démarrage Où nous trouver Date d’achat GénératriceMoteur Numéro de modèle Révision Numéro de sérieDirectives de sécurité importantes Installation Commandes FonctionnementSymboles de Danger et Moyens Directives de sécurité importantesSécurité Certains composants de ce produit ainsi que lesTension dangereuse Avis Responsabilités de l’Installateur Description de l’équipementResponsabilités de l’Acheteur Précautions Lors du DéballageDégagement Autour de la Génératrice Emplacement du Génératrice d’état d’AttenteInstallez l’unité à l’extérieur Seulement Soulèvement de la Génératrice Portes d’Accès Le système de combustible gazeuxRetrait des commandes La sortie pour manomètre permet l’installation temporaireAucune fuite ne peut être tolérée CapacitéDimension du Réservoir de Propane Nécessaire Consommation de CombustibleGas Naturel Vapeur PL Grosseur du Tuyau de CombustibleConnexions de système Interconnexions du Circuit de Commande Mise à la Masse de la GénératriceCommunication du commutateur de transfert Système de Détection des PannesSystème d’Alimentation en Combustible Tableau de Commande du SystèmeConsidérations pour l’installation finale Démarrage initial sans charge Réglage du MoteurRéglez l’interrupteur de système de la génératrice sur Auto Recommencez le processus jusqu’à ce que le moteur démarreFrançais Commandes Vérification installationFonctionnement Séquence de fonctionnement automatique