In–Delta Connections For Delta connected motors, the Soft–Start can be connected inside the delta windings. This connection method is shown in Figure 2-2.

 

 

 

Figure 2-2

In–Delta Soft–Start Connections

 

 

 

 

L1

L2

L3

 

 

 

 

L1

L2

L3

 

 

 

 

Earth

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1

* Circuit

 

 

 

 

 

Alternate *

 

 

 

 

Note 2

 

Fuse

 

 

Note 1

 

Breaker

 

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Optional components not provided with control.

Note 3, 9

 

 

 

 

 

 

 

 

 

 

 

L1

L2

L3

 

 

 

 

 

 

 

 

 

 

 

 

X1

115/230VAC

 

 

 

 

 

 

 

 

 

X2

In–Delta connections for correct motor rotation

 

 

Baldor

 

Note 6, 7

 

 

Digital

 

 

 

Soft–Start

Motor

 

 

 

 

Soft–Start

 

 

 

 

 

 

 

 

 

 

Terminal

Terminal

 

 

 

T1

T2

T3

 

 

 

T1

T3

 

 

 

 

 

 

T2

T1

 

 

 

 

 

 

 

 

 

T3

T2

 

 

 

 

T1

 

 

 

L1

T5

 

 

 

 

T3

T2

 

 

 

L2

T6

 

 

 

* AC Motor

 

G

 

 

 

L3

T4

 

 

 

 

T5

T4

 

 

 

 

 

 

 

 

 

T6

 

 

 

 

 

 

 

 

Note 8

 

 

 

 

 

 

 

 

 

 

See Recommended Tightening Torques in Table 2-4.

Notes:

1.See “Protective Devices” described previously in this section.

2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.

3.Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.

4.Derating factor for soft–start is 57%.

5.Parameter P6– Firing Mode must be set to 1.

6.X1 and X2 control terminal power must be present or the logic circuits will not work. Either 115VAC or 230VAC can be used. Be sure the 115/230VAC switch (Control Voltage Selector Switch) is set to the proper voltage before you apply power.

7.The X1 and X2 control voltage input has different VA ratings depending on enclosure size, see Table 2-3.

8.For reversing operation, L1 and L2 should be switched. Reversing any two of the three input phases will reverse the motor rotation.

9.To protect the control, be sure to add MOV protection. Refer to Appendix D for additional information.

Fan Connections – Size 3 and 4 only Size 1 and 2 controls do not have fan connections. For Size 3 controls make the fan connections as shown in Figure 2-3.The Fan and Control voltages must be the same (both must be 115VAC or both must be 230VAC). 150VA (minimum) required.

Figure 2-3 Fan Connections

115V Connections

230V Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X1

X2

(150VA minimum)

X1

X2

MN850

Installation 2-7

Image 12
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DLimited Warranty Section General InformationIntroduction Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Tools Required Mounting Instruction For tapped mounting holesMounting Instructions For clearance mounting holes AC Main Circuit Connection Descriptions UL Required Fuses for Short Circuit RatingCatalog Number Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20Three Wire Control Two Wire Control115 / 230VAC Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Password Menu Permanent Store MenuInputs Menu Outputs Menu Parameters MenuTrips Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationInput Ratings Storage ConditionsOperating Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E Remote Keypad Mounting Template 500340 810 500 250 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500