Title | P# | Parameter |
|
|
|
| Description |
|
|
|
| ||||
Parameters | P51 | User Flags 1 | Note that these bits operate with P52 bit 6 (param group selector). This lets you set | ||||
Continued |
|
| a primary and secondary group value: e.g. P14: Kick Time 1 (primary); | ||||
|
|
| P82: Kick Time 2 (secondary). | ||||
|
|
|
| Definition (Preset Value) | |||
|
|
| Bit0= | Kickstart selector (0, do not select kickstart) | |||
|
|
| Bit1= | Current limit timeout (1, trip on timeout) | |||
|
|
| Bit2= | Overload selector (1, selects overload operation) | |||
|
|
| Bit3= | Shearpin selector (1, selects shearpin operation) | |||
|
|
| Bit4= | Low current selector (0, do not select low current operation) | |||
|
|
| Bit5= | Thermistor selector (0, do not select thermistor operation) | |||
|
|
| Bit6= | Not Used |
|
| |
|
|
| Bit7= | Remote input selector (1, start/stop by remote terminals) (See P52 Bit4) | |||
|
|
|
|
| |||
| P52 | User Flags 2 |
| Definition (Preset Value) | |||
|
|
| Bit0= | Low voltage stop selector (0, do not select low voltage part of stop ramp) | |||
|
|
| Bit1= | Not global enable 1 - active low (0, not active signal from terminal) | |||
|
|
| Bit2= | Not global enable 2 - active low (0, not active signal from bus) | |||
|
|
| Bit3= | Keypad Start/Stop (0, Off)- (Available when P51 Bit7=0) | |||
|
|
| Bit4= | Remote Start/Stop (0, Off)- (Available when P51 Bit7=1) | |||
|
|
| Bit5= | Main contactor selector (0, Off)- (use with a relay) | |||
|
|
| Bit6= | Parameter group selector (0, Off= Group 1) | |||
|
|
| Bit7= | Zero Start Time (0, do not use full voltage at motor start) | |||
|
|
|
|
| |||
| P53 | User Flags 3 |
| Definition (Preset Value) | |||
|
|
| Bit0= | User Flag 1 Polarity (1, positive) | |||
|
|
| Bit1= | User Flag 2 Polarity (1, positive) | |||
|
|
| Bit2= | User Current limit (0, do not request a start ramp hold) | |||
|
|
| Bit3= | User trip (0, do not request a trip) | |||
|
|
| Bit4= | Invert Controller Input (1, set point source input is inverted in servo loop) | |||
|
|
| Bit5= | Inhibit restart (0, inhibited restart control is disabled) | |||
|
|
| Bit6= | Thermal Switch 2 Enable (0, Secondary thermal control is disabled) | |||
|
|
| Bit7= | Unused |
|
| |
|
|
|
| ||||
| P54 | I/O Polarity | Determines the polarity of the digital inputs and outputs. | ||||
|
|
| A Bit set=0; is negative logic. A Bit set=1; is positive logic. | ||||
|
|
| Example: |
|
| ||
|
|
| P54, Bit0=1 (K1 mapped to Main Contactor), P57=52, | ||||
|
|
| P58=00100000 P52, Bit 5=1 will cause K1 to close. | ||||
|
|
|
| Definition (Preset Value) | |||
|
|
| Bit0= | Relay K1 (1, positive) | |||
|
|
| Bit1= | Relay K2 (1, positive) | |||
|
|
| Bit2= | Relay K3 (1, positive) | |||
|
|
| Bit3= | Relay K4 (1, positive) | |||
|
|
| Bit4= | Control Input 1 (1, positive) | |||
|
|
| Bit5= | Control Input 2 (1, positive) | |||
|
|
| Bit6= | Control Input 3 (1, positive) | |||
|
|
| Bit7= | Led (RED) Unused | |||
|
|
|
|
|
|
| |
| P55 | MAP LED | Unused |
|
|
| |
|
|
|
|
|
|
| |
| P56 | LED MASK | Unused |
|
|
| |
|
|
|
| ||||
| P57 | Map K1 To (Parameter) | The parameter number that will control Relay K1. The preset is P52: | ||||
|
|
| User Flags | ||||
|
|
| electronic transfer of the analog value.) | ||||
|
|
|
| ||||
| P58 | K1 Bit Mask (P57 bit selected for K1) | Sets the bit in the parameter selected by P57 that operates the relay | ||||
|
|
| K1 on the control card. The preset is P52:User Flags | ||||
|
|
| contactor). (P58 operates with P57). | ||||
|
|
| 7 6 | 5 | 4 3 2 1 | 0 | Bits |
|
|
| 1 0 | 0 | 0 0 0 0 | 0 |
|
|
|
| 0 1 | 0 | 0 0 0 0 | 0 |
|
|
|
| 0 0 | 1 | 0 0 0 0 | 0 (Preset) | |
|
|
| 0 0 | 0 | 1 0 0 0 | 0 |
|
|
|
| 0 0 | 0 | 0 1 0 0 | 0 |
|
|
|
| 0 0 | 0 | 0 0 1 0 | 0 |
|
|
|
| 0 0 | 0 | 0 0 0 1 | 0 |
|
|
|
| 0 0 | 0 | 0 0 0 0 | 1 |
|
|
|
|
| ||||
| P59 | Map K2 To (Parameter) | The parameter number that will control Relay K2. The preset is P8: | ||||
|
|
| Status 1. (P59 operates with P60). (Mapped to means electronic | ||||
|
|
| transfer of the analog value.) | ||||
|
|
|
|
|
|
|
|
| MN850 |