10.When you enter the second pump number, the controller checks to make sure that both pumps are offline and that the standby pump has no stations assigned to it. If these conditions are not all met, error messages appear on the screen instead of a Press To Move Stations button. If you get an error message, first check to make sure that you have entered the correct numbers and reenter if necessary.

If the error message tells you to disable the source pump and/or the standby pump, touch Return at this screen, then Pumps at the Pump n Setup screen. Take the pumps offline and then return to the Transfer to Standby Pump screen.

If the error message tells you that the standby pump has stations assigned, you must either use a different standby pump or you must remove the pump assignment for all stations assigned to the standby pump. To remove the assignments, touch Return at this screen, then Stations at the Pump n Setup screen.

Hold a station icon to go to its Station Operator screen, then touch Setup to go to the Station n Setup screen. Use ◄ Back. and Next ► to review all pump assignments and, where necessary, choose Assigned to Pump x to set station assignments to 0 (unassigned). Then return to the Transfer to Standby Pump screen.

1.Touch Transfer To Standby Pump.

“Transfer in Progress” appears briefly on the screen, followed by “Transfer Complete,” in place of the Transfer To Standby Pump button. The controller switches the setting for Source Pump to the new pump and switches the setting for Standby Pump to 0 (unassigned).

2.Touch Return.

The Pump n Setup screen appears.

3.Touch Pumps.

The Pump Status screen appears.

4.Put the standby pump online by briefly touching its icon.

The icon changes color to show the new status, and the system begins using the pump. In addition, all Station n Operator and Setup screens show the new pump assignment.

When the failed pump is operational again, you can repeat this process, this time using the standby pump’s number as the setting for Source Pump the repaired pump’s number as the setting for Standby Pump.

24-Pump, 128-Station Controller

Chapter 4: Operation

61

Image 62
Contents SCC 24-Pump 128-Station Controller Parts and Service Department Shipping Information Table of Contents Maintenance Safety Symbols Used in this Manual SafetyHow to Use This Manual Wear Safety Glasses and Work Gloves Operator Responsibility ResponsibilityGeneral Responsibility Maintenance Responsibility Reporting a Safety DefectFunctional Description Standard FeaturesMechanical Features Models Covered in This ManualElectrical Features Optional FeaturesSafety Devices and Interlocks Controller FeaturesFail Safe Operation Safety Circuit StandardsSafety Device Lock-Outs Uncrating InstallationSystem Installation Overview Mounting the Control PanelElectrical Connections Making Control Panel Power Drop Wiring ConnectionsInstalling KwikLink Cable Running KwikLink CablesSetting Up and Installing Mounting Plates Setting Up Mounting PlatesInstalling Assembled Mounting Plates Terminating Cable RunsInstalling Inside KwikLink Connectors with Blank Caps Discard the standard resistor cap to eliminate confusionArmorBlock Address Ranges Addressing and Installing ArmorBlocksAddressing ArmorBlocks Setting ArmorBlock Addresses Using seal block to pierce cable Installing KwikLink Connectors Connecting the Controller to the Network Connecting the Remote Interface to the Main ControllerPage Connecting the Power Supply Enclosure to the Network Proper Controller and Remote Interface ConnectionsPage Proper Power Supply Enclosure Connections Connecting Vacuum Receivers to the Network24/128 8-Connector ArmorBlock Connections Proper Vacuum Receiver Connections Connecting Vacuum Pumps and Filter Chambers to the Network Connecting Vacuum PumpsProper Vacuum Pump Connections, Standard XPD/XPC Pumps Proper Vacuum Pump Connections, Xpdb Pump Connecting Filter Chambers Proper Filter Chamber Connections, Blowback Proper Filter Chamber Connections, Implosion Type Connecting Central Alarms to the Network Proper Central Alarm Connections Setup Connector ArmorBlock Connections for Central AlarmsSetting Up the System Setting the Number of Stations and the Number of PumpsNaming Purge Valves and Materials Setting the Date/TimeChecking Addressing and Wiring for System Components Setting Up Alarm Silences Alarm Horn Silence Setting Up Pump StagingSetting Up Stations Setting Up a Single StationNaming Stations Copying Settings from One Station to Others To copy the selected station’s settings to one other stationSetting Up Pumps Setting Up a Single PumpPage Copying Settings from One Pump to Others Naming PumpsTo copy the selected pump’s settings to one other pump To copy the current pump’s settings to all other pumpsFinishing Setup Setting Up Passwords Password Duration Save/Restore SettingsInitial Startup Starting and Stopping the System OperationOverview Basic Tasks Reviewing Station StatusReviewing Pump Status Color Label DescriptionLogging On and Logging Off Enter the alphanumeric password Enabling and Disabling Stations and PumpsNavigating among the Station Operator Screens Reviewing and Adjusting Basic Station SettingsReaching and Reading the Station Operator Screens Adjusting Convey Time and Dump Delay Activating and Stopping Priority Convey for a StationChanging the Mixture for a Remote Proportioning Valve Transferring Stations to a Standby Pump Reviewing and Resetting a Pump Hour MeterAdvanced Tasks Page Page Silencing Alarms AlarmsReviewing Alarms Corrective Maintenance MaintenancePreventative Maintenance Network Scanner Module ConsiderationsMemory Module Considerations Configurable SettingsOptions for Station Setup Name Description Options Default Conveying Options Option Input Pump, 128-Station Controller Configurable Settings Pump, 128-Station Controller Configurable Settings Options for Pump Setup Pump, 128-Station Controller Configurable Settings Troubleshooting General TroubleshootingStation Alarms Alarm message Possible causePump, 128-Station Controller Troubleshooting Pump Alarms System AlarmsOptional Components WarrantyAppendix Drawings and Diagrams 24-Pump, 128-Station Controller with 10 DisplaySpare Parts List Typical System Installation LayoutCredit Returns Warranty ReturnsReturned Material Policy Controller Identification Serial Number Tag Safety Tag InformationController Safety Tags Parts Department Service DepartmentTechnical Assistance Contact Information Sales Department