Xantrex Technology 809-0915 Starting and Stopping the Generator, To start the generator manually

Page 75

Operation of the Xanbus AGS

Starting and Stopping the Generator

Use the AGS to start or stop the generator manually using the Xanbus System Control Panel (SCP) or automatically in response to an electrical system condition.

To set the AGS to start and stop the generator automatically:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [Automatic].

3.Press Enter.

To start the generator manually:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [ManualOn].

3.Press Enter.

To stop the generator manually:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [ManualOff].

3.Press Enter.

IMPORTANT: To avoid AGS faults, try not to combine automatic and external manual starts and stops.

When the generator has been started automatically, allow it to stop automatically unless a situation occurs that requires the generator to be stopped urgently.

Likewise, if the generator has been started manually, ensure that it is stopped manually. Only the "Max Run Time" setting can automatically stop the generator after it has been started manually.

FSW System Home Screen

 

Select Device Menu

AGS Menu

 

 

System Status

 

 

 

 

Select Device

 

XAGS 00: Setup

 

Battery

20.4A

53.9V

 

 

 

System Settings

GenMode

[ManualOff]

 

BatLev

 

 

 

E--F

 

 

 

FSW3012

Mode

[Operating]

 

Load

 

 

 

1235W

 

 

 

EMS

 

 

Clear Faults Warnings

 

AC1

1150W

3202V

 

 

 

XAGS

 

 

 

View Device Info

Menu

Figure 34 Starting and Stopping the Generator

975-0082-01-01

65

Image 75
Contents Xanbus Automatic Generator Start AGS Page Document Part Number TrademarksExclusion for Documentation Date and RevisionAudience About This GuidePurpose ScopeRelated Information Reference Important Safety InstructionsRestrictions on USE FCC Information to the UserPage Contents Page Xanbus Automatic Generator Start AGS Basic Function IntroductionSystem Requirements Functions AGS unit Material ListXanbus-Enabled Products and Accessories Front panel features FeaturesXanbus Bottom panel featuresXanbus Automatic Generator Start Installation Materials and Tools RequiredChoosing a Location Shock and Energy Hazards Routing ConnectionsMounting the Unit Installation OverviewCircuit Parameter Circuit Maximum Wiring to the 20-contact ConnectorFt m Over 30 ft m To install the AGS using the wiring harnessXanbus Automatic Generator Start Installation Connecting the Generator Type Relay Function Preset Configuration SettingType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Relay Function Type 5 Connection DiagramType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Connecting the Thermostats optional WireNumber Function Wire Color Connecting an External Shutdown optional Connecting an External Manual ON/OFF Switch optionalWire Wiring Harness Number Function Wire Color Connecting an External ON/OFF LEDExternal ON/OFF Switch and LED Wiring Diagram To connect the wiring harness to the AGS Connecting the Wiring Harness to the AGSConnecting the AGS to the Xanbus Network Connecting the Xanbus System Control Panel SCP Verifying Power Is AvailableOverview Configuration of the Xanbus AGSTo change operational settings on the AGS Menu Accessing the AGS MenuXanbus Automatic Generator Start AGS Menu Xanbus AGS Menu To configureAGS Configuration Menu Contents Configuration Menu QT EnValue Description QT Begin Gen Type QT EndDescription Cfg Trigger Start DCV 30 sec Values DefaultStart DCV 15 min Start DCV 24 hr Start DCV 2 hrStop Absorb Stop FloatStop Temp2 Temp1Value Default LoadStart Load Stop Load Starter Cool Down Cfg GenGen Spin Down Gen Cool DownExercise Per Max Run TimeExercise Time Exercise DurGen Run Hold Time Relay3Preheat Time Crank DelayCrank Time Crank Retry TimeGen Start Tries Restore Defaults Automatic ModeGenMode Manual Off Mode Manual On ModeView Event Log View Fault LogMode View Device InfoItems User SettingsOperation of the Xanbus AGS Accessing the AGS Home ScreenTo start the generator manually Starting and Stopping the GeneratorTo enable Quiet Time Using Quiet TimeModes of Operation Putting the AGS in Standby ModeTo return the AGS to Operating Mode Returning the AGS to Operating ModeTo view a message from a fault list or warning list TroubleshootingTroubleshooting AGS Warning Messages AGS Fault Messages Fault Reference TableRegulatory Approvals SpecificationsElectrical Specifications Environmental SpecificationsDimensions Weight Mounting Connectors Physical SpecificationsWarranty Warranty and Return InformationDisclaimer Warranty and Return InformationReturn Procedure Return Material Authorization PolicyInformation About Your System Recommended Features Appendix a Generator Auto Start Requirements and TypesGenerator Starting Types Three-Wire Onan Two WireThree-Wire Automotive RunMode Appendix B Relay TimingMomentaryRun Mode Timing Diagram MomentaryRun ModeGlowStop Mode Timing Diagram GlowStop ModeStartStop Mode Timing Diagram StartStop ModePulseStop Mode Timing Diagram PulseStop ModePulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc