English
1.Only rigid metal duct work should be used.
2.Venting vertically through a roof may expose the exhaust system to down drafts causing an increase in vent restriction.
3.Running the exhaust system through an uninsulated area may cause condensation and faster accumulation of lint.
4.Compression of crimping of the exhaust system will cause an increase in vent restriction.
5.In Canada, that only those
6.In Canada, that the exhaust duct shall be 102 mm in diameter. In the United States, the required exhaust duct diameter.
The exhaust system should be inspected and cleaned a minimum of every 12 months with normal usage. The more the dryer is used the more often you should check the exhaust system and vent hood for proper operation.
Side and Bottom Exhaust
For your convenience, your dryer can be exhausted through the side or the bottom. If you need to change the exhaust on the dryer to the side or the bottom of the cabinet, you will need to order the exhaust kit from your Haier dealer or call 1-
RECOMMENDED MAXIMUM
Exhaust Hood Types
Recommended
Use only for short
run installations
|
|
|
|
|
No. of 90º | Rigid Metal | Rigid Metal | ||
elbows |
|
|
|
|
0 | 90 | ft. | 60 | ft. |
1 | 60 | ft. | 45 | ft. |
2 | 45 | ft. | 35 | ft. |
3 | 35 | ft. | 25 | ft. |
The total length of flexible metal duct shall not exceed 94 inches.
8