Baldor Baldor, MN850 manual NEC Wire Size and Protection Devices, 45x20

Page 13

Wire Size and Protection Devices

Table 2-4 Control Wire Sizes and Tightening Torques

Control

Terminal

Wire Gauge *

Terminal Torque

Size

AWG

mm2

Lb–in

Nm

 

 

L1, L2, L3, T1, T2, T3

 

 

106

12

1

(M8 Stud for Ring connector)

1/0

50

 

 

 

 

 

Earth (Ground) Terminal

106

12

 

 

 

 

(M8 Stud for Ring connector)

 

 

 

 

 

 

 

 

 

 

 

L1, L2, L3, T1, T2, T3

 

 

106

12

2

(M8 Stud for Ring connector)

(2)

(2) 120

 

 

Earth (Ground) Terminal

250MCM

106

12

 

 

 

(M8 Stud for Ring connector)

 

 

 

 

 

 

 

 

 

 

 

L1, L2, L3, T1, T2, T3

Busbar

size:

212

24

3, 4

** (Connector with two M10 holes on 30mm center)

45x20

 

 

Earth (Ground) Terminal

60x10

212

24

 

 

(M10 Stud for Ring connector)

80x10

 

 

 

 

 

 

 

 

 

S0 and S1

14 – 22

0.5 – 2.5

4.5

0.5

All

X1 and X2

14 – 22

0.5 – 2.5

4.5

0.5

K1 (11, 12, 14)

14 – 22

0.5 – 2.5

4.5

0.5

 

 

K2 (21, 22, 24)

14 – 22

0.5 – 2.5

4.5

0.5

*Use same gauge wire for Earth ground as is used for L1, L2 and L3.

**Use terminal #4–350kcmil,1 per phase (ILSCO Part No.LO–350–S, LO–600–S or LO–1000–S or equivalent).

Table 2-5 NEC Wire Size and Protection Devices

Control Rating

Input Breaker

Input Fuse (Amps)

Wire Gauge

 

Amps

(Amps)

 

 

 

 

 

Fast Acting

Time Delay

AWG

 

mm2

9

15

30

20

12

 

3.31

16

30

50

30

12

 

3.31

23

40

70

40

10

 

5.26

30

50

90

60

8

 

8.37

 

 

 

 

 

 

 

44

70

150

80

8

 

8.37

 

 

 

 

 

 

 

59

90

200

110

6

 

13.3

 

 

 

 

 

 

 

85

110

250

150

4

 

21.2

 

 

 

 

 

 

 

105

175

350

200

2

 

33.6

146

250

450

275

2/0

 

67.4

174

275

600

300

3/0

 

85.0

202

300

600

350

4/0

 

107.0

242

400

750

450

250MCM

 

127.0

300

450

900

600

350MCM

 

177.0

 

 

 

 

 

 

 

370

600

1200

700

500MCM

 

253.0

500

800

1500

900

(2) 250MCM

 

(2) 127.0

600

900

1800

1100

(2) 350MCM

 

(2) 177.0

750

1200

2500

1400

(2) 500MCM

 

(2) 253.0

900

1400

3000

1600

(2) 700MCM

 

(2) 355.0

 

 

 

 

 

 

 

1100

1600

 

2000

(3) 700MCM

 

(3) 355.0

1200

1800

 

2000

(3) 700MCM

 

(3) 355.0

 

 

 

 

 

 

 

Note: All wire sizes are based on 75° C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 40° C ambient, maximum continuous control output current and no harmonic current.

2-8 Installation

MN850

Image 13
Contents Digital Soft-Start Table of Contents Appendix B Appendix aAppendix C Appendix DSection General Information Limited WarrantyIntroduction Precautions Safety NoticeReceiving, Inspection and Storage Section InstallationPhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instruction For tapped mounting holes Tools RequiredMounting Instructions For clearance mounting holes AC Main Circuit UL Required Fuses for Short Circuit Rating Connection DescriptionsCatalog Number Motor Overload and Thermal Protection Control SupplyBaldor Digital Soft-StartBaldor Digital In-Delta Soft-Start Connections45x20 NEC Wire Size and Protection DevicesTwo Wire Control Three Wire Control115 / 230VAC 115/230VAC Top of Ramp Bypass ConnectionTo AC Input Motor Reversing ConnectionShock Mounting InstallationSection Operation Pre-Start ChecklistOverview Sure to check the following itemsKeypad Mode Switch System Program Menu Data Status Entry Start-Up ProcedureKeypad Operation Action Description Display CommentsMenu Mode System Status Mode Description Display CommentsData Entry Mode Operating ModesMenu Structure Menu Structure DiagramMenu Navigation Menu Navigation ExamplesSave Param Motor Starting Definitions Term Motor Starting Key TermsApplications Auto Features Remote Start and Running the Motor Optimising CurrentStopping the Motor Motor Stopping Definitions TermMenu Descriptions Section Parameter IndexBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Permanent Store Menu Password MenuInputs Menu Parameters Menu Outputs MenuTrips Menu Parameter Description Title Parameter Description Parameter DescriptionsRatedCurrent x Example P52 User Flags Definition Preset ValueK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Fault Trip Messages Section TroubleshootingPower Off Checks Preliminary ChecksIndication Corrective Action Troubleshooting Guide230/460VAC 3 Phase Electrical Noise Considerations Analog SignalsRelay and Contactor Coils Special Motor ConsiderationsIdentification Section Specifications and Product DataStorage Conditions Input RatingsOperating Conditions 230V 460V 575V Size Mounting Dimensions10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Appendix a CE Guidelines Wiring of Shielded Screened CablesCE Declaration of Conformity EMC Conformity and CE MarkingControl Cable Screens Grounding EMC Installation InstructionsAppendix MN850 Appendix B Parameter Values Title Parameter Adjustable Range Factory User SettingApplications MN850 MN850 Applications B-3 Section General Information Voltage Independent Parts Description Appendix C Replacement Parts575VAC Parts Description Grounding Appendix D Voltage Surge ProtectionVoltage Surge Protection MN850 Grounded or Symbol High Resistance Ground Control EnclosureTable D-1 Baldor MOV Specifications Corner or Center-Tap Symbol Grounded Control EnclosureVoltage Surge Protection MN850 Appendix E 500 Remote Keypad Mounting Template340 810 500 250  Baldor Electric Company MN850 03 C&J1500 Baldor Electric Company