Baldor MN850, Baldor manual Appendix D Voltage Surge Protection, Grounding

Page 64

Appendix D

Voltage Surge Protection

Grounding

Proper grounding is extremely important. The symptoms produced by improper

 

grounding are obvious. Sometimes filters and other expensive devices are added to

 

reduce the effects of problems caused by poor grounding. There can be several

 

reference points (neutrals) in a circuit but there should always only be one ground point.

 

Neutral and ground are not the same. Neutral should normally be a non current carrying

 

conductor, but it should be sized to carry momentary current caused be short circuits in

 

the equipment. All of the neutrals in a system should connect at a central point and that

 

point should be connected to the system ground.

 

The goal is to minimize the current through the ground conductor. Circulating ground

 

current is a source of electrical noise normally associated with unbalanced voltages or

 

unbalanced loads. Capacitive or inductive coupling between power lines and the neutral

 

or ground conductors is another noise source. Currents that flow through capacitive

 

paths or from a magnetic field tend to change rapidly and produce high frequency

 

interference called RFI (radio frequency interference).

 

Good grounding is also important to minimize the effects of large voltage spikes that can

 

create significant current flow in the ground conductors. The source of these voltages

 

can be lightning striking the power lines, switching of large power loads and others. A

 

balanced three phase four wire system with a system ground as shown in Figure D-1 can

 

minimize noise problems normally associated with grounding. AC power and motor

 

leads should be as short as possible and enclosed in conduit or shielded cable should be

 

used. Power wires and Motor leads should never be in the same conduit.

Figure D-1

 

 

Control

 

Note: Wiring shown for clarity of grounding

 

 

Enclosure

 

 

method only. Not representative of

 

 

 

 

 

 

L1 L2 L3

T1 T2 T3

actual terminal block location.

 

 

 

AC Main Supply

L1

 

 

 

 

 

 

 

 

L2

 

 

 

 

L3

 

 

Safety

 

Earth

 

 

Four Wire

 

 

Ground

 

 

 

 

“Wye”

 

 

Driven Earth Ground Rod

Route all 4 wires L1, L2, L3 and Earth (Ground)

(Plant Ground)

together in conduit or shielded cable.

Route all 4 wires T1, T2, T3 and Motor Ground together in conduit or shielded cable.

Connect all wires (including motor ground) inside the motor terminal box.

Ground per NEC and Local codes.

MOV

(Metal Oxide Varistor)

 

Baldor recommends that MOV devices be installed at the input power connections to the

 

Soft–Start control to provide “phase–to phase” and “phase–to–ground” voltage spike

 

protection. Three MOV devices can be connected in “WYE” configuration with an

 

additional MOV device connected to ground. Figures D-2 and D-3 shows how to connect

 

the MOV’s into the various power distribution system designs. Voltage spikes on any

 

phase will be conducted to ground by the lowest impedance path (phase–to–phase or

 

phase–to–ground).

MN850

Voltage Surge Protection D-1

Image 64
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DSection General Information Limited WarrantyIntroduction Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instruction For tapped mounting holes Tools RequiredMounting Instructions For clearance mounting holes AC Main Circuit UL Required Fuses for Short Circuit Rating Connection DescriptionsCatalog Number Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20Two Wire Control Three Wire Control115 / 230VAC Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Permanent Store Menu Password MenuInputs Menu Parameters Menu Outputs MenuTrips Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationStorage Conditions Input RatingsOperating Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E 500 Remote Keypad Mounting Template340 810 500 250 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500