Baldor Baldor, MN850 manual Menu Structure Diagram

Page 21

Menu Structure

Level 0

Figure 3-2 Menu Structure Diagram

Level 1

Level 2

Level 3

ENTER

ENTER

ENTER

ENTER

Stopped and ready

Applications

Auto features

Auto features

Basic

Basic

Advanced

Advanced

Permanent store

Permanent store

Password

Password

Inputs

Outputs

Parameters

Trips

Settings

Auto Jog (Off) Auto Pedestal (Off)

Auto end start (Off) Auto stop (Off)

Auto end stop (Off) Auto bypass (On) Auto 3MC (On)

Auto off (Off)

Stop smoothing (Off)

Starting (Keypad)

Start pedestal Start time (5s)

Stop pedestal (10%)

Stop time (0s) Current limit (3.5xle)

Power on Param Protection

Save parameters Power on parameters Default parameters

Enter password Change password

Settings

Default (keypad)

Small Pump

Large Pump

Conveyor

Low Inertia Fan

High Inertia Fan

Recip Compressor

Screw Compressor

Rotary Compressor

Current Optimise rate (5) Kick start (Off)

Kick pedestal (75%) Kick time (25cycles) Dwell time (5s)

Low volts stop (On) Contactor delay (160ms) Trip sensitivity (1) Station number (1) Language (44)

Firing mode (0) * Stop Smoothing (5)

Full

Full + optimise(Preset) Start + bypass Phase loss only

Rated current (Ie) ** Low current (Off)

Low amps level (0.1xFLC) Low amps time (50cycles) C/L time out (On)

Current limit (3.5xIe) Limit time out (30s) Shearpin (On)

Shearpin level (3.125xIe) Shearpin time (100cycles) Overload level (1.1xIe)

Overload delay (140)

#

#

#

#

*The “Firing Mode” must be set to 1 for the In–Delta configuration.

**The “Rated Current” setting is for reference only and is not user adjustable.

3-4 Operation

MN850

Image 21
Contents Digital Soft-Start Table of Contents Appendix B Appendix aAppendix C Appendix DLimited Warranty Section General InformationIntroduction Precautions Safety NoticeReceiving, Inspection and Storage Section InstallationPhysical Location Air Flow Clearance RequirementsCover Removal Tools Required Mounting Instruction For tapped mounting holesMounting Instructions For clearance mounting holes AC Main Circuit Connection Descriptions UL Required Fuses for Short Circuit RatingCatalog Number Motor Overload and Thermal Protection Control SupplyBaldor Digital Soft-StartBaldor Digital In-Delta Soft-Start Connections45x20 NEC Wire Size and Protection DevicesThree Wire Control Two Wire Control115 / 230VAC 115/230VAC Top of Ramp Bypass ConnectionTo AC Input Motor Reversing ConnectionShock Mounting InstallationSection Operation Pre-Start ChecklistOverview Sure to check the following itemsKeypad Mode Switch System Program Menu Data Status Entry Start-Up ProcedureKeypad Operation Action Description Display CommentsMenu Mode System Status Mode Description Display CommentsData Entry Mode Operating ModesMenu Structure Menu Structure DiagramMenu Navigation Menu Navigation ExamplesSave Param Motor Starting Definitions Term Motor Starting Key TermsApplications Auto Features Remote Start and Running the Motor Optimising CurrentStopping the Motor Motor Stopping Definitions TermMenu Descriptions Section Parameter IndexBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Password Menu Permanent Store MenuInputs Menu Outputs Menu Parameters MenuTrips Menu Parameter Description Title Parameter Description Parameter DescriptionsRatedCurrent x Example P52 User Flags Definition Preset ValueK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Fault Trip Messages Section TroubleshootingPower Off Checks Preliminary ChecksIndication Corrective Action Troubleshooting Guide230/460VAC 3 Phase Electrical Noise Considerations Analog SignalsRelay and Contactor Coils Special Motor ConsiderationsIdentification Section Specifications and Product DataInput Ratings Storage ConditionsOperating Conditions 230V 460V 575V Size Mounting Dimensions10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Appendix a CE Guidelines Wiring of Shielded Screened CablesCE Declaration of Conformity EMC Conformity and CE MarkingControl Cable Screens Grounding EMC Installation InstructionsAppendix MN850 Appendix B Parameter Values Title Parameter Adjustable Range Factory User SettingApplications MN850 MN850 Applications B-3 Section General Information Voltage Independent Parts Description Appendix C Replacement Parts575VAC Parts Description Grounding Appendix D Voltage Surge ProtectionVoltage Surge Protection MN850 Grounded or Symbol High Resistance Ground Control EnclosureTable D-1 Baldor MOV Specifications Corner or Center-Tap Symbol Grounded Control EnclosureVoltage Surge Protection MN850 Appendix E Remote Keypad Mounting Template 500340 810 500 250  Baldor Electric Company MN850 03 C&J1500 Baldor Electric Company