| Table |
|
|
|
INDICATION |
| CORRECTIVE ACTION |
|
| |
Initial motor kick | Verify that AC input power and motor power wires are not reversed. | |
then bad start | (The motor will give an initial kick then start very roughly.) | |
|
|
|
Current is not | 1. | Verify the current transformer connections at J3 control terminal. |
displayed | 2. | Verify that the |
|
|
|
Motor does not | 1. | Verify the Current Limit parameter value and increase if necessary. |
accelerate | 2. | Verify the Ramp Time parameter value and decrease if necessary. |
| 3. | Excessive motor current, decrease load. |
| 4. | Insufficient break away torque. Change pedestal voltage value to allow greater break away torque. |
|
|
|
Fuse(s) blown | 1. | Excessive start time. |
| 2. | Fuse undersized. Use only specified fuses for UL short circuit current ratings (see Section 2). |
|
| |
Cannot change | Remote start input. Factory preset start input is Programmable Input 1 terminals S1 and S0. If a start voltage has | |
starting from | been applied to S1 and S0, you cannot change to Keypad until the start command is removed. Therefore, | |
“Remote” to | remove the start voltage from S1 and S0 and then change to keypad. | |
“Keypad” |
|
|
|
|
|