General Information

Optional Remote Keypad Installation The keypad may be remotely mounted using optional Baldor keypad extension cable. Keypad assembly (white - DC00005A-01; gray - DC00005A-02) comes complete with the screws and gasket required to mount it to an enclosure. When the keypad is properly mounted to a NEMA Type 4X enclosure, it retains the Type 4X rating.

Tools Required:

• Center punch, tap handle, screwdrivers (Phillips and straight) and crescent wrench.

8-32 tap and #29 drill bit (for tapped mounting holes) or #19 drill (for clearance mounting holes).

1-1/4 standard knockout punch (1-11/16 nominal diameter).

• RTV sealant.

• (4) 8-32 nuts and lock washers.

• Extended 8-32 screws (socket fillister) are required if the mounting surface is thicker than 12 gauge and is not tapped (clearance mounting holes).

• Remote keypad mounting template. A tear out copy is provided at the end of this manual for your convenience. (Photo copy or tear out.)

Mounting Instruction:

For tapped mounting holes

 

1.

Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should

 

 

be sufficient thickness (14 gauge minimum).

 

2.

Place the template on the mounting surface or mark the holes as shown.

 

3.

Accurately center punch the 4 mounting holes (marked A) and the large

 

 

knockout (marked B).

 

4.

Drill four #29 mounting holes (A). Thread each hole using an 8-32 tap.

 

5.

Locate the 1-1/4 knockout center (B) and punch using the manufacturers

 

 

instructions.

 

6.

Debur knockout and mounting holes making sure the panel stays clean and flat.

 

7.

Apply RTV to the 4 holes marked (A).

 

8.

Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.

 

9.

From the inside of the panel, apply RTV over each of the four mounting screws

 

 

and nuts. Cover a 3/4″ area around each screw while making sure to completely

 

 

encapsulate the nut and washer.

Mounting Instructions:

For clearance mounting holes

 

1.

Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should

 

 

be sufficient thickness (14 gauge minimum).

 

2.

Place the template on the mounting surface or mark the holes as shown on the

 

 

template.

 

3.

Accurately center punch the 4 mounting holes (marked A) and the large

 

 

knockout (marked B).

 

4.

Drill four #19 clearance holes (A).

 

5.

Locate the 1-1/4 knockout center (B) and punch using the manufacturers

 

 

instructions.

 

6.

Debur knockout and mounting holes making sure the panel stays clean and flat.

 

7.

Apply RTV to the 4 holes marked (A).

 

8.

Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.

 

9.

From the inside of the panel, apply RTV over each of the four mounting screws

 

 

and nuts. Cover a 3/4″ area around each screw while making sure to completely

encapsulate the nut and washer.

MN850

Installation 2-3

Image 8
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DIntroduction Limited WarrantySection General Information Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instructions For clearance mounting holes Tools RequiredMounting Instruction For tapped mounting holes AC Main Circuit Catalog Number Connection DescriptionsUL Required Fuses for Short Circuit Rating Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20115 / 230VAC Three Wire ControlTwo Wire Control Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions TermApplications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Inputs Menu Password MenuPermanent Store Menu Trips Menu Outputs MenuParameters Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationOperating Conditions Input RatingsStorage Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E 340 810 500 250 Remote Keypad Mounting Template500 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500