UL Required Fuses for Short Circuit Rating
UL requires R/C fuses, special purpose fuses (JFHR2) or semiconductor fuses rated 700VAC be used to obtain the short circuit current ratings required by UL.
| Fuse Manufacturer | Fuse | Short Circuit Rating | |
Model Number | Bussman (300 KA A.I.C.) | Ferraz (200 KA A.I.C.) | Current Rating | Amperes |
| Catalog Number | Catalog Number | Amperes | |
|
| |||
|
|
|
|
|
MD9 to MD16 | 170M3110 | 6.6 URD 30 D08 A 0063 | 63 | 5,000 |
MD23 to MD30 | 170M3112 | 6.6 URD 30 D08 A 0100 | 100 | 5,000 |
MD44 | 170M3114 | 6.6 URD 30 D08 A 0160 | 160 | 5,000 |
MD59 | 170M3115 | 6.6 URD 30 D08 A 0200 | 200 | 5,000 |
MD72 to MD85 | 170M3116 | 6.6 URD 30 D08 A 0250 | 250 | 10,000 |
MD105 to MD146 | 170M3119 | 6.6 URD 30 D08 A 0400 | 400 | 10,000 |
MD174 to MD202 | 170M3121 | 6.6 URD 30 D08 A 0500 | 500 | 10,000 |
|
|
|
|
|
MD242 | 170M4114 | 6.6 URD 31 D08 A 0500 | 500 | 10,000 |
MD300 | 170M4114 | 6.6 URD 31 D08 A 0500 | 500 | 18,000 |
MD370 | 170M4116 | 6.6 URD 31 D08 A 0630 | 630 | 18,000 |
MD500 | 170M6113 | 6.6 URD 33 D08 A 0900 | 900 | 18,000 |
MD600 | 170M6113 | 6.6 URD 33 D08 A 0900 | 900 | 30,000 |
MD750 | 170M6116 | 6.6 URD 33 D08 A 1250 | 1250 | 30,000 |
MD900 | 170M6116 | 6.6 URD 33 D08 A 1250 | 1250 | 42,000 |
MD1100 | 170M6116 |
| 1500 | 42,000 |
MD1200 | (2) 170M6116 |
| (2) 1000 | 42,000 |
Main Input Contactor An IEC or NEMA rated contactor is recommended at the input power to the control. The
| Table | ||
Terminal | Description |
| |
L1, L2, L3 | Input AC power terminals. Connect input isolated 3 phase supply (any phase to any terminal). | ||
T1, T2, T3 | Output Power Terminals. Connect an induction motor to these terminals. For correct motor rotation, | ||
connection of these phases must correspond with the supply connections (L1, L2, L3). | |||
| |||
|
| ||
X1, X2 | Control Supply Input. The internal circuits require power from a 115VAC or 230VAC source (Table | ||
A selector switch is provided to select the voltage range of the source that is connected to this input. | |||
| |||
|
| ||
| Remote Start/Stop Input. A voltage present across these terminals will initiate a “Start”. | ||
S1, S0 | Removing the voltage from across these terminals will initiate a “Stop”. | ||
| Note that the factory setting is keypad Start/Stop. | ||
|
|
| |
Relay K1 | Pins 11 and 12 are the | normally closed “Run” relay contacts. | |
Pins 11 and 14 are the | normally open “Run” relay contacts. | ||
| |||
Relay K2 | Pins 21 and 22 are the | normally closed “Top of Ramp” relay contacts. | |
Pins 21 and 24 are the | normally open “Top of Ramp” relay contacts. | ||
|
MN850 | Installation |