Baldor MN850, Baldor manual 230/460VAC 3 Phase

Page 44

 

 

Table 5-2 Troubleshooting Guide Continued

 

 

 

INDICATION

 

CORRECTIVE ACTION

 

 

Initial motor kick

Verify that AC input power and motor power wires are not reversed.

then bad start

(The motor will give an initial kick then start very roughly.)

 

 

 

Current is not

1.

Verify the current transformer connections at J3 control terminal.

displayed

2.

Verify that the soft–start control is correctly sized.

 

 

 

Motor does not

1.

Verify the Current Limit parameter value and increase if necessary.

accelerate

2.

Verify the Ramp Time parameter value and decrease if necessary.

 

3.

Excessive motor current, decrease load.

 

4.

Insufficient break away torque. Change pedestal voltage value to allow greater break away torque.

 

 

 

Fuse(s) blown

1.

Excessive start time.

 

2.

Fuse undersized. Use only specified fuses for UL short circuit current ratings (see Section 2).

 

 

Cannot change

Remote start input. Factory preset start input is Programmable Input 1 terminals S1 and S0. If a start voltage has

starting from

been applied to S1 and S0, you cannot change to Keypad until the start command is removed. Therefore,

“Remote” to

remove the start voltage from S1 and S0 and then change to keypad.

“Keypad”

 

 

 

 

 

Figure 5-1

 

230/460VAC 3 Phase

 

5MC–PCB

L1

L2

L3

 

 

 

 

5

 

 

 

 

Red

1

 

 

 

Yellow

 

 

 

2

 

 

 

 

 

 

 

Yellow

 

RUN

 

 

Red 3

 

 

 

4

 

 

3

6

 

 

 

 

Red

5

 

 

 

Yellow

TOR

 

 

6

 

 

 

 

 

Yellow

7

 

 

 

Red

 

 

 

8

 

 

 

 

 

14

Red 9

Yellow 10

Yellow

Red 1112

2

T1 T2T3

3Phase Motor

MN850

Troubleshooting 5-3

Image 44
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DIntroduction Limited WarrantySection General Information Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instructions For clearance mounting holes Tools RequiredMounting Instruction For tapped mounting holes AC Main Circuit Catalog Number Connection DescriptionsUL Required Fuses for Short Circuit Rating Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20115 / 230VAC Three Wire ControlTwo Wire Control Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Inputs Menu Password MenuPermanent Store Menu Trips Menu Outputs MenuParameters Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationOperating Conditions Input RatingsStorage Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E 340 810 500 250 Remote Keypad Mounting Template500 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500