10.When you enter the second pump number, the controller checks to make sure that both pumps are offline and that the standby pump has no stations assigned to it. If these conditions are not all met, error messages appear on the screen instead of a Press To Move Stations button. If you get an error message, first check to make sure that you have entered the correct numbers and reenter if necessary.
If the error message tells you to disable the source pump and/or the standby pump, touch Return at this screen, then Pumps at the Pump n Setup screen. Take the pumps offline and then return to the Transfer to Standby Pump screen.
If the error message tells you that the standby pump has stations assigned, you must either use a different standby pump or you must remove the pump assignment for all stations assigned to the standby pump. To remove the assignments, touch Return at this screen, then Stations at the Pump n Setup screen.
Hold a station icon to go to its Station Operator screen, then touch Setup to go to the Station n Setup screen. Use ◄ Back. and Next ► to review all pump assignments and, where necessary, choose Assigned to Pump x to set station assignments to 0 (unassigned). Then return to the Transfer to Standby Pump screen.
1.Touch Transfer To Standby Pump.
“Transfer in Progress” appears briefly on the screen, followed by “Transfer Complete,” in place of the Transfer To Standby Pump button. The controller switches the setting for Source Pump to the new pump and switches the setting for Standby Pump to 0 (unassigned).
2.Touch Return.
The Pump n Setup screen appears.
3.Touch Pumps.
The Pump Status screen appears.
4.Put the standby pump online by briefly touching its icon.
The icon changes color to show the new status, and the system begins using the pump. In addition, all Station n Operator and Setup screens show the new pump assignment.
When the failed pump is operational again, you can repeat this process, this time using the standby pump’s number as the setting for Source Pump the repaired pump’s number as the setting for Standby Pump.