Input Ratings
Input Voltage Range | |
| |
Phase | Three Phase |
Input Frequency | 60/50 HZ ± 5% |
Overload Rating | Continuous 115% of FLA; 350% for 30 seconds. |
Duty Cycle | Continuous |
Peak Inverse Voltage | |
| |
S0, S1 | 12VDC or 24VDC |
X1, X2 | 115VAC (98 – 126VAC) or 230VAC (196 – 253VAC) |
Storage Conditions |
|
Ambient Temperature: | |
Humidity: | 0 - 95% RH |
Operating Conditions |
|
Enclosure: | NEMA 1 – Wall mounted (Industrial indoor, general purpose) |
| For other enclosures, contact Baldor. |
| The SCR’s generate about 3.3 watts of heat per running amp (motor |
| FLA). If the control is mounted in an enclosure, the installer must |
| provide fans or blower with sufficient ventilation. Fan or blower |
| should be rated for at least 0.8 CFM per ampere of motor FLA rating. |
| Baldor provided enclosures are designed to dissipate the heat from |
| the SCR’s. |
Humidity: | 0 - 85% RH |
Control Heat Loss | 3.3 Watt per running ampere of input current |
Ambient Operating Temperature: | |
| |
Altitude: | Sea level to 3300 Feet (1000 Meters) |
| Derate 1% per 330 Feet (100 Meters) above 3300 Feet |
Derating | Derate Amp rating 1% per 330 Feet (100 Meters) above 3300 Feet |
| Derate Amp rating 2% per ° C over 40 ° C to 60 ° C Max |
Output Relays – K1 and K2 contacts | Category AC1, 230VAC, 3A. |
MN850 |