Alliance Laundry Systems PHM798N, PHM802N Do not use a phase adder on any variable- speed machine

Page 49

On variable-speed models, the AC drive provides thermal overload protection for the drive motor. However, a separate three-phase circuit breaker must be installed for complete electrical overload protection. This prevents damage to the motor by disconnecting all legs if one should be lost accidentally. Check the serial plate on the back of the washer-extractor for recommended circuit breaker requirements size.

Specifications and Dimensions

WARNING

Electrically heated machines DO NOT require dual power sources. Do not connect customer power or customer load to the Internal Load Distribution terminal block. Refer to the machine electrical schematic for details.

IMPORTANT: Do NOT use fuses in place of a circuit breaker.

CAUTION

2

W759

L1

L2

Do not use a phase adder on any variable- speed machine.

SW037

The washer-extractor should be connected to an individual branch circuit not shared with lighting or other equipment.

The connection should be shielded in a liquid-tight or approved flexible conduit with proper conductors of correct size installed in accordance with the National Electric Code or other applicable codes. The connection must be made by a qualified electrician using the wiring diagram provided with the washer- extractor, or according to accepted European standards for equipment labeled with the CE mark.

Refer to serial plate for recommended circuit breaker size and determine wire size based on local code requirements.

Refer to serial plate for recommended wire sizes for runs up to 50 feet (15.24 meters). Use next larger size for runs of 50 to 100 feet (15.24 to 30.48 meters). Use 2 sizes larger for runs greater than 100 feet (30.48 meters).

For personal safety and for proper operation, the washer-extractor must be grounded in accordance with state and local codes. If such codes are not available, grounding must conform with the National Electric Code, article 250 (current edition) or accepted European standards for equipment labeled with the CE mark. The ground connection must be made to a proven earth ground, not to conduit or water pipes. Refer to Figure 25 and 26.

1L3

SERVICE

CHASIS

GROUND

3

TB1

MACHINES WITH ELECTRIC HEAT

PHM

 

 

PHM700N

1Grounding Lug: Connect to proven earth ground

2Customer Input Power Terminals

3Internal Load Distribution - DO NOT connect customer power source or load.

Figure 25

1

SERVICE

CHASIS

GROUND

2

L1

L2

L3

TB1

MACHINES WITHOUT ELECTRIC HEAT

P

 

 

PHM721N

1Grounding Lug: Connect to proven earth ground

2Customer Input Power Terminals

Figure 26

F8138601

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

47

Image 49
Contents Washer-Extractors Page Contents Important Safety Instructions Explanation of Safety MessagesSafety Information Safety Decals Operator Safety Environmental Conditions Safe Operating EnvironmentMachine Location AC Inverter Drive Input and Output ServicesModel Identification IntroductionCustomer Service Replacement PartsDelivery Inspection Name plate LocationModel Number Familiarization Guide Models Starting 4/1/09 0001Wash Cylinder Information Weight And Shipping InformationDoor Opening Information Drive Train InformationDirect Steam Heating Optional Balance DetectionElectrical Heating Optional Overall width, in. mm MED Specifications and Dimensions Machine DimensionsCrush hazard Uwtv Models Through 3/31/09UW35TV UW125TV Models UW150TV Models Dimension 35 125 Models Models UW Design 3 Models starting 10/4/10 Refer to and Figure Base BA Base Overall PHM807N Machine Foundation Requirements Proceed to Machine Mounting and Grouting section Concrete Foundation Pad InstallationLength for ONE Machine Floor Load Data 1272 1442 Speed 1745 2392 Speed 1797 2342 10.4 Mounting Bolt Installation Requirements Machine Mounting and Grouting Speed Models only Mounting Bolt Hole LocationsVARIABLE-SPEED Model Front of Machine 80 / 100 Models 1181 mm 178 mm 254 mm Model 35 2-SPEED Model Grout PlacementFor UniLinc Models, Navigate to the Inputs Outputs Menu Gap Setting for Vibration SwitchPound Model 60, 80, 100 and 125 Pound Models Design 1 150 Pound Model Drain Connection Requirements Drain Trough ConfigurationDrain Information Specifications 100 125 150 Water Connection Water Supply Information Specifications 80/100 125/150Air Cushions Risers 50Hz Conversion Electrical Installation RequirementsDo not use a phase adder on any variable- speed machine Specifications and Dimensions Cycle CodeM30 Control Models only Steam Supply Information 100 125/150 Steam Requirements Steam Heat Option OnlyChemical Injection Supply System Chemical Injection Supply System Connecting External Liquid Supplies to the Washer-ExtractorPHM553N External Supplies Chemical Injection Using Internal 24VAC Control Transformer Chemical injection Using External AC Power Source External Supply Signals ES1 Power supply Supply 1 Signal K1 Contact