EMC Installation Instructions

To ensure electromagnetic compatibility (EMC), the following installation instructions should be completed. These steps help to reduce interference.

Consider the following:

Grounding of all system elements to a central ground point

Shielding of all cables and signal wires

Filtering of power lines

A proper enclosure should have the following characteristics:

A)All metal conducting parts of the enclosure must be electrically connected to the back plane. These connections should be made with a grounding strap from each element to a central grounding point . ￿

B)Keep the power wiring (motor and power cable) and control wiring separated. If these wires must cross, be sure they cross at 90 degrees to minimize noise due to induction.

C)The shield connections of the signal and power cables should be connected to the screen rails or clamps. The screen rails or clamps should be conductive clamps fastened to the cabinet. ￿

D)The cable to the regeneration resistor must be shielded. The shield must be connected to ground at both ends.

E)The location of the AC mains filter has to be situated close to the drive so the AC power wires are as short as possible.

F)Wires inside the enclosure should be placed as close as possible to conducting metal, cabinet walls and plates. It is advised to terminate unused wires to chassis ground. ￿

G)To reduce ground current, use at least a 10mm2 (6 AWG) solid wire for ground connections.

￿Grounding in general describes all metal parts which can be connected to a protective conductor, e.g. housing of cabinet, motor housing, etc. to a central ground point. This central ground point is then connected to the main plant (or building) ground.

￿Or run as twisted pair at minimum.

Cable Screens Grounding

Cable (Twisted Pair Conductors)

Conductive Clamp – Must contact bare cable shield and be secured to metal backplane.

MN850

Appendix A-3

Image 56
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DIntroduction Limited WarrantySection General Information Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instructions For clearance mounting holes Tools RequiredMounting Instruction For tapped mounting holes AC Main Circuit Catalog Number Connection DescriptionsUL Required Fuses for Short Circuit Rating Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20115 / 230VAC Three Wire ControlTwo Wire Control Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Inputs Menu Password MenuPermanent Store Menu Trips Menu Outputs MenuParameters Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationOperating Conditions Input RatingsStorage Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E 340 810 500 250 Remote Keypad Mounting Template500 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500