Name | Description | Options | Default |
Partial convey | When this option is enabled, the controller | disabled, | disabled |
| issues a “partial convey” alarm if it has | enabled |
|
| repeatedly attempted to convey material to the |
|
|
| station, and material has moved from the station |
|
|
| into the receiver, but the |
|
|
| sensor has never signaled that the station is full. |
|
|
| (The number of attempts is controlled by the |
|
|
| next setting.) |
|
|
| For a |
|
|
| usually be enabled. At times, you may wish to |
|
|
| disable it during operation as a stopgap |
|
|
| measure for dealing with an alarm. For a |
|
|
| station, disable this option. |
|
|
# attempts B4 alarm | Number of attempts before alarm: the number of | 3 | |
| times the controller will attempt to convey |
|
|
| material to a station before it issues a “partial |
|
|
| convey” alarm. |
|
|
| The setting for this option depends on the same |
|
|
| considerations as those given above for number |
|
|
| of attempts before a “no convey” alarm. |
|
|
Option Input |
|
|
|
Receiver low level | When this option is enabled, the controller | disabled, | disabled |
| issues a “receiver level” alarm if material in the | enabled |
|
| receiver drains below the level of the receiver’s |
|
|
|
|
| |
| Enable this option if and only if your facility has |
|
|
| installed a |
|
|
| receiver. At times, you may wish to disable it |
|
|
| during operation as a stopgap measure for |
|
|
| dealing with an alarm. |
|
|
Bypass switch | When this option is enabled, a switch at the |
|
|
| station is used to disable/”bypass” the station. |
|
|
Grinder empty | When this option is enabled, a proximity switch |
|
|
| is used to verify that material is present in the |
|
|
| grinder bin. The station will only be conveyed to |
|
|
| when the receiver is empty and the grinder bin |
|
|
| has material. |
|
|
Grinder empty with | When this option is enabled, alarm monitoring is |
|
|
Alarm | added to the grinder empty option described |
|
|
| above. If the grinder bin has material and the |
|
|
| receiver is full, a “grinder full” alarm is |
|
|
| generated. |
|
|
Option output |
|
|
|
Local alarm | When this option is enabled, the controller turns | disabled, | disabled |
| on the local alarm light for any alarm at this | enabled |
|
| specific station. |
|
|
| Enable this option if and only if your facility has |
|
|
| installed a local alarm light for this station. |
|
|
Blow back | When this option is enabled, the controller | disabled, | disabled |
| periodically sends compressed air backward | enabled |
|
| through the station’s air filter to dislodge |
|
|
| accumulated dust and debris. |
|
|
| Enable this option if and only if the station has |
|
|
| the equipment for compressed air filter cleaning. |
|
|
| Chapter 6: Configurable Settings | 66 |