Baldor Baldor, MN850 manual Parameter Descriptions, Title Parameter Description

Page 35

Parameter Descriptions

Version 5MC

(4/2/01)

 

 

 

 

 

 

 

 

 

Title

P#

Parameter

 

 

Description

Parameter

P0

Dummy Parameter

 

Map unused bits, parameters etc.

 

P1

Station Number

 

Unused

 

 

P2

Country

 

Determines the language used by the display. 44=English.

 

P3

Software Type

 

Manufacturers product code for the Soft-Start software.

 

P4

Software Version

 

Version of the software.

Password

P5

Password Value

 

Allows you to set and enter a password.

Advanced

P6

Firing Mode

 

0= Normal motor (outside delta or star)

 

 

 

 

1= Delta (inside delta, no optimization)

 

 

 

 

2= Closed loop phase control

 

 

 

 

3= Open loop phase control

 

 

 

 

 

Basic

P7

Protection Mode

 

Determines the fault protection method.

 

 

 

 

0=

Input phase loss detection only.

 

 

 

 

64=

Full protection with full volts after top of ramp.

 

 

 

 

128=

Full protection during start then bypass (no protection)

 

 

 

 

192=

Full protection + Optimization

 

 

 

 

 

 

Parameters

P8

Status 1

 

 

Definition (Preset Value, all = 0)

 

 

 

 

Bit0=

Stopped (1=Start/stop signal inactive, SCR's Off, Main contactor open).

 

 

 

 

Bit1=

Starting (1= Starter is in Start Ramp).

 

 

 

 

Bit2=

Current Limit (1=Motor current has reached limit and is being held).

 

 

 

 

Bit3=

Top of Ramp (Full volts) (1=start ramp and current limit is complete).

 

 

 

 

Bit4=

Dwell (1=the time at the end of the start ramp when the motor is

 

 

 

 

 

held at full volts before optimizing to stabilize the load).

 

 

 

 

Bit5=

Full Conduction- (1= thyristors in continuous conduction).

 

 

 

 

Bit6=

Energy Saving (1=Motor pf is monitored and volts are adjusted to optimum)

 

 

 

 

Bit7=

Stopping (1=the stop ramp is active).

 

 

 

 

 

 

 

P9

Status 2

 

 

Definition (Preset Value, all = 0)

 

 

 

 

Bit0=

Alarm (1=fault is detected and a trip has occurred)

 

 

 

 

Bit1=

Overload Integrating (1=overcurrent is detected and is integrating)

 

 

 

 

Bit2=

Stall (1=a stall condition is detected, motor speed decreasing).

 

 

 

 

Bit3=

Forced Override (1= Optimizing not available even if selected because

 

 

 

 

 

motor current>80%FLA).

 

 

 

 

Bit4=

Noise (1=Noise on AC input power mains is detected).

 

 

 

 

Bit5=

Inhibit Start (1=Start is inhibited for a period to maintain duty cycle).

 

 

 

 

Bit6=

DC I/P level reached (1= DC > P48).

 

 

 

 

Bit7=

4-20mA I/P level reached (1= 4-20mA > P46).

 

 

 

 

 

 

 

P10

Status 3

 

 

Definition (Preset Value, all = 0)

 

 

 

 

Bit0=

K1 (1= K1

Active).

 

 

 

 

Bit1=

K2 (1= K2

Active).

 

 

 

 

Bit2=

K3 (1= K3

Active).

 

 

 

 

Bit3=

K4 (1= K4

Active).

 

 

 

 

Bit4=

Starter I/P 1 (1= Control Input1 is high).

 

 

 

 

Bit5=

Starter I/P 2 (1= Control Input2 is high).

 

 

 

 

Bit6=

Starter I/P 3 (1= Control Input3 is high).

 

 

 

 

Bit7=

Red LED status (unused)

 

 

 

 

 

Basic

P11

Start Pedestal

 

Sets the voltage level for the •Start of Voltage Ramp". Must be sufficient to allow

 

 

 

 

motor to generate a breakaway torque.

 

 

 

 

 

 

P12

Start Time

 

Sets the time allowed for motor voltage to equal line voltage.

Advanced

P13

Kick Pedestal

 

Sets the voltage level at the start of the kickstart operation.

 

P14

Kick Time

 

Sets the number of cycles that the P13 voltage is applied. Note that for

 

 

 

 

60 Hz, 40 cycles = 667ms. For 50 Hz, 40 cycles = 800ms.

 

 

 

 

 

 

P15

Dwell Time

 

Sets the dwell time allowed after top of ramp is reached.

Basic

P16

Stop Pedestal

 

Sets the drop in motor voltage for the •Stop Voltage Ramp" operation.

 

P17

Stop Time

 

Sets the ramp down time for motor stopping.

Auto Features

P18

Auto Config

 

Auto configuration flags to use with the first parameter set.

 

 

 

 

 

Definition (Preset Value)

 

 

 

 

Bit0=

Unused

 

 

 

 

 

Bit1=

Auto 3MC (1, Auto remove low volt. ramp for high start pedestal).

 

 

 

 

Bit2=

Auto Bypass (1, Enable Automatic Bypass Contactor detection).

 

 

 

 

Bit3=

Auto Jog (0, Disable auto jog detect. If 1, a stop request within .5 sec

 

 

 

 

 

of a start request is forced to 0 stop time).

 

 

 

 

Bit4=

Auto Endstop (0, Do not detect stalled motor at softstop).

 

 

 

 

Bit5=

Auto Stop (0, Do not detect variations in pf during stop smooth stall).

 

 

 

 

Bit6=

Auto Endstart (0, Do not detect full speed at start and adjust start ramp).

 

 

 

 

Bit7=

Auto Pedestal (0, Do not detect rotation at start and adjust pedestal).

 

 

 

 

 

Advanced

P19

Optimise Rate

 

Sets the optimizing response rate. This parameter helps to stabilize small slip speed

 

 

 

 

motors with low inertia loads. (4=fastest optimizing rate).

 

 

 

 

 

 

 

4-8 Parameter Index

MN850

Image 35
Contents Digital Soft-Start Table of Contents Appendix D Appendix aAppendix B Appendix CIntroduction Limited WarrantySection General Information Precautions Safety NoticeAir Flow Clearance Requirements Section InstallationReceiving, Inspection and Storage Physical LocationCover Removal Mounting Instructions For clearance mounting holes Tools RequiredMounting Instruction For tapped mounting holes AC Main Circuit Catalog Number Connection DescriptionsUL Required Fuses for Short Circuit Rating Digital Soft-Start Control SupplyMotor Overload and Thermal Protection BaldorBaldor Digital In-Delta Soft-Start Connections45x20 NEC Wire Size and Protection Devices115 / 230VAC Three Wire ControlTwo Wire Control 115/230VAC Top of Ramp Bypass ConnectionTo AC Input Motor Reversing ConnectionShock Mounting InstallationSure to check the following items Pre-Start ChecklistSection Operation OverviewAction Description Display Comments Start-Up ProcedureKeypad Mode Switch System Program Menu Data Status Entry Keypad OperationOperating Modes System Status Mode Description Display CommentsMenu Mode Data Entry ModeMenu Structure Menu Structure DiagramMenu Navigation Menu Navigation ExamplesSave Param Motor Starting Definitions Term Motor Starting Key TermsApplications Auto Features Remote Start and Running the Motor Optimising CurrentStopping the Motor Motor Stopping Definitions TermApplications Menu Section Parameter IndexMenu Descriptions Basic MenuParameter Index MN850 Advanced Menu Auto Features Menu Inputs Menu Password MenuPermanent Store Menu Trips Menu Outputs MenuParameters Menu Parameter Description Title Parameter Description Parameter DescriptionsRatedCurrent x Example P52 User Flags Definition Preset ValueK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Preliminary Checks Section TroubleshootingFault Trip Messages Power Off ChecksIndication Corrective Action Troubleshooting Guide230/460VAC 3 Phase Special Motor Considerations Analog SignalsElectrical Noise Considerations Relay and Contactor CoilsIdentification Section Specifications and Product DataOperating Conditions Input RatingsStorage Conditions 230V 460V 575V Size Mounting Dimensions10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 EMC Conformity and CE Marking Wiring of Shielded Screened CablesAppendix a CE Guidelines CE Declaration of ConformityControl Cable Screens Grounding EMC Installation InstructionsAppendix MN850 Appendix B Parameter Values Title Parameter Adjustable Range Factory User SettingApplications MN850 MN850 Applications B-3 Section General Information Voltage Independent Parts Description Appendix C Replacement Parts575VAC Parts Description Grounding Appendix D Voltage Surge ProtectionVoltage Surge Protection MN850 Grounded or Symbol High Resistance Ground Control EnclosureTable D-1 Baldor MOV Specifications Corner or Center-Tap Symbol Grounded Control EnclosureVoltage Surge Protection MN850 Appendix E 340 810 500 250 Remote Keypad Mounting Template500  Baldor Electric Company MN850 03 C&J1500 Baldor Electric Company