Xantrex Technology 809-0915 manual Type 11 Connection Diagram

Page 35

Xanbus Automatic Generator Start Installation

Type 11

Type 11 is a two-wire run mode configuration. It requires only two wires and one relay to control the generator. Relay 1 closes momentarily once to start the generator, and closes momentarily again to stop the generator.

AGS Harness W ires

 

Generator W ires

 

12

 

GENERATOR RUN SIGNAL

 

13

 

GENERATOR RUN SIGNAL RETURN

Relay 1

14

5A fuse

RUN

16

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 19 Type 11 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

MomentaryRun

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

10 s

Crank retry time

15 s

Gen Cool Down

30 s

 

 

Relay Function

Preset Configuration Setting

 

 

Gen Spin Down

3 s

Shutdown bypass time

0 s

Start tries

3

 

 

975-0082-01-01

25

Image 35
Contents Xanbus Automatic Generator Start AGS Page Document Part Number TrademarksExclusion for Documentation Date and RevisionAudience About This GuidePurpose ScopeRelated Information Reference Important Safety InstructionsRestrictions on USE FCC Information to the UserPage Contents Page Xanbus Automatic Generator Start AGS Basic Function IntroductionSystem Requirements Functions AGS unit Material ListXanbus-Enabled Products and Accessories Front panel features FeaturesXanbus Bottom panel featuresChoosing a Location Xanbus Automatic Generator Start InstallationMaterials and Tools Required Shock and Energy Hazards Routing ConnectionsMounting the Unit Installation OverviewCircuit Parameter Circuit Maximum Wiring to the 20-contact ConnectorFt m Over 30 ft m To install the AGS using the wiring harnessXanbus Automatic Generator Start Installation Connecting the Generator Type Relay Function Preset Configuration SettingType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Relay Function Type 5 Connection DiagramType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Number Function Wire Color Connecting the Thermostats optionalWire Connecting an External Shutdown optional Connecting an External Manual ON/OFF Switch optionalWire Wiring Harness Number Function Wire Color Connecting an External ON/OFF LEDExternal ON/OFF Switch and LED Wiring Diagram To connect the wiring harness to the AGS Connecting the Wiring Harness to the AGSConnecting the AGS to the Xanbus Network Connecting the Xanbus System Control Panel SCP Verifying Power Is AvailableOverview Configuration of the Xanbus AGSTo change operational settings on the AGS Menu Accessing the AGS MenuXanbus Automatic Generator Start AGS Menu Xanbus AGS Menu To configureAGS Configuration Menu Contents Value Description Configuration MenuQT En QT Begin Gen Type QT EndDescription Cfg Trigger Start DCV 30 sec Values DefaultStart DCV 15 min Start DCV 24 hr Start DCV 2 hrStop Absorb Stop FloatStop Temp2 Temp1Start Load Value DefaultLoad Stop Load Starter Cool Down Cfg GenGen Spin Down Gen Cool DownExercise Per Max Run TimeExercise Time Exercise DurGen Run Hold Time Relay3Preheat Time Crank DelayCrank Time Crank Retry TimeGen Start Tries GenMode Restore DefaultsAutomatic Mode Manual Off Mode Manual On ModeView Event Log View Fault LogMode View Device InfoItems User SettingsOperation of the Xanbus AGS Accessing the AGS Home ScreenTo start the generator manually Starting and Stopping the GeneratorTo enable Quiet Time Using Quiet TimeModes of Operation Putting the AGS in Standby ModeTo return the AGS to Operating Mode Returning the AGS to Operating ModeTo view a message from a fault list or warning list TroubleshootingTroubleshooting AGS Warning Messages AGS Fault Messages Fault Reference TableRegulatory Approvals SpecificationsElectrical Specifications Environmental SpecificationsDimensions Weight Mounting Connectors Physical SpecificationsWarranty Warranty and Return InformationDisclaimer Warranty and Return InformationReturn Procedure Return Material Authorization PolicyInformation About Your System Generator Starting Types Recommended FeaturesAppendix a Generator Auto Start Requirements and Types Three-Wire Onan Two WireThree-Wire Automotive RunMode Appendix B Relay TimingMomentaryRun Mode Timing Diagram MomentaryRun ModeGlowStop Mode Timing Diagram GlowStop ModeStartStop Mode Timing Diagram StartStop ModePulseStop Mode Timing Diagram PulseStop ModePulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc