Baldor MN850, Baldor manual Advanced Menu

Page 30

Advanced Menu

Block Title

Parameter

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Advanced

Current

Rated Current – (View Only) this value is the continuous current rating of the control.

 

 

Low Current – If on, activates low current trip protection. Useful to detect a low current

 

 

condition (broken belt, coupling, pump etc.) on driven equipment.

 

 

Low Current Level – The value of the low current trip detection. Value can be 0 to 100%

 

 

of the Rated Current parameter value. Parameter 28.

 

 

Low Current Time – The number of power cycles the motor current is allowed to remain

 

 

below the low current level before a low current trip occurs. Value can be 5 to 255

 

 

cycles. Parameter 29.

 

 

C/L Time Out – If on, allows current limit time out trip (active).

 

 

Current Limit – The value of the current limit trip detection. Value can be 1 to 7.9 times

 

 

the Rated Current parameter value. Parameter 30.

 

 

Limit Time Out – The number of seconds

 

 

Value can be 0 to 255 seconds. Parameter 31.

 

 

Shearpin – If on, Shearpin protection is active. Useful to detect a high current condition

 

 

(such as a jammed conveyor or press) on driven equipment.

 

 

Shearpin Level – The value of the high current Shearpin trip detection. Value can be 1 to

 

 

5 times the Rated Current parameter value. Parameter 32.

 

 

Shearpin Time – The number of power cycles the motor current is allowed to remain

 

 

above the low shearpin level before a Shearpin trip occurs. Value can be

 

 

cycles. Parameter 33.

 

 

Overload Level – Provides overload protection for SCR’s. (Not for motor thermal

 

 

overload). The value of the overload current trip detection. Value can be 0.6 to 2

 

 

times the Rated Current parameter value. Parameter 34.

 

 

Overload Delay – A numerical value that represents the time and current characteristics

 

 

for overload integration. Value can be 10 to 140. Parameter 35.

 

 

Note: For applications that have frequent Start/Stop sequences, it is necessary to

 

 

 

 

 

 

 

 

maintain 115VAC at terminals X1 and X2. Removing 115VAC from these

 

 

 

 

 

 

 

 

terminals resets the overload delay integration to 140.

 

 

 

 

 

 

 

 

Overload Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to Trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay = 140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay = 80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay =30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay = 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload Level (Motor Current x N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optimise Rate

A numerical value that represents the rate at which the motor voltage is reduced during

 

 

optimizing. When this number is large, improves efficiency on stable loads. A lower

 

 

number for unstable loads will reduce speed variations. Value can be 4 to 30.

 

 

Parameter 19.

 

 

 

 

Kick Start

If on, Kick Start feature is active.

 

 

 

 

Kick Pedestal

For traction or “frozen” loads, this boost pulse of higher voltage helps the load to start

 

 

moving. Value can be 60% to 90% of line voltage. Parameter 13.

 

 

 

 

Kick Time

Number of cycles duration the kick pedestal voltage is applied. Value can be 10 to 40.

 

 

Parameter 14.

 

 

 

 

Dwell Time

Number of seconds that full voltage is applied to the motor before optimizing begins (if

 

 

optimizing is selected). Value can be 1 to 255. Parameter 15.

 

 

 

 

Low Volts Stop

Allows decel to zero volts (not just to the level of the start pedestal). (Sometimes helpful

 

 

for unstable loads or regeneration).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MN850

Parameter Index 4-3

Image 30
Contents Digital Soft-Start Table of Contents Appendix C Appendix aAppendix B Appendix DLimited Warranty Section General InformationIntroduction Safety Notice PrecautionsPhysical Location Section InstallationReceiving, Inspection and Storage Air Flow Clearance RequirementsCover Removal Tools Required Mounting Instruction For tapped mounting holesMounting Instructions For clearance mounting holes AC Main Circuit Connection Descriptions UL Required Fuses for Short Circuit RatingCatalog Number Baldor Control SupplyMotor Overload and Thermal Protection Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20Three Wire Control Two Wire Control115 / 230VAC Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingOverview Pre-Start ChecklistSection Operation Sure to check the following itemsKeypad Operation Start-Up ProcedureKeypad Mode Switch System Program Menu Data Status Entry Action Description Display CommentsData Entry Mode System Status Mode Description Display CommentsMenu Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorBasic Menu Section Parameter IndexMenu Descriptions Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Password Menu Permanent Store MenuInputs Menu Outputs Menu Parameters MenuTrips Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Power Off Checks Section TroubleshootingFault Trip Messages Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Relay and Contactor Coils Analog SignalsElectrical Noise Considerations Special Motor ConsiderationsSection Specifications and Product Data IdentificationInput Ratings Storage ConditionsOperating Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 CE Declaration of Conformity Wiring of Shielded Screened CablesAppendix a CE Guidelines EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E Remote Keypad Mounting Template 500340 810 500 250 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500