Baldor MN850, Baldor Section Parameter Index, Menu Descriptions, Basic Menu, Applications Menu

Page 28

Section 4

Parameter Index

Menu Descriptions

Basic Menu

Block Title

Parameter

Description

 

 

 

Basic

Starting

Keypad – Allows motor starting and stopping by pressing Start/Stop key on keypad.

 

 

Remote – Allows motor starting and stopping by applying or removing 115VAC at

 

 

terminals S0 and S1 of the control board.

 

 

 

 

Start Pedestal

Start Pedestal Voltage – end of stop smoothing and beginning of low voltage ramp to

 

 

zero volts (if low voltage ramp is active).

 

 

 

 

Start Time

Number of seconds after the 3 cycle power–up to full motor voltage.

 

 

 

 

Stop Pedestal

Stop Pedestal Voltage is the percentage of line voltage applied to the motor after a stop

 

 

command.

 

 

 

 

Stop Time

Time in seconds after a stop command to ramp down the motor voltage (Stop Time 1 or

 

 

2). Stop Time 1 with low voltage ramp active. Stop Time 2 with no low voltage ramp.

 

 

 

 

Current Limit

Percentage of running current (P24 and P25). Adjustable from 100 – 800%.

 

 

 

 

Power on

Resets all parameter values to the values at the most recent power up. Display blinks

 

Parameter

twice to confirm reset is complete.

 

 

 

 

Protection

Full – provides shorted SCR protection during start and run, single phase protection

 

 

during start, optimizing not selected.

 

 

Full + Optimise – provides shorted SCR protection during start and run, single phase

 

 

protection during start, optimizing is selected.

 

 

Start + Bypass – provides shorted SCR protection during start, single phase protection

 

 

during start, optimizing not selected and no single phase protection during run.

 

 

This mode must be used with top of ramp bypass contactor.

 

 

Phase Loss only – shorted SCR protection during start and run is disabled, single phase

 

 

protection during start, optimizing not selected.

 

 

This mode is recommended when input power noise frequently causes nuisance trips.

 

 

 

Applications Menu

Block Title

Parameter

Description

 

 

 

Applications

Settings

Display starting method, either Keypad or Remote. Also displays operating mode

 

 

(Optimizing or Full Voltage).

 

 

 

 

Default (Keypad)

Sets starting and stopping mode to keypad, resets control and restores all parameters to

 

 

factory preset values.

 

 

 

 

Small Pump

Uses preset parameter values for typical small centrifugal pump. (P11, P12, P16, P17,

 

 

P30 and P31 values).

 

 

 

 

Large Pump

Uses preset parameter values for typical large centrifugal pump. (P11, P12, P16, P17,

 

 

P30 and P31 values).

 

 

 

 

Conveyor

Uses preset parameter values for typical conveyor. (P11, P12, P16, P17, P30 and P31

 

 

values).

 

 

 

 

Low Inertia Fan

Uses preset parameter values for Low Inertia Fan. (P11, P12, P16, P17, P30 and P31

 

 

values).

 

 

 

 

High Inertia Fan

Uses preset parameter values for High Inertia Fan. (P11, P12, P16, P17, P30 and P31

 

 

values).

 

 

 

 

Reciprocating

Uses preset parameter values for Reciprocating Compressor. (P11, P12, P16, P17, P30

 

Compressor

and P31 values).

 

 

 

 

Screw Compressor

Uses preset parameter values for Screw Compressor. (P11, P12, P16, P17, P30 and

 

 

P31 values).

 

 

 

 

Rotary Compressor

Uses preset parameter values for Rotary Compressor. (P11, P12, P16, P17, P30 and

 

 

P31 values).

 

 

 

MN850

Parameter Index 4-1

Image 28
Contents Digital Soft-Start Table of Contents Appendix a Appendix BAppendix C Appendix DSection General Information Limited WarrantyIntroduction Safety Notice PrecautionsSection Installation Receiving, Inspection and StoragePhysical Location Air Flow Clearance RequirementsCover Removal Mounting Instruction For tapped mounting holes Tools RequiredMounting Instructions For clearance mounting holes AC Main Circuit UL Required Fuses for Short Circuit Rating Connection DescriptionsCatalog Number Control Supply Motor Overload and Thermal ProtectionBaldor Digital Soft-StartIn-Delta Soft-Start Connections Baldor DigitalNEC Wire Size and Protection Devices 45x20Two Wire Control Three Wire Control115 / 230VAC Top of Ramp Bypass Connection 115/230VACMotor Reversing Connection To AC InputInstallation Shock MountingPre-Start Checklist Section OperationOverview Sure to check the following itemsStart-Up Procedure Keypad Mode Switch System Program Menu Data Status EntryKeypad Operation Action Description Display CommentsSystem Status Mode Description Display Comments Menu ModeData Entry Mode Operating ModesMenu Structure Diagram Menu StructureMenu Navigation Examples Menu NavigationSave Param Motor Starting Key Terms Motor Starting Definitions Term Applications Auto Features Optimising Current Remote Start and Running the MotorMotor Stopping Definitions Term Stopping the MotorSection Parameter Index Menu DescriptionsBasic Menu Applications MenuParameter Index MN850 Advanced Menu Auto Features Menu Permanent Store Menu Password MenuInputs Menu Parameters Menu Outputs MenuTrips Menu Parameter Description Parameter Descriptions Title Parameter DescriptionRatedCurrent x P52 User Flags Definition Preset Value ExampleK3 BIT Mask Missing. Check fuses etc Second of a start request is forced to 0 stop time Thermal Switch 2 Over temp . Prevents re-start if set , Off Section Troubleshooting Fault Trip MessagesPower Off Checks Preliminary ChecksTroubleshooting Guide Indication Corrective Action230/460VAC 3 Phase Analog Signals Electrical Noise ConsiderationsRelay and Contactor Coils Special Motor ConsiderationsSection Specifications and Product Data IdentificationStorage Conditions Input RatingsOperating Conditions 230V 460V 575V Mounting Dimensions Size10.43 265 Mounting Dimensions 151 200 100 105 12.68 24.45 10.87 Specifications and Product Data MN850 Wiring of Shielded Screened Cables Appendix a CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingControl EMC Installation Instructions Cable Screens GroundingAppendix MN850 Title Parameter Adjustable Range Factory User Setting Appendix B Parameter ValuesApplications MN850 MN850 Applications B-3 Section General Information Appendix C Replacement Parts Voltage Independent Parts Description575VAC Parts Description Appendix D Voltage Surge Protection GroundingGrounded or Symbol High Resistance Ground Control Enclosure Voltage Surge Protection MN850Corner or Center-Tap Symbol Grounded Control Enclosure Table D-1 Baldor MOV SpecificationsVoltage Surge Protection MN850 Appendix E 500 Remote Keypad Mounting Template340 810 500 250 Baldor Electric Company  Baldor Electric Company MN850 03 C&J1500